Carrier
Rollout
HazardRollout / flame spill
Flame left the burner box.
Walk Rollout in Diagnose
2 plates — walk the one on the cabinet
First check
1 Treat this as flame outside the exchanger
Do not reset the Carrier 48FC rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
The rest of the walkthrough is Diagnose.
On the plates
- Heat exchanger crack, blocked flue, or inducer that is not moving air.
- Do not jump a rollout. CO check the space below.
- Burner alignment after a heat-exchanger job.
Plates that use Rollout
Same number, other makers
Rollout on Carrier is not the same code on these plates.