Models
Carrierfurnace

58TP0

Performance 80 · two-stage · variable-speed · Cat I

Carrier Performance 80% two-stage VS (58TP1 is Low-NOx). Metal vent. Twin of Bryant 820T. Two-digit 31 is chimney draft. Not 58CVA Infinity 80%.

Not 58CVA Infinity 80% two-stage. Not 58STA Comfort 80. Not 59TP6 96%.

AFUE

80% two-stage · Cat I

Sister SKU

58TP1 Low-NOx · Bryant 820T / 821T

This board

Infinity / two-digit IFC (80% metal vent)

  • 13/33 limit, 14/34 ignition, 31 pressure/draft, 24 fuse — same numbers as the 96% boards, different vent.
  • No secondary condensate path. Do not pull the trap playbook from a 59TP6, 59SC5, or 59MN7.
  • 31 is Category I draft / inducer / chimney. It is not a 96% trap, not an attic PVC slope, and not a modulating pressure band.
  • Infinity wall control events first when the ABCD control is alive. Board two-digit if the stat is blank.

Infinity events or board last-status button.

Universal swap

No universal

Performance 80% VS two-stage. Same rule as 820T.

Silk: HK42FZ017

White-Rodgers

ICM

Honeywell

  • 58CVA Infinity IFC. 50A55-843.

After you pull the dead card

  1. 1OEM Performance 80% VS IFC. Metal vent.

Field wiring

Written landings for Carrier 58TP0. Not a factory schematic.

Furnace · two-stage 24V
R / C / W1 / W2 / Y / GGas furnace

Two-stage conventional furnace. W1 low fire, W2 high fire. Outdoor staging is Y or Y1/Y2 — separate from the gas valve.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC → R120V / 24V
  2. 2Low. W1 → inducer LOW → LPS → HSI → valve LOWFirst fire
  3. 3High. W2 → inducer HIGH → HPS → valve HIGHSecond solenoid
  4. 4Flame. Rod → IFCµA DC both stages
  5. 5Blow. IFC → heat blowerAfter flame

This indoor

Performance 80 two-stage. Metal vent.

24V two-stage heat

Door has W1 and W2. Not Infinity. Not ComfortBridge.

Two-stage thermostat

A single-W stat never proves high fire. That is not a weak inducer.

  • R24V hot24V
  • CCommon24V
  • W1Low-fire heat24V
  • W2High-fire heat24V
  • Y / Y1Cool24V
  • Y2Outdoor high if the condenser is two-stage24V
  • GFan24V

Two-stage IFC

W2 is high fire. Do not tee the pressure-switch hoses because there are two stages.

  • RHot24V
  • CCommon to outdoor24V
  • W1Low fire24V
  • W2High fire24V
  • YCool out24V
  • GBlower / cool tap24V

Landing

  • 24VStat W1IFC W1

    Low fire

  • 24VStat W2IFC W2

    High fire. Missing W2 = stuck on low.

  • 24VStat YIFC Youtdoor Y

    Cool

  • 24VC throughout

    Common

IFC harness — two-stage heat

W1 then W2. Low-fire prove is not high-fire prove.

Transformer + fuse

Same 24V transformer as single-stage. Fuse still kills the whole strip.

  • L1 / N120VLine
  • XFMR24V to R24V
  • FUSEOn the IFC24V

24V safety chain

Door, limit, rollout. A limit trip is not an E9 / 32 pressure-switch story.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + two pressure switches

W1 = inducer low + LPS. W2 = inducer high + HPS. Separate hoses. Do not tee.

  • IND LO120V low-speed inducerLine
  • IND HI120V high-speed inducerLine
  • LPSLow-fire prove24V
  • HPSHigh-fire prove24V
  • HOSESOne hose per switch. Never tee LPS and HPS24V

HSI + two-stage valve

Igniter 120V. Low solenoid on W1. Second solenoid on W2 after HPS closes.

  • HSI120V igniterLine
  • MV / LO24V low-fire solenoid24V
  • HV / HI24V high-fire solenoid24V
  • FLAMEµA DC on the rod24V

Constant-torque ECM

Tap / profile motor. Not serial VS. Not a PSC cap.

  • TAPSHeat / cool / adjust profiles on the IFC24V
  • COMMONMotor common back to the IFC24V

Landing

  • LineW1IFCinducer LOWLPS

    120V inducer, 24V prove

  • LineIFCHSIvalve LOW

    120V igniter, 24V low solenoid

  • 24VW2inducer HIGHHPSvalve HIGH

    Missing W2 = stuck on low

  • 24VFlame rodIFC

    µA DC

  • LineIFCheat blower

    After flame. Motor class on this plate.

Prove it

  • W1 then W2 at the IFC under a 2-heat call.
  • If it never stages, W2 is missing at the board — not a bad gas valve until that is proven.

Do not

  • Do not convert this to Infinity by landing W on a random terminal.
  • Do not apply AMVC / ARVT ComfortBridge menus or a memory card.

926T / 59TP6 / AR9T96 / GR9T96 / S9V2 / EL296E class. Same landing on 80% metal-vent cousins — the vent is not the wire.

Sequence

  1. 1

    W1 / low

    Inducer → draft/pressure switch on metal vent → HSI → low fire. 31 if the metal vent will not prove.

  2. 2

    W2 / high

    High fire, still Category I draft. Wind and shared chimneys show up here. Still no PVC trap.

  3. 3

    Limit

    33 airflow / rollout. 80% A-coils dirty the same as anything else. Held open → 13.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

24

Secondary fuse open

warn

24 V fuse on the IFC.

  1. 1 Find the 24 V short before you replace the fuse

    On Carrier 58TP0 an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. Tstat / ABCD miswire, HUM/EAC, valve harness. Replace fuse after the short is gone.

    Expect: Fuse out. 24 V transformer still good. Harness isolated.

  2. 2 Replace the fuse with the harness off

    New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC).

    Expect: Fuse holds with harness off. Dies when the shorted lead lands.

  3. 3 If it blows with the harness off

    Short is on the Carrier 58TP0 IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.

    Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.

31

Draft / PS

lockout

Metal vent will not prove. This is not a 96% trap.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Carrier 58TP0 active code. Write 31. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Chimney liner, cap, common-vent tables, inducer wheel.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

33 / 13

Limit

warn

Airflow. 80% coils still dirty. 13 is the hardened 33.

  1. 1 Airflow before you touch the limit

    On Carrier 58TP0 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, AC coil on top, blower, Infinity heat CFM.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Carrier 58TP0 blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Rollout: exchanger / burners / flue. Manual reset.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).

    Expect: Manifold on plate. Limit closed when cool.

34 / 14

Ignition

lockout

HSI / gas / rod. 14 is the hardened 34.

  1. 1 Ohms at the igniter, then at the IFC

    On Carrier 58TP0 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Same prove logic as other Carrier IFCs. Fix 31 draft before a fair 34 test.

    Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

ABCD

Communication

lockout

Wall control or outdoor dropped (communicating 58CVA SKUs).

  1. 1 Data pair, not 24 V

    On Carrier 58TP0 indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. A/B/C/D, polarity, C required, no 24V on D.

    Expect: Pair continuous, not shorted to chassis, polarity per the diagram.

  2. 2 Power both ends, then the outdoor status

    Indoor transformer and outdoor control both alive. Read the outdoor LED / 7-seg. Water in the outdoor control is the usual dead-end after a storm. Non-communicating 58CVX cousins may be 24V — read the actual board.

    Expect: Both controls powered. Outdoor showing a comm or address state, not a blank board.

  3. 3 Address / bias, then the control

    Communicating plates need a matching indoor address and sometimes a terminating bias. Swap is last: known-good pair + power both ends + correct address.

    Expect: Indoor sees the outdoor. No comm code after a power cycle.

Workflows

58TP0 vs 58CVA

Carrier 80% two-stage.

  1. 1 Prove the call and the live code

    ABCD wall control = 58CVA Infinity. 24V Preferred/Performance = 58TP0.

    Expect: Write whatever Infinity / two-digit IFC (80% metal vent) is showing. Infinity events or board last-status button.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Both are metal vent. 31 is still a chimney.

    Expect: W2 / high: High fire, still Category I draft. Wind and shared chimneys show up here. Still no PVC trap.

  3. 3 Confirm with a number, then the next part

    Both are metal vent. 31 is still a chimney.

    Expect: Vent: Cat I tables. Spillage at the draft hood / inducer inlet is a fail. No PVC trap to pull. · ABCD: On communicating SKUs: D is not W. C required.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Vent

Cat I tables. Spillage at the draft hood / inducer inlet is a fail. No PVC trap to pull.

ABCD

On communicating SKUs: D is not W. C required.

31 hose

Inducer housing tap on metal vent. Water here is flue condensate, not a 96% collector.

Gotchas

  • 58CVA is the Infinity 80% already in the bench. This is the 24V Performance 80%.

Related plates

Install this plate

Install Carrier 58TP0 as Performance 80 · two-stage · variable-speed · Cat I.

Performance 80 · two-stage · variable-speed · Cat I

This plate — not the sister SKU

  • Not 58CVA Infinity 80% two-stage. Not 58STA Comfort 80. Not 59TP6 96%.
  • 58CVA is the Infinity 80% already in the bench. This is the 24V Performance 80%.

IFC on this door

  • 13/33 limit, 14/34 ignition, 31 pressure/draft, 24 fuse — same numbers as the 96% boards, different vent.
  • No secondary condensate path. Do not pull the trap playbook from a 59TP6, 59SC5, or 59MN7.
  • 31 is Category I draft / inducer / chimney. It is not a 96% trap, not an attic PVC slope, and not a modulating pressure band.
  • Infinity wall control events first when the ABCD control is alive. Board two-digit if the stat is blank.

Hardware

  • AFUE: 80% two-stage · Cat I
  • Sister SKU: 58TP1 Low-NOx · Bryant 820T / 821T

First fire

  1. 1ABCD wall control = 58CVA Infinity. 24V Preferred/Performance = 58TP0.
  2. 2Both are metal vent. 31 is still a chimney.

Do not on Carrier 58TP0

  • Not 58CVA Infinity 80% two-stage. Not 58STA Comfort 80. Not 59TP6 96%.
  • 58CVA is the Infinity 80% already in the bench. This is the 24V Performance 80%.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • Carrier residential furnacesLiterature searchProduct pages carry current literature. I/O booklets are typically HVACpartners / dealer.Open manufacturer PDF
  • Carrier HVAC resourcesLiterature searchOwner-facing literature hub. Do not invent a 59-series I/O URL.Open manufacturer PDF
  • Carrier residential furnacesLiterature searchSearch Carrier 58TP0 on the maker’s literature page.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    warranty sheet

    Carrier / Bryant registered heat-exchanger terms

    Current 59-series / Evolution / Preferred registered warranty · Limited warranty certificate

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal