Models
Carrierfurnace

58CVA

Infinity 80% · two-stage · metal vent

80% two-stage Infinity furnace. Category I vent (metal), no PVC secondary, no condensate collector. Codes look like other Carrier two-digit charts but the physics are draft-hood / inducer + metal vent, not a 96% trap. A 31 here is chimney/draft, never a drowned collector.

Not 59TP6 / 59MN7 / 59TN6 / 59SC5 condensing. A 31 on 58CVA is metal-vent draft, not a drowned 96% trap. Not 58STA Comfort 80 (24V single-stage, no ABCD) — same vent family, different control.

AFUE

80% class · Category I

Vent

Metal Category I · not PVC · no secondary drain / trap

Staging

Two-stage gas · two-speed inducer · metal-vent draft switch

Bus

Infinity ABCD on communicating SKUs

This board

Infinity / two-digit IFC (80% metal vent)

  • 13/33 limit, 14/34 ignition, 31 pressure/draft, 24 fuse — same numbers as the 96% boards, different vent.
  • No secondary condensate path. Do not pull the trap playbook from a 59TP6, 59SC5, or 59MN7.
  • 31 is Category I draft / inducer / chimney. It is not a 96% trap, not an attic PVC slope, and not a modulating pressure band.
  • Infinity wall control events first when the ABCD control is alive. Board two-digit if the stat is blank.

Infinity events or board last-status button.

Universal swap

No universal

Infinity-family 80% two-stage. Treat as communicating until the silk is HK42FZ017.

Silk: Infinity · HK42FZ017

White-Rodgers

ICM

  • ICM2807

    Only if the silk is HK42FZ017 and there is no Infinity UI.

Honeywell

  • Any 50A55-843 / 50A65-843 / 50M56U-843 / 50M56X-843 / S9200U1000 universal — those are conventional 24V HSI, not this data bus.
  • ICM280 / 2811 / 2810 / 282B — wrong IFC family.
  • 58STA Comfort single-stage. 50A55-843.

After you pull the dead card

  1. 1Infinity UI → OEM Infinity IFC. HK42FZ017 only → ICM2807. Metal vent either way.

Field wiring

Written landings for Carrier 58CVA. Not a factory schematic.

Infinity / Evolution furnace
ABCDGas furnace

59MN7 / 59TN6 / 987M / 986T class. Four-wire communicating furnace. D is 24V hot, not W and not Y.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC120V
  2. 2Call. Data pair or 24V W → IFCBus or 24V
  3. 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
  4. 4Ignite. IFC → HSI → valve120V igniter
  5. 5Blow. IFC → serial ECMNo tap, no cap

This indoor

Infinity 80% two-stage. Metal vent. ABCD.

ABCD only

Infinity or Evolution wall control and a matching outdoor.

Infinity / Evolution control

A/B data, C common, D 24V hot.

  • ADataData
  • BDataData
  • C24V common24V
  • D24V hot — not W24V

Infinity / Evolution IFC

Same ABCD. Do not convert it to 24V by landing W and walking away.

  • ADataData
  • BDataData
  • CCommon24V
  • D24V hot24V

Landing

  • DataStat A/BIFC A/Boutdoor A/B

    Data

  • 24VStat C/DIFC C/D

    24V common / hot. D is not Y or W.

IFC harness — communicating two-stage

Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.

Transformer + fuse

24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.

  • L1 / N120VLine
  • R / C24V strip24V
  • FUSEOn the IFC24V

24V safety chain

Limit / rollout / door still open the heat path. Codes are on THIS IFC language.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + dual PS

Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.

  • IND LO/HITwo-speed inducerLine
  • LPSLow prove24V
  • HPSHigh prove24V

HSI + two-stage valve

Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.

  • HSI120V igniterLine
  • MV / HV24V low / high solenoids24V
  • FLAMEµA DC24V

Serial variable-speed ECM

IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.

  • SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
  • CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V

Landing

  • LineCallIFCinducerprove

    Low then high

  • LineIFCHSIvalve

    120V igniter, 24V or serial valve

  • 24VFlame rodIFC

    µA DC

  • DataIFCserial blower

    No F-taps. No PSC cap.

Prove it

  • Wall-control equipment list. The furnace and outdoor both present.
  • ABCD polarity. C still required.

Do not

  • Do not land W on a spare screw to make it 24V.
  • A 926T / 59TP6 / 59SC5 is the other diagram.

ABCD is the published Infinity / Evolution control.

Sequence

  1. 1

    W1 / low

    Inducer → draft/pressure switch on metal vent → HSI → low fire. 31 if the metal vent will not prove.

  2. 2

    W2 / high

    High fire, still Category I draft. Wind and shared chimneys show up here. Still no PVC trap.

  3. 3

    Limit

    33 airflow / rollout. 80% A-coils dirty the same as anything else. Held open → 13.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

24

Secondary fuse open

warn

24 V fuse on the IFC.

  1. 1 Find the 24 V short before you replace the fuse

    On Carrier 58CVA an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. Tstat / ABCD miswire, HUM/EAC, valve harness. Replace fuse after the short is gone.

    Expect: Fuse out. 24 V transformer still good. Harness isolated.

  2. 2 Replace the fuse with the harness off

    New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC).

    Expect: Fuse holds with harness off. Dies when the shorted lead lands.

  3. 3 If it blows with the harness off

    Short is on the Carrier 58CVA IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.

    Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.

