Rheem
Comm
LockoutABCD / outdoor drop
Drive or bus. Wall control loses the outdoor.
Walk Comm in Diagnose
Sign in for the next measurement
First check
1 Let it cool, then read the drive LED
On Rheem RA19AY overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. ABCD landing and polarity, outdoor board power, inverter comms harness.
Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.
The rest of the walkthrough is Diagnose.
On the plates
- ABCD landing and polarity, outdoor board power, inverter comms harness.
- C still required at the wall control.
- Indoor must be Infinity-capable. A 24ACC6-style indoor pairing is the wrong mental model.
Plates that use Comm
Same number, other makers
Comm on Rheem is not the same code on these plates.