Models
Amanafurnace

ARVT80

ComfortBridge · two-stage · serial VS · 80% Cat I

Amana ComfortBridge two-stage 80%. Factory twin of Goodman GRVT80. Triple 7-seg + serial ECM + memory card. E2/E9 are metal-vent draft. Not ARVT96 (96% PVC, 0.5" heat-ESP on that SS) and not AR9S80 (9-speed tap, single 7-seg).

Not ARVT96 / ADVT96 (96% ComfortBridge — same tokens, collector and trap). Not AR9T80 / AR9S80 (9-speed 24V). Not AMVC96 (96% ComfortBridge older plate).

AFUE

80% · Category I metal vent

Control

ComfortBridge · CoolCloud · ARVT80 memory card

Sister SKU

ADVT80 downflow · Goodman GRVT80 / GDVT80

This board

ComfortBridge 80% IFC — ARVT80 card, metal-vent E2/E9

  • Same E/b/d language as AMVC96. Vent is not. E2/E9 = chimney / B-vent.
  • Memory card is ARVT80 / ADVT80. An ARVT96 or AMVC96 card is d4.

IFC menu history. Write the three characters.

Universal swap

No universal

Amana ComfortBridge 80%. No universal. ARVT96 card is d4.

Silk: ARVT80 · ComfortBridge

White-Rodgers

ICM

Honeywell

  • Any 50A55-843 / 50A65-843 / 50M56U-843 / 50M56X-843 / S9200U1000 universal — those are conventional 24V HSI, not this data bus.
  • ICM280 / 2811 / 2810 / 282B — wrong IFC family.
  • ARVT96 96% card. AR9S80 9-speed board.

After you pull the dead card

  1. 1OEM ARVT80 / ADVT80 ComfortBridge IFC. Metal vent.

Field wiring

Written landings for Amana ARVT80. Not a factory schematic.

ComfortBridge / ComfortNet furnace
1 / 2 data — or 24VGas furnace

Goodman / Amana / Daikin communicating two-stage. Outdoor on 1 and 2 when the outdoor talks. A 24V GSX16 still wants Y, not data.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC120V
  2. 2Call. Data pair or 24V W → IFCBus or 24V
  3. 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
  4. 4Ignite. IFC → HSI → valve120V igniter
  5. 5Blow. IFC → serial ECMNo tap, no cap

This indoor

ComfortBridge 80%. Metal vent. Same 1/2.

Communicating outdoor

GSXC / ASXC / GXV / DZ / FIT on the same bus. CoolCloud or Daikin One at the wall.

CoolCloud / Daikin One

Menus on the indoor. Do not put R/C on 1 and 2.

  • 1DataData
  • 2DataData

ComfortBridge / ComfortNet IFC

Memory card must match THIS cabinet (ARVT96 card is not AMVC96).

  • 1Data to outdoorData
  • 2Data to outdoorData
  • R24V accessories24V
  • CCommon24V

Landing

  • DataIFC 1outdoor 1 · IFC 2outdoor 2

    Data. Polarity matters.

24V outdoor on this IFC

GSX16 / GLXS4B / any contactor outdoor. Land Y. Leave 1/2 empty.

Conventional stat (allowed)

W1/W2/Y/G on the IFC 24V strip. Not on 1/2.

  • RHot24V
  • CCommon24V
  • W1Heat24V
  • YCool24V
  • GFan24V

Landing

  • 24VStat YIFC Youtdoor Y

    ~24 VAC. Data wire is a miswire.

IFC harness — communicating two-stage

Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.

Transformer + fuse

24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.

  • L1 / N120VLine
  • R / C24V strip24V
  • FUSEOn the IFC24V

24V safety chain

Limit / rollout / door still open the heat path. Codes are on THIS IFC language.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + dual PS

Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.

  • IND LO/HITwo-speed inducerLine
  • LPSLow prove24V
  • HPSHigh prove24V

HSI + two-stage valve

Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.

