Carrier fault codes
79 codes from Carrier plates on FieldBench. Same number on another maker is a different code.
The list stays open.
- Protect
0-10V
VFD speed reference
Drive is enabled but stays at min Hz or 0 because analog / serial speed is missing.
3 plates
- Protect
2-flash
IGC 2-flash — example
Example on most Carrier/Bryant packaged CES IGC stickers: pressure switch / draft did not make. Confirm the sticker in THIS heat section — revisions differ.
2 plates
- Protect
3-flash
IGC 3-flash — example
Example on many CES rooftop IGC stickers: limit open. Confirm THIS sticker.
2 plates
- Hazard
4-flash
IGC 4-flash — example
Example: rollout / aux limit on many CES stickers; consecutive limit on others. Read THIS IGC.
2 plates
- Lockout
6-flash
IGC 6-flash — example
Example on many CES rooftop IGCs: ignition lockout after retries. Confirm THIS sticker.
2 plates
- Lockout
8-flash
IGC 8-flash — example
Example: internal control / valve circuit on current CES rooftop stickers. Power-cycle once; if 8-flash returns, valve ohms then IGC.
2 plates
- Status
11
No stored history
Memory empty or power was cycled.
7 plates
- Status
12
Blower on after power-up
Powered up on a W call.
7 plates
- Lockout
13
Limit lockout
Hardened 33. Limit/rollout stayed open.
7 plates
- Protect
13 / 33
Limit / lockout
Airflow or rollout. 13 is the hardened 33.
1 plate
- Lockout
14
Ignition lockout
Hardened 34. Auto-reset ~3 h.
7 plates
- Lockout
14 / 34
Ignition
No flame prove. 14 is the hardened 34.
1 plate
- Lockout
21
Gas-heat lockout / model plug
Valve relay fault, or missing/wrong model plug on boards that use one.
7 plates
- Hazard
22
Flame with valve off
Flame sense while GV de-energized.
7 plates
- Lockout
23
PS did not open
Draft switch still made when it should be open.
7 plates
- Protect
24
Secondary fuse open
24 V fuse on the IFC.
13 plates
- Lockout
31
Metal-vent draft / inducer
Category I draft will not prove. NEVER a PVC condensate trap.
10 plates
- Lockout
31 / 32
Low vs high pressure switch
Two-stage draft path. 31 is the active-stage / draft prove; 32 is low-fire PS. Unlike 59MN7, these are discrete switches.
2 plates
- Lockout
31 / 42
Pressure / inducer band
Modulating inducer did not hit the pressure band for the commanded firing rate. Not a discrete two-stage PS.
1 plate
- Lockout
32
32 on Comfort 96 — the only PS
If this door card lists 32, it is the same single draft switch as 31 — not 59TP6 low-fire and not a missing high-fire hose. One switch, one hose.
5 plates
- Protect
33
Limit or rollout open
Airflow or flame-containment. Dirty A-coil on an 80% is the winter/summer crossover call.
7 plates
- Protect
33 / 13
Limit
Airflow or flame-containment. 13 is the hardened 33.
5 plates
- Lockout
34
Ignition prove fail
Trial without flame sense. Repeats → 14.
7 plates
- Lockout
34 / 14
Ignition
HSI / gas / rod. 14 is the hardened 34.
5 plates
- Lockout
41
Blower RPM out of band
Infinity VS motor not at commanded CFM.
7 plates
- Lockout
41 / 44
Blower RPM / calibration
VS motor vs setup.
1 plate
- Lockout
42
Inducer RPM out of band
Inducer not at commanded speed.
2 plates
- Lockout
43
PS tubing / drain
Blockage or disconnected hose.
2 plates
- Protect
44
Blower calibration
CFM learn failed.
2 plates
- Lockout
45
Control lockout
IFC parked itself.
5 plates
- Hazard
A2L
A2L / mitigation
Leak sensor or mitigation input on an R-454B cabinet.
1 plate
- Lockout
ABCD
Communication
Wall control or outdoor dropped off the bus.
5 plates
- Protect
ACT ERR
ACT ERROR (JADE LCD example)
JADE LCD: ACT ERROR / ACT RANGE. Actuator did not follow command. Feedback pot off the shaft is the weekly.
3 plates
- Protect
Cap
Dual run capacitor
HERM and/or FAN section out of rating. Single-stage Comfort dies this way all summer.
6 plates
- Protect
Charge
Charge (SH piston / SC TXV)
Wrong charge method is as common as wrong charge.
6 plates
- Protect
CO2 ERR
CO2 SENS ERR (JADE LCD example)
JADE LCD: CO2 / SENS ERR. DCV sensor failed or the 0–10 V input is floating. Damper holds open; compressor never runs.
3 plates
- Lockout
COMM
ABCD / outdoor drop
Drive or bus. Wall control loses the outdoor.
6 plates
- Lockout
COMM OUT
No communication with outdoor
Outdoor dropped off ABCD.
3 plates
- Lockout
Contactor
Contactor / coil
Will not pull, chatters, or is welded.
9 plates
- Protect
Defrost
Defrost fault
Stuck in defrost or never defrosts.
1 plate
- Hazard
Draft / PS lockout
Will not prove / fails combustion
On this family that is often a restricted secondary, not a 59TP6 trap lecture alone.
