Amana codes

Amana

EA

Lockout

Reversed polarity / poor ground

L1/N reversed or chassis ground missing. Furnace will not operate.

Walk EA in Diagnose

9 plates — walk the one on the cabinet

First check

1 Measure µA while it is running

Do not clean first and guess. Series-µA the rod on Amana AMVC96 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Hot and neutral at the IFC, not just the disconnect.

Expect: Flame rod: µA per this IFC sticker, not the AR9T96 card. Rising while running is the goal.

The rest of the walkthrough is Diagnose.

On the plates

  • Hot and neutral at the IFC, not just the disconnect.
  • Burner box to IFC ground screw.
  • Twinned jobs — follow the twinning kit, then look at EEJ.
  • Hot and neutral at the IFC. Burner-box ground screw.
  • 24V transformer leads swapped on a replacement IFC.
  • Hot and neutral at the IFC.
  • Burner-box ground screw.

Plates that use EA

Same number, other makers

EA on Amana is not the same code on these plates.