  • HSI120V igniterLine
  • MV / HV24V low / high solenoids24V
  • FLAMEµA DC24V

Serial variable-speed ECM

IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.

  • SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
  • CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V

Landing

  • LineCallIFCinducerprove

    Low then high

  • LineIFCHSIvalve

    120V igniter, 24V or serial valve

  • 24VFlame rodIFC

    µA DC

  • DataIFCserial blower

    No F-taps. No PSC cap.

Prove it

  • Indoor family first. Communicating outdoor = 1/2. Contactor outdoor = Y.
  • Memory card / CoolCloud sees THIS furnace.

Do not

  • Do not drop an ARVT96 card into AMVC96 or the other way around.
  • Do not land 1/2 on a GR9T96.

1 and 2 are the published ComfortBridge / ComfortNet pair.

Sequence

  1. 1

    Call

    Communicating stat requests heat capacity. On 24V fallback, W1/W2 behave like a two-stage furnace but blower CFM still comes from the IFC tables, not taps.

  2. 2

    Prove limits

    IFC proves primary/aux/rollout closed. Open limit → E3. Open 24V fuse → E5. No 115V / door switch / internal → EE.

  3. 3

    Low inducer / LPS

    Two-speed inducer starts low. Low-stage PS must close. Already closed with inducer off → E1. Never closes (5 min then 1-hour lockout) → E2. Same physics as AR9T96, E1/E2 on this board.

  4. 4

    HSI / low-fire valve

    Silicon nitride warm-up, then first-stage solenoid. Open igniter / no-ground → E7. Flame must prove at the rod. Failures stack toward E0 (3 retries, 1-hour auto reset).

  5. 5

    Blower

    Serial ECM ramps to the IFC heat CFM table. No tap plugs. Silent motor → b0/b1. Wrong motor HP vs the shared-data set → b2. Do not hang an AR9T96 9-speed motor on this harness.

  6. 6

    High fire

    Communicating capacity or W2. Inducer goes high. High-stage PS must close (E9 if open — no high fire; E8 if it was already closed — runs low only). Second-stage solenoid opens.

  7. 7

    Satisfied

    Valve off, inducer post-purge, blower heat-off delay. Unexpected flame after valve-off → E4.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

idle / Ht1 / Ht2 / CF / CL1 / CL2

Status, not a fault

info

Normal run states on the triple display. idle = standby. Ht1 / Ht2 = low / high heat. CF = continuous fan. CL1 / CL2 = cooling stage.

  1. 1 Confirm this is not a fault

    On the Amana ARVT80 this readout (idle / Ht1 / Ht2 / CF / CL1 / CL2) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.

    Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.

    If fail: If the word never changes on a real call, the call is not reaching this IFC.

    If pass: The board is alive. Diagnose the comfort complaint, not this code.

  2. 2 Prove the call at the board

    Measure R to W / Y / G at the Amana ARVT80 IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.

    Expect: Do not replace the board because it says Ht1 or CF.

    If fail: Fix the stat, harness, or data pair before you change parts.

  3. 3 Watch one full sequence

    Leave power on. Watch ComfortBridge 80% IFC — ARVT80 card, metal-vent E2/E9 through one cycle and write the first real fault that replaces this status word.

    Expect: Call: Communicating stat requests heat capacity. On 24V fallback, W1/W2 behave like a two-stage furnace but blower CFM still comes from the IFC tables, not taps.

E0

System / ignition lockout

lockout

Control failed to sense flame after 3 full ignition retries and shut off gas. Auto-resets after 1 hour (or a tstat cycle).

  1. 1 Watch one full try — do not reset

    Write the Amana ARVT80 code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. Watch one full try: inducer, HSI glow, valve click, flame, µA.

    Expect: Call → Prove limits → Low inducer / LPS → HSI / low-fire valve → Blower → High fire → Satisfied

  2. 2 Gas and the valve

    Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence. Gas supply and manifold (low then high).

    Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

  3. 3 Flame prove, then the lockout timer

    Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets. Ground and flame-rod cleanliness.

