ICP
31
LockoutDraft / pressure switch
Inducer running, the one PS did not close (or the draft path will not hold). On this 96% that is trap / PVC / inducer.
3 plates — walk the one on the cabinet
First check
1 Prove inducer and the live code
Do not pull power — that clears the ICP N80ESN active code. Write 31. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- One PS only — do not hunt a second high-fire switch.
- Dump the trap and open the collector. N9MSB 96% drowns overnight.
- PVC intake/exhaust, ice, wind, hose on the only collector tap.
- Inducer 120 VAC and spinning. This is not Goodman 3-flash even if the neighbor unit is.
- This is Category I metal vent. There is no 96% collector or PVC trap to prime.
- Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Plates that use 31
Same number, other makers
31 on ICP is not the same code on these plates.