Carrier
A2L
HazardA2L / mitigation
Leak sensor or mitigation input on an R-454B cabinet.
Walk A2L in Diagnose
Sign in for the next measurement
First check
1 Confirm this pair is actually A2L
On Carrier 48FE FE3 / LE4 / SE5 / rE6-class codes are only valid when this furnace is tied to an R-32 or R-454B outdoor. On R-410A this is a miswired mitigation harness — not a leaking indoor coil.
Expect: Outdoor refrigerant from the outdoor nameplate, not from memory.
If fail: Remove / correct the mitigation harness. Do not condemn the IFC.
The rest of the walkthrough is Diagnose.
On the plates
- Only legal on the A2L plate. A leftover 410A 48FC will not have this harness.
- Find the leak. Do not disable the sensor to ‘get cooling back.’