    Expect: Flame rod: µA per this IFC sticker, not the AR9T96 card. Rising while running is the goal.

E1

Low-stage PS stuck closed

lockout

Low-stage pressure switch is made with the inducer off. Control waits for the fault to clear.

  1. 1 Unplug the switch with the inducer off

    On Amana ARVT80 this code is the switch made when the inducer is not running. Unplug that switch only. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: Code changes when the harness is open.

    If fail: Wrong switch, or the IFC input is shorted.

    If pass: Switch/hose path. Go to step 2.

  2. 2 Water in the hose vs a welded switch

    Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Hose empty. Switch opens with no draft.

  3. 3 IFC input last

    If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Amana ARVT80 IFC input is shorted. Do not keep swapping switches. Unplug the LPS. If the code changes, the switch is welded or the hose is holding residual draft.

    Expect: Known-good open switch + open harness = code gone. If not, IFC.

E2

Low-stage PS stuck open

lockout

Inducer is on low and the low-stage switch did not close within 5 minutes. Then 1-hour lockout and retry.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Amana ARVT80 active code. Write E2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Inducer spinning? 120 VAC at the inducer on a heat call.

    Expect: LPS / HPS: Both NO. Two hoses, two taps, never teed. Closed only when that inducer speed is making the collector setpoint.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

E3

Open primary / aux / rollout limit

warn

A limit opened. Both blowers typically run until it recloses. Airflow or overfire — not a charge problem. Rollout is still a manual-reset hazard.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Amana ARVT80 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. IFC heat CFM setting, not a 9-speed tap. Filter, blower wheel, A-coil, return size, total external static.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Amana ARVT80 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave. Manifold pressure on low and high vs rating plate.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

E4

Flame sensed with no call for heat

hazard

Rod sees flame with both solenoids de-energized. Control runs circulator and inducer and will not fire again.

  1. 1 Shut the gas cock first

    On Amana ARVT80 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. If flame stays, leaking valve — replace, do not jump.

    Expect: Flame dies when the cock is shut.

    If fail: Leaking valve. Replace. Do not leave the unit.

  2. 2 Rod and IFC flame circuit

    If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Rod shorted to ground or IFC flame circuit.

    Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.

  3. 3 Confirm valve solenoids are actually off

    Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Treat as a hazard until the valve is proven closed.

    Expect: 0 VAC at both solenoids after the call. No flame.

E5

Open 24V fuse

warn

Low-voltage fuse on the IFC is open. All furnace operation is inhibited except the error display.

  1. 1 Find the 24 V short before you replace the fuse

    On Amana ARVT80 an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. 24 V short on W, Y, G, humidifier, EAC, or a leftover data pair landed on R/C.

    Expect: Fuse out. 24 V transformer still good. Harness isolated.

  2. 2 Replace the fuse with the harness off

    New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC). Unplug the tstat / data harness and replace the fuse. If it blows again the short is on the board or gas-valve harness.

    Expect: Fuse holds with harness off. Dies when the shorted lead lands.

  3. 3 If it blows with the harness off

    Short is on the Amana ARVT80 IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.

    Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.

E6

Low flame-sense µA

warn

Flame is present but the micro-amp signal is below the IFC threshold.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Amana ARVT80 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod with a non-scratch pad — not sandpaper.

    Expect: Flame rod: µA per this IFC sticker, not the AR9T96 card. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Chassis ground to burner box and IFC.

    Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

  3. 3 Prove it is not a switch opening

    Watch the live Amana ARVT80 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Manifold pressure / orifice / LP conversion.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

E7

Igniter open / no-ground

lockout

Igniter is open, not connected, or the IFC failed its ground check on the igniter circuit.

  1. 1 Ohms at the igniter, then at the IFC

    On Amana ARVT80 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Igniter ohms cold (confirm sticker — nitride, not a 80% Norton chart).

    Expect: HSI: Nitride, 120 VAC during warm-up. Cold ohms per sticker.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. 120 VAC to igniter during warm-up.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter. Cracked nitride element. Burner-box ground screw and painted-cabinet star washer.

