Carrier
COMM OUT
LockoutNo communication with outdoor
Outdoor dropped off ABCD.
Walk COMM OUT in Diagnose
3 plates — walk the one on the cabinet
First check
1 Is Y actually at the contactor?
On Carrier 59MN7 a silent outdoor is often no Y. Measure 24 VAC coil-to-C at the contactor on a cool call. Outdoor on the same ABCD pair.
Expect: ~24 VAC at the coil when the indoor is calling.
If fail: Indoor Y / IFC / stat — not a capacitor.
The rest of the walkthrough is Diagnose.
On the plates
- Outdoor on the same ABCD pair.
- Outdoor events, not only indoor Last 10.
- Setup outdoor model matches the plate.
- Same ABCD pair at the outdoor.
- Contactor-only outdoor will never talk.
- Setup outdoor ID vs plate.
Plates that use COMM OUT
Same number, other makers
COMM OUT on Carrier is not the same code on these plates.