Carrier codes

Carrier

Rollout

Hazard

Rollout / flame spill

Flame left the burner box.

Walk Rollout in Diagnose

2 plates — walk the one on the cabinet

First check

1 Treat this as flame outside the exchanger

Do not reset the Carrier 48FC rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

Expect: No flame outside the exchanger. Burners seated. Crossover lit.

If pass: Still inspect secondary / flue / condensate before you reset.

The rest of the walkthrough is Diagnose.

On the plates

  • Heat exchanger crack, blocked flue, or inducer that is not moving air.
  • Do not jump a rollout. CO check the space below.
  • Burner alignment after a heat-exchanger job.

Plates that use Rollout

Same number, other makers

Rollout on Carrier is not the same code on these plates.