    Expect: One clean light after a known-good igniter and a proven ground.

E8

High-stage PS stuck closed

lockout

High-stage pressure switch is made with the inducer not on high. Furnace runs low only regardless of demand.

  1. 1 Unplug the switch with the inducer off

    On Amana ARVT80 this code is the switch made when the inducer is not running. Unplug that switch only. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: Code changes when the harness is open.

    If fail: Wrong switch, or the IFC input is shorted.

    If pass: Switch/hose path. Go to step 2.

  2. 2 Water in the hose vs a welded switch

    Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Hose empty. Switch opens with no draft.

  3. 3 IFC input last

    If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Amana ARVT80 IFC input is shorted. Do not keep swapping switches. This is the second switch — do not confuse with E1.

    Expect: Known-good open switch + open harness = code gone. If not, IFC.

E9

High-stage PS stuck open

lockout

Inducer on high, high-stage switch never closes. Classic ‘runs on low, will not go high.’

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Amana ARVT80 active code. Write E9. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Inducer actually changes speed on a high-fire request? Listen / amp it.

    Expect: LPS / HPS: Both NO. Two hoses, two taps, never teed. Closed only when that inducer speed is making the collector setpoint.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

EA

Reversed polarity / poor ground

lockout

L1/N reversed or chassis ground missing. HSI and flame sense both suffer. Furnace will not operate.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Amana ARVT80 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Hot and neutral at the IFC, not just the disconnect.

    Expect: Flame rod: µA per this IFC sticker, not the AR9T96 card. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Burner box to IFC ground screw.

    Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

  3. 3 Prove it is not a switch opening

    Watch the live Amana ARVT80 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. 24V transformer leads swapped on a replacement IFC.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

EE

No 115V to control / internal / door switch

lockout

No line voltage reaching the IFC, door switch open, or an internal control condition. This is power, not a ComfortBridge data-pair code.

  1. 1 Measure at the IFC under load

    On Amana ARVT80 line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. Furnace switch, breaker, and blower-door switch fully made.

    Expect: Voltage in the rating-plate window under load.

  2. 2 Drop, breaker, and the whip

    Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. 115 VAC at L1/N on the IFC.

    Expect: Minimal drop. Tight lugs. Correct breaker size.

  3. 3 Transformer 24 V last

    If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call. Do not confuse EE on this board with a comms complaint — check the data pair separately if the stat is dark and the IFC is alive.

    Expect: 24 V holds under load. Line stays in window.

b0

ECM blower not running

lockout

IFC commanded the serial ECM and does not detect it running. Furnace will not operate.

  1. 1 Reseat the serial plug

    On Amana ARVT80 this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. 14-pin harness seated at motor and IFC. No tap plugs on this motor.

    Expect: Plug fully seated both ends. Correct motor for this cabinet.

  2. 2 Power and the data pair at the motor

    Line voltage at the motor, then the serial/data pair continuity. A half-seated plug or a pinched harness throws comm on a good motor. 120 VAC to the motor, wheel free, no wet winding.

    Expect: Line voltage present. Data pair not shorted to chassis.

  3. 3 Motor vs IFC serial driver

    Known-good motor still throws this code = Amana ARVT80 IFC serial driver. Known-good IFC still throws it = motor module. Do not put a PSC or 9-speed tap motor on a serial IFC. Do not install an AR9T96 9-speed motor as a ‘cheaper ECM’ — it will not talk this serial bus.

    Expect: One clean CFM request after a known-good pair.

b1

ECM communications lost

lockout

IFC cannot communicate with the variable-speed blower. Furnace will not operate.

  1. 1 Reseat the serial plug

    On Amana ARVT80 this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. Same 14-pin harness — pins bent, corrosion, half-seated.

    Expect: Plug fully seated both ends. Correct motor for this cabinet.

  2. 2 Power and the data pair at the motor

    Line voltage at the motor, then the serial/data pair continuity. A half-seated plug or a pinched harness throws comm on a good motor. Motor vs IFC: if a known-good motor still b1s, the IFC serial driver is the fault.

