Carrier codes

Carrier

Draft / PS lockout

Hazard

Will not prove / fails combustion

On this family that is often a restricted secondary, not a 59TP6 trap lecture alone.

Walk Draft / PS lockout in Diagnose

Sign in for the next measurement

First check

1 Prove inducer and the live code

Do not pull power — that clears the Carrier 58MCA active code. Write Draft / PS lockout. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Serial in 2993A00001–1808A99999? If no, this bulletin does not apply — treat as a standard 90% draft call.

Expect: 120 VAC at the inducer on a heat call. Wheel turning.

If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

The rest of the walkthrough is Diagnose.

On the plates

  • Serial in 2993A00001–1808A99999? If no, this bulletin does not apply — treat as a standard 90% draft call.
  • Visual secondary / coupling box per the Carrier inspection sheet. Do not punch holes in the secondary to ‘test.’
  • Combustion analysis if it still fires. Failed CA + restriction = bulletin path.
  • CO / rollout: shut it down. This is a hazard call until the secondary is proven.

Plates that use Draft / PS lockout