Trane
Comm
LockoutData bus
Indoor / stat / outdoor dropped off ComfortLink. Not an S9V2 E-decimal.
Walk Comm in Diagnose
Sign in for the next measurement
First check
1 Data pair, not 24 V
On Trane XC95m indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. Data pair landing and polarity. One communicating control.
Expect: Pair continuous, not shorted to chassis, polarity per the diagram.
The rest of the walkthrough is Diagnose.
On the plates
- Data pair landing and polarity. One communicating control.
- No 24V on the data pins. No extra ‘common’ spliced onto the pair.
- Isolate devices: stat only, then indoor, then outdoor. A failed XV20i drive can look like a dead furnace IFC.
Plates that use Comm
Same number, other makers
Comm on Trane is not the same code on these plates.