    Expect: Line voltage present. Data pair not shorted to chassis.

  3. 3 Motor vs IFC serial driver

    Known-good motor still throws this code = Amana ARVT80 IFC serial driver. Known-good IFC still throws it = motor module. Do not put a PSC or 9-speed tap motor on a serial IFC. Power-cycle once to see if it is a hard loss or a glitch after a static event.

    Expect: One clean CFM request after a known-good pair.

b2

Motor HP mismatch vs shared-data set

lockout

Connected motor horsepower does not match the value in the furnace shared-data set. Furnace will not operate.

  1. 1 Read the plug / card on THIS cabinet

    On Amana ARVT80 the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Wrong replacement motor for this cabinet size.

    Expect: Plug / card part matches the rating plate and the replacement control bulletin.

  2. 2 Reseat, then confirm the menu

    Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. Wrong memory card after an IFC swap (see d0/d4).

    Expect: IFC recognizes the plug. No size-mismatch code.

  3. 3 Do not run it mismatched

    A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint. Do not ‘make it work’ with a different HP ECM — ComfortBridge CFM tables are card-specific.

    Expect: One clean sequence on the correct identity.

b3

Motor limiting (power / speed / temp)

warn

ECM is folding back on power, speed, or temperature. Furnace keeps running at reduced CFM.

  1. 1 Airflow before you touch the limit

    On Amana ARVT80 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Amana ARVT80 blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Filter, coil, and total external static vs the AMVC96 blower chart.

    Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

b4 / b5 / b7

Motor trip / locked rotor / failed start

lockout

b4 = lost rotor or overload trip (shuts down and retries). b5 = locked rotor after 10 start attempts. b7 = motor parameters missing or failed to start after 40 attempts.

  1. 1 Is the wheel free?

    Spin the Amana ARVT80 blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Wheel rub, debris in the housing, seized bearings.

    Expect: Wheel free. Correct motor family for this IFC.

  2. 2 Command vs rotation

    Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Static so high the motor cannot start the wheel.

    Expect: Command present. Motor amps in range, not locked.

  3. 3 Static and the wrong motor

    High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call. Harness intermittents look like b7. Prove the 14-pin before a motor or IFC.

    Expect: Static on the blower chart. Matching motor / shared-data card.

b9

Low indoor airflow

warn

Indoor airflow fell below the calculated minimum. Furnace stages down (high to low) and will halt if CFM reaches 0.

  1. 1 Is the wheel free?

    Spin the Amana ARVT80 blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Filter, coil, closed registers, undersized return.

    Expect: Wheel free. Correct motor family for this IFC.

  2. 2 Command vs rotation

    Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. IFC heat/cool CFM setting vs the coil and the outdoor.

    Expect: Command present. Motor amps in range, not locked.

  3. 3 Static and the wrong motor

    High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call. TES. A communicating motor will ramp into a brick and then b9 / E3.

    Expect: Static on the blower chart. Matching motor / shared-data card.

d0 / d4

Shared data / memory card

lockout

d0 = IFC has no shared-data set (replacement board, missing card) and cannot drive the serial ECM or calculate CFM. d4 = card rejected (wrong model card).

  1. 1 Read the plug / card on THIS cabinet

    On Amana ARVT80 the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. After an IFC swap the AMVC96 memory card must be installed and seated.

    Expect: Plug / card part matches the rating plate and the replacement control bulletin.

  2. 2 Reseat, then confirm the menu

    Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. A GMVC96 card usually twins; an AMVM97, AVPTC, or AR9T96 card is d4.

    Expect: IFC recognizes the plug. No size-mismatch code.

  3. 3 Do not run it mismatched

    A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint. Do not run the furnace on empty shared data and guess CFM.

    Expect: One clean sequence on the correct identity.

Workflows

ARVT80 vs ARVT96

Badge says Amana ComfortBridge.

