Carrier
EH
ProtectElectric heat
Strips not coming on, or on when they should not.
Walk EH in Diagnose
Sign in for the next measurement
First check
1 Is aux actually being requested?
On Carrier 50FC confirm W / E / aux at the indoor control. A heat-pump call with a communicating board that thinks it needs strips is a config / outdoor issue first. W1/W2 at the unit board. Sequencer 24V, then element ohms, then kit fuses.
Expect: Aux request present only when it should be.
The rest of the walkthrough is Diagnose.
On the plates
- W1/W2 at the unit board. Sequencer 24V, then element ohms, then kit fuses.
- A unit that only runs strips on a 50FCQ is a failed HP circuit.