Carrier
31
LockoutMetal-vent draft / inducer
Category I draft will not prove. NEVER a PVC condensate trap.
Walk 31 in Diagnose
10 plates — walk the one on the cabinet
First check
1 Prove inducer and the live code
Do not pull power — that clears the Carrier 58CVA active code. Write 31. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Chimney liner, cap, common-vent tables, inducer wheel.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Trap, collector, PVC, wind, inducer RPM (42 if the inducer itself is out of band).
- If open >5 min, many of these IFCs park the inducer 15 min before retry.
- Trap, collector, PVC slope, wind, inducer.
- Attic jobs: ice in the vent, dry-siphoned or frozen trap.
- If the door card also lists 32, treat 32 as this same single PS path — confirm the sticker.
- Chimney liner, cap, common-vent tables, inducer wheel.
- Not a PVC trap and not a collector box. Do not cut a ‘condensate’ drain that does not exist.
- PS hose to the inducer housing can hold flue condensate on a long metal run — still Category I, still not a 59SC5 collector.