  1. 1 Prove the call and the live code

    Plate ARVT80 = 80% metal. Plate ARVT96 = 96% PVC + 0.5" heat-ESP hard limit.

    Expect: Write whatever ComfortBridge 80% IFC — ARVT80 card, metal-vent E2/E9 is showing. IFC menu history. Write the three characters.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Same CoolCloud habit. Wrong memory card is d4 and a dead serial motor.

    Expect: Prove limits: IFC proves primary/aux/rollout closed. Open limit → E3. Open 24V fuse → E5. No 115V / door switch / internal → EE.

  3. 3 Confirm with a number, then the next part

    E2 on this plate is a chimney. Do not prime a trap that is not here.

    Expect: Data pair: OEM communicating voltage / polarity — never 24 VAC between the data pins. · Motor harness: 14-pin serial ECM, fully seated. No tap plugs. Do not hang an AR9T96 9-speed here.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Data pair

OEM communicating voltage / polarity — never 24 VAC between the data pins.

Motor harness

14-pin serial ECM, fully seated. No tap plugs. Do not hang an AR9T96 9-speed here.

Flame rod

µA per this IFC sticker, not the AR9T96 card. Rising while running is the goal.

LPS / HPS

Both NO. Two hoses, two taps, never teed. Closed only when that inducer speed is making the collector setpoint.

Manifold low / high

Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.

HSI

Nitride, 120 VAC during warm-up. Cold ohms per sticker.

Memory card

Seated AMVC96 (or GMVC96 twin) card after any IFC swap. d0 empty, d4 wrong card.

24V fuse / door

Fuse intact (E5). Door switch made, 115 VAC at L1 (EE if not).

Gotchas

  • ARVT96 is the 96% ComfortBridge plate techs just left. Same display, different vent and a different card.
  • AR9S80 is the 9-speed 80% sister — 0140F20001-B, no CoolCloud.

Related plates

Install this plate

Install Amana ARVT80 as ComfortBridge · two-stage · serial VS · 80% Cat I.

ComfortBridge · two-stage · serial VS · 80% Cat I

This plate — not the sister SKU

  • Not ARVT96 / ADVT96 (96% ComfortBridge — same tokens, collector and trap). Not AR9T80 / AR9S80 (9-speed 24V). Not AMVC96 (96% ComfortBridge older plate).
  • ARVT96 is the 96% ComfortBridge plate techs just left. Same display, different vent and a different card.
  • AR9S80 is the 9-speed 80% sister — 0140F20001-B, no CoolCloud.

IFC on this door

  • Same E/b/d language as AMVC96. Vent is not. E2/E9 = chimney / B-vent.
  • Memory card is ARVT80 / ADVT80. An ARVT96 or AMVC96 card is d4.

Hardware

  • AFUE: 80% · Category I metal vent
  • Control: ComfortBridge · CoolCloud · ARVT80 memory card
  • Sister SKU: ADVT80 downflow · Goodman GRVT80 / GDVT80

First fire

  1. 1Plate ARVT80 = 80% metal. Plate ARVT96 = 96% PVC + 0.5" heat-ESP hard limit.
  2. 2Same CoolCloud habit. Wrong memory card is d4 and a dead serial motor.
  3. 3E2 on this plate is a chimney. Do not prime a trap that is not here.

Do not on Amana ARVT80

  • Not ARVT96 / ADVT96 (96% ComfortBridge — same tokens, collector and trap). Not AR9T80 / AR9S80 (9-speed 24V). Not AMVC96 (96% ComfortBridge older plate).
  • ARVT96 is the 96% ComfortBridge plate techs just left. Same display, different vent and a different card.
  • AR9S80 is the 9-speed 80% sister — 0140F20001-B, no CoolCloud.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • Amana literature libraryLiterature searchGas furnace / air-handler PDFs. Match the plate, not just the Amana badge.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Standard limited warranty

    warranty sheet

    Amana furnace heat-exchanger / unit-replacement terms

    Registered residential furnace warranty terms · Limited warranty certificate

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal