Amana
Comm
LockoutIndoor/outdoor data
ComfortBridge data pair only. Invalid as a diagnosis on a 24V Y1/Y2 hookup.
Walk Comm in Diagnose
3 plates — walk the one on the cabinet
First check
1 Data pair, not 24 V
On Amana ALXT7C indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. Data pair polarity and splices. This is not 24V Y.
Expect: Pair continuous, not shorted to chassis, polarity per the diagram.
The rest of the walkthrough is Diagnose.
On the plates
- Data pair polarity and splices. This is not 24V Y.
- Indoor IFC family must be GMVC / AVPTC communicating. GR9T96 / GMEC96 / GMSS96 cannot be the ComfortBridge indoor.
- One master on the bus. Outdoor board power before you condemn the indoor IFC.
- ABCD landing and polarity, outdoor board power, inverter comms harness.
- C still required at the wall control.
- Indoor must be Infinity-capable. A 24ACC6-style indoor pairing is the wrong mental model.