Carrier
31 / 42
LockoutPressure / inducer band
Modulating inducer did not hit the pressure band for the commanded firing rate. Not a discrete two-stage PS.
Sign in for the next measurement
First check
1 Prove inducer and the live code
Do not pull power — that clears the Carrier 59MN7 active code. Write 31 / 42. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Vent, trap, inducer, pressure transducer/hose — there may not be two discrete PS like 59TN6 or 59TP6.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Vent, trap, inducer, pressure transducer/hose — there may not be two discrete PS like 59TN6 or 59TP6.
- Do not ohm a ‘low’ and a ‘high’ switch that are not there.
- Attic PVC and collector still drown a modulator. Band miss + wet collector is still a trap call.
- 42 = inducer RPM out of the band the IFC commanded.
Plates that use 31 / 42
Same number, other makers
31 / 42 on Carrier is not the same code on these plates.