31

Draft / PS

lockout

Metal vent will not prove. This is not a 96% trap.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Carrier 58CVA active code. Write 31. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Chimney liner, cap, common-vent tables, inducer wheel.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Not a PVC trap and not a collector box. Do not cut a ‘condensate’ drain that does not exist.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. PS hose to the inducer housing can hold flue condensate on a long metal run — still Category I, still not a 59SC5 collector.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

33 / 13

Limit

warn

Airflow. 80% coils still dirty. 13 is the hardened 33.

  1. 1 Airflow before you touch the limit

    On Carrier 58CVA a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, AC coil on top, blower, Infinity heat CFM.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Carrier 58CVA blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Rollout: exchanger / burners / flue. Manual reset.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).

    Expect: Manifold on plate. Limit closed when cool.

34 / 14

Ignition

lockout

HSI / gas / rod. 14 is the hardened 34.

  1. 1 Ohms at the igniter, then at the IFC

    On Carrier 58CVA measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Same prove logic as other Carrier IFCs. Fix 31 draft before a fair 34 test.

    Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

ABCD

Communication

lockout

Wall control or outdoor dropped (communicating 58CVA SKUs).

  1. 1 Data pair, not 24 V

    On Carrier 58CVA indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. A/B/C/D, polarity, C required, no 24V on D.

    Expect: Pair continuous, not shorted to chassis, polarity per the diagram.

  2. 2 Power both ends, then the outdoor status

    Indoor transformer and outdoor control both alive. Read the outdoor LED / 7-seg. Water in the outdoor control is the usual dead-end after a storm. Non-communicating 58CVX cousins may be 24V — read the actual board.

    Expect: Both controls powered. Outdoor showing a comm or address state, not a blank board.

  3. 3 Address / bias, then the control

    Communicating plates need a matching indoor address and sometimes a terminating bias. Swap is last: known-good pair + power both ends + correct address.

    Expect: Indoor sees the outdoor. No comm code after a power cycle.

Workflows

31 on an 80% Infinity

Do not dump the condensate trap.

  1. 1 Prove the call and the live code

    This furnace has no secondary drain. Look at the metal vent and the inducer wheel. 31 is not a 96% trap.

    Expect: Write whatever Infinity / two-digit IFC (80% metal vent) is showing. Infinity events or board last-status button.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Common-vented water heater: the 31 may be a venting table problem, not a switch.

    Expect: W2 / high: High fire, still Category I draft. Wind and shared chimneys show up here. Still no PVC trap.

  3. 3 Confirm with a number, then the next part

    Chimney liner, cap, masonry debris, wind cap. Category I tables — spillage at the draft hood / inducer inlet is a fail. Then the PS hose to the inducer housing — still can fill with water from flue condensation in long metal runs, but it is not a 96% collector. Infinity events will say pressure or draft. Believe that over a 59MN7 band story or a 59SC5 trap story.

    Expect: Vent: Cat I tables. Spillage at the draft hood / inducer inlet is a fail. No PVC trap to pull. · ABCD: On communicating SKUs: D is not W. C required.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Which Carrier 80% is this?

Plate is rusty or someone called it a 59-series.

  1. 1 Prove the call and the live code

    Metal vent, no collector = 80%. PVC + trap = you are on the wrong page (59-series).

    Expect: Write whatever Infinity / two-digit IFC (80% metal vent) is showing. Infinity events or board last-status button.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    ABCD wall control + two-stage 80% = 58CVA / Infinity 80. Single-stage Comfort 80 24V = 58STA.

    Expect: W2 / high: High fire, still Category I draft. Wind and shared chimneys show up here. Still no PVC trap.

  3. 3 Confirm with a number, then the next part

    58MVP / 355CAV older variable 80% — similar metal-vent 31, different IFC generation. Read that door card.

    Expect: Vent: Cat I tables. Spillage at the draft hood / inducer inlet is a fail. No PVC trap to pull. · ABCD: On communicating SKUs: D is not W. C required.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Vent

Cat I tables. Spillage at the draft hood / inducer inlet is a fail. No PVC trap to pull.

ABCD

On communicating SKUs: D is not W. C required.

31 hose

Inducer housing tap on metal vent. Water here is flue condensate, not a 96% collector.

Gotchas

  • 58MVP / 355CAV older variable 80% — similar idea, different IFC generation. Read that door card.
  • Bryant 355CAV is the badge twin on many jobs.
  • A tech who just left a 59SC5 will dump the ‘trap’ and miss the chimney liner.

Related plates

Install this plate

Install 58CVA as Infinity 80% two-stage. Metal vent + ABCD. Twin of Bryant 355CAV / 880TA.

Cat I metal vent · two-stage 80% · Infinity ABCD · no PVC secondary

Vent

  • Category I only. 31 is chimney / liner / common-vent / inducer.
  • No collector, no primed 96% trap. Public product page for this older plate is retired — use the furnaces hub + dealer I/O.

First fire

  1. 1Pair Infinity. Heat call on a legal Cat I vent. Spillage / CO is a fail.

Do not on Carrier 58CVA

  • Do not apply 59MN7 PVC trap steps to this 31.
  • Do not install as a 24V Comfort 80 (that is 58STA).

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • Carrier residential furnacesLiterature searchProduct pages carry current literature. I/O booklets are typically HVACpartners / dealer.Open manufacturer PDF
  • Carrier HVAC resourcesLiterature searchOwner-facing literature hub. Do not invent a 59-series I/O URL.Open manufacturer PDF
  • Carrier residential furnacesLiterature searchSearch Carrier 58CVA on the maker’s literature page.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    warranty sheet

    Carrier / Bryant registered heat-exchanger terms

    Current 59-series / Evolution / Preferred registered warranty · Limited warranty certificate

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal