Carrier
23
LockoutPS did not open
Draft switch still made when it should be open.
Walk 23 in Diagnose
7 plates — walk the one on the cabinet
First check
1 Unplug the switch with the inducer off
On Carrier 58SP0 this code is the switch made when the inducer is not running. Unplug that switch only. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
The rest of the walkthrough is Diagnose.
On the plates
- Welded switch, water in hose, inducer still spinning when it should be off.
- One switch — there is no ‘the other PS’ to swap to.
- Welded switch, residual chimney draft, inducer still spinning.
- This is Category I metal vent. There is no 96% collector or PVC trap to prime.
- Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Plates that use 23
Same number, other makers
23 on Carrier is not the same code on these plates.