Carrier codes

Carrier

LED off

Lockout

IGC dark

No 24V at the ignition control, or the module is dead.

Walk LED off in Diagnose

2 plates — walk the one on the cabinet

First check

1 Measure at the IFC under load

On Carrier 48FC line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. 24 VAC at IGC R to C. Control fuse / breaker on the unit board.

Expect: Voltage in the rating-plate window under load.

The rest of the walkthrough is Diagnose.

On the plates

  • 24 VAC at IGC R to C. Control fuse / breaker on the unit board.
  • W present during a heat call. Unoccupied shutdown will darken this LED.
  • Door / heat-section plug seated. A rooftop heat-exchanger panel switch is easy to leave open.

Plates that use LED off

Same number, other makers

LED off on Carrier is not the same code on these plates.