1 plate
- Protect
Drain
Condensate / float
Float switch or tripped condensate opened 24V.
3 plates
- Protect
Econo
Economizer FDD
Start here when the hood is the complaint. Title 24 FDD classes: sensor, not-economizing, false-economizing, damper not modulating, excess OA.
3 plates
- Protect
EH
Electric heat
Strips not coming on, or on when they should not.
1 plate
- Protect
Enable
VFD enable missing
Drive has line voltage but will not run — the unit board never enabled it.
3 plates
- Protect
Excess OA
Excess outdoor air
Damper open past the commanded minimum with no economizer or DCV request.
3 plates
- Protect
False econ
Economizing when it should not
Damper open with OA above changeover. Space hot, high OA bills, or wet coil.
3 plates
- Lockout
Fan prove
Indoor fan proving
Controller did not see blower current / pressure.
3 plates
- Protect
Flame
Flame sense
Flame present then dropped, or µA too low to prove.
2 plates
- Protect
FREEZE
FREEZING (JADE LCD example)
JADE LCD: FREEZING. Mixed air below the low-limit. Damper drives shut; mechanical cool may lock.
3 plates
- Hazard
GF
GF — ground fault
Keypad example: GF. Drive sees current to ground on the motor leads.
3 plates
- Lockout
HPS
High pressure switch open
Outdoor HPS opened — coil circuit is dead. Not an inverter pressure fault and not an L-code.
9 plates
- Lockout
HPS / LPS
Pressure protection
Still real on an inverter.
3 plates
- Lockout
Ignition
Ignition lockout
Trial for ignition failed after the IGC retries.
2 plates
- Lockout
Inverter
Drive overcurrent / overheat
L5/L4-class faults on the drive.
3 plates
- Lockout
LED off
IGC dark
No 24V at the ignition control, or the module is dead.
2 plates
- Protect
Limit
Limit / aux limit
Heat-exchanger or supply limit opened.
2 plates
- Protect
Limit / rollout
Overheat or flame containment
Restricted secondary raises head and can open rollout / limit.
1 plate
- Protect
Limp
VFD limp / min Hz — fan prove
Drive is running too slow to close the prove switch, so the unit board reports fan fail. Reliatel example: Fan Fail with the drive still at min Hz.
3 plates
- Lockout
LPS
Low pressure / freeze
Suction dropped out the low-pressure switch.
3 plates
- Protect
MA ERR
MA SENS ERR (JADE LCD example)
JADE two-line LCD: MA / SENS ERR. Mixed-air sensor failed. This one alarms immediately on power-up — others wait the 60-minute setup window.
3 plates
- Protect
MISMATCH
Equipment ID / size mismatch
Wall-control setup indoor/outdoor size does not match the device on the bus. A setup, not a pressure switch.
1 plate
- Protect
No mod
Damper not modulating
Damper is two-position (0 or 100) instead of tracking 2–10 V. Title 24 FDD class.
3 plates
- Protect
Not econ
Not economizing when it should
OA is in the free-cooling window and the damper stayed shut. Title 24 FDD class.
3 plates
- Protect
OA ERR
OA SENS ERR (JADE LCD example)
JADE LCD: OA / SENS ERR (or OA SYLK ERR). Outside-air thermistor failed or lost SYLK. Board thinks the roof is 20 °F or 120 °F.
3 plates
- Lockout
oC
oC / OC — overcurrent
Keypad example: oC (Yaskawa) or OC. Output current trip. Locked rotor, dirty filters, or FLA set too low.
3 plates
- Protect
ODF
Outdoor fan fail
Fan not turning. Compressor may still run and then HPS.
6 plates
- Protect
oH
oH — heatsink overtemp
Keypad example: oH. Drive thermal trip.
3 plates
- Lockout
ov
ov / OU — overvoltage
Keypad example: ov (Yaskawa) or OU. DC bus high. Usually regen on decel, not a new drive.
3 plates
- Lockout
PF
PF — input phase loss
Keypad example: PF. Missing or imbalanced incoming phase.
3 plates
- Lockout
Phase
Phase loss / rotation
Three-phase monitor opened.
3 plates
- Protect
PS
Pressure switch
Inducer ran (or should have) and the draft switch did not make.
2 plates
- Protect
RA ERR
RA SENS ERR (JADE LCD example)
JADE LCD: RA / SENS ERR. Return-air thermistor failed. Differential / enthalpy changeover compares OA to RA.
3 plates
- Hazard
Rollout
Rollout / flame spill
Flame left the burner box.
2 plates
- Lockout
RV
No shift
Reversing valve did not stroke.
1 plate
- Hazard
Smoke
Smoke / firestat
Supply or return smoke detector, or a firestat, has the unit locked out.
3 plates
- Hazard
Unexpected
Flame out of sequence
Flame with no trial.
2 plates
- Lockout
Uv
Uv / LU — undervoltage
Keypad example: Uv (Yaskawa) or LU. DC bus dropped. Incoming power or a missing phase.
3 plates
- Lockout
VFD
VFD / indoor-fan drive
The indoor fan is a drive, not a contactor + cap. Type the keypad string: oC, Uv, ov, GF, oH, PF.
3 plates