Bryant codes

Bryant

31 / 42

Lockout

Pressure / inducer band

Modulating inducer did not hit the band for the commanded rate.

Walk 31 / 42 in Diagnose

Sign in for the next measurement

First check

1 Prove inducer and the live code

Do not pull power — that clears the Bryant 987M active code. Write 31 / 42. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Vent, trap, inducer, transducer/hose — do not ohm a ‘low’ and ‘high’ switch that are not there.

Expect: 120 VAC at the inducer on a heat call. Wheel turning.

If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

The rest of the walkthrough is Diagnose.

On the plates

  • Vent, trap, inducer, transducer/hose — do not ohm a ‘low’ and ‘high’ switch that are not there.
  • 42 = inducer RPM out of the commanded band.

Plates that use 31 / 42

Same number, other makers

31 / 42 on Bryant is not the same code on these plates.