Carrier codes

Carrier

PF

Lockout

PF — input phase loss

Keypad example: PF. Missing or imbalanced incoming phase.

Walk PF in Diagnose

3 plates — walk the one on the cabinet

First check

1 Three legs at the disconnect and the contactor

On Carrier 48FC measure L1 L2 L3 at the disconnect and at the compressor contactor. A phase monitor trips on loss, imbalance, or reverse rotation. L1 L2 L3 at the drive and at the disconnect. Tight lugs.

Expect: All three legs, nameplate voltage ±10%, phase monitor closed.

The rest of the walkthrough is Diagnose.

On the plates

  • L1 L2 L3 at the drive and at the disconnect. Tight lugs.
  • A rooftop fuse that opened one leg looks like a dead motor until you read PF.

Plates that use PF

Same number, other makers

PF on Carrier is not the same code on these plates.