Carrier
COMM
LockoutABCD / outdoor drop
Drive or bus. Wall control loses the outdoor.
Walk COMM in Diagnose
6 plates — walk the one on the cabinet
On the plates
- R to C at the control. 0 VAC = missing C, not a dead furnace.
- A/B polarity. D is not W.
- One SYSTX-class control on the bus. A 59TP6 hanging this stat will never talk.
- R to C. A/B polarity. D is not W.
- One control on the bus.
- 59TP6 + this stat is the wrong bus — load 59TP6, not this plate.
- ABCD landing and polarity, outdoor board power, inverter comms harness.
- C still required at the wall control.
Plates that use COMM
Same number, other makers
COMM on Carrier is not the same code on these plates.