Carrier
RV
LockoutNo shift
Reversing valve did not stroke.
Walk RV in Diagnose
Sign in for the next measurement
First check
1 Confirm O/B is energized the way THIS outdoor expects
Most US splits energize O in cool. Some Rheem/Ruud energize B in heat. Read the Carrier 50FC diagram, not a generic heat-pump card. O/B 24 VAC at the board on a heat call (or cool, depending on this controller’s logic — confirm silk).
Expect: Correct 24 V at the solenoid for the mode that is failing.
The rest of the walkthrough is Diagnose.
On the plates
- O/B 24 VAC at the board on a heat call (or cool, depending on this controller’s logic — confirm silk).
- Coil ohms. Then the piston — a stuck RV is not a charge call.