ARVT96
ComfortBridge · two-stage · communicating VS · up to 97.50% AFUE
Current Amana ComfortBridge two-stage 96–97.5% with a serial variable-speed ECM, CoolCloud Bluetooth, and a two-speed inducer / dual PS. SS-ARVT96_ADVT96-R32 (Feb 2025): do not operate above 0.5" w.c. ESP in heating — 0.5–0.8" tables are cooling only. Compatible with any single-stage thermostat. This is not AR9T96 (9-speed taps) and not the older AMVC96 plate (memory card is ARVT96).
Not AR9T96 / GR9T96 (9-speed tap ECM, conventional 24V, single 7-seg E0–E9, 2-second recall hold). Not AR9S96 (single-stage, one PS, no ComfortBridge). Not AMVC96 (older ComfortBridge two-stage — same E/b/d language, different memory card and this SS’s 0.5" heat-ESP hard limit). Not AMVM97 (modulating valve + variable inducer).
Input / AFUE
40–120 kBtu · up to 97.50% AFUE (SS-ARVT96_ADVT96-R32 Feb 2025) · 40 ng/J Low NOx, not SCAQMD after Oct 1 2019
SKUs (upflow)
ARVT960403BN / 0603BN / 0803BN / 0804CN / 1005CN / 1005DN / 1205DN
SKUs (downflow)
ADVT960403BN / 0603BN / 0804CN / 1005CN / 1205DN
Staging
Two-stage gas valve · two-speed inducer · dual pressure switches
Blower
Communicating variable-speed ECM (serial CFM, no tap plugs). Ships high-speed cooling — installer must adjust. ~400 CFM/ton.
Heat ESP
HARD LIMIT 0.5" w.c. in heating (SS p.7). CFM between 0.5" and 0.8" is tabulated for cooling only.
Rec. heat CFM
0403BN 1025 · 0603BN 1200 · 0803BN 1400 · 0804CN 1760 · 1005CN 1770 · 1005DN 2000 · 1205DN 2150 (mid-rise)
Ignition
120 VAC silicon nitride HSI
Vent
Cat IV PVC 2–3" · 2-pipe or 1-pipe · 24" front service
Control
ComfortBridge IFC · UP/MENU/DOWN · CoolCloud Bluetooth · compatible with any single-stage thermostat
Accessories
LPM-34 all SKUs · HASFK-1/2/3 (1005DN TBD) · 72950/72951 · RF000142 · EFR02 · 0170K00000S/00001S · 0270F20723 (upflow) / 0270F20670 (downflow) · CFSB17/21/24 downflow
Sister SKU
ADVT96 downflow. Not AMVC96 (older card). Not AR9T96 taps.
This board
ComfortBridge IFC · three 7-segment digits + UP/MENU/DOWN · CoolCloud
- Three digits and menu buttons (UP / MENU / DOWN) — not the AR9T96 single 7-seg and not 9-speed taps. Status words (idle, Ht1, Ht2, CF, CL1, CL2) are run states, not faults.
- SS wiring p.9 is the ComfortBridge menu IFC — no E-code table printed on that sheet. Door card on THIS cabinet wins. ComfortBridge two-stage language on this family is E0–E9 (dual PS), b0–b9 (serial ECM), d0/d4 (memory card).
- Shared-data memory card is ARVT96. d0 = no card / empty set. d4 = wrong-model card (AMVC96, AMVM97, AR9T96, AVPTC). The replacement board will not drive the serial ECM without the correct ARVT96 card.
- Compatible with any single-stage thermostat (SS). 24V W/W1 fallback is legal. CFM still comes from IFC tables, not tap plugs. A leftover data pair shorted to R/C will look like a dead bus.
- CoolCloud Bluetooth is the menu for CFM, outdoor type, and commissioning. Do not look for F01–F09 heat taps — there are none.
IFC menu fault history (not the AR9T96 2-second hold). Step UP/MENU/DOWN to last faults. Write the exact token off THIS door card. Power cycle can clear the active display; stored history lives in constant memory.
Universal swap
No White-Rodgers, ICM, or Honeywell universal. This is a communicating ComfortBridge IFC with a serial ECM.
Silk: ARVT96 · ComfortBridge
White-Rodgers
—ICM
—Honeywell
—- Any 50A55-843 / 50A65-843 / 50M56U-843 / 50M56X-843 / S9200U1000 universal — those are conventional 24V HSI, not this data bus.
- ICM280 / 2811 / 2810 / 282B — wrong IFC family.
- An AMVC96 board — same E/b/d language, different memory card and this SS’s 0.5" heat-ESP limit.
- 50M56-743 / PCBBF132 — that is the 9-speed tap cousin (AR9T96).
After you pull the dead card
- 1Order the OEM ComfortBridge IFC for ARVT96 / ADVT96. Program with CoolCloud. Do not clone an AMVC96 card into this cabinet.
Field wiring
Written landings for Amana ARVT96. Not a factory schematic.
Goodman / Amana / Daikin communicating two-stage. Outdoor on 1 and 2 when the outdoor talks. A 24V GSX16 still wants Y, not data.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC120V
- 2Call. Data pair or 24V W → IFCBus or 24V
- 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
- 4Ignite. IFC → HSI → valve120V igniter
- 5Blow. IFC → serial ECMNo tap, no cap
This indoor
Current ComfortBridge 96%. ARVT96 card — not AMVC96.
Communicating outdoor
GSXC / ASXC / GXV / DZ / FIT on the same bus. CoolCloud or Daikin One at the wall.
CoolCloud / Daikin One
Menus on the indoor. Do not put R/C on 1 and 2.
- 1DataData
- 2DataData
ComfortBridge / ComfortNet IFC
Memory card must match THIS cabinet (ARVT96 card is not AMVC96).
- 1Data to outdoorData
- 2Data to outdoorData
- R24V accessories24V
- CCommon24V
Landing
- DataIFC 1outdoor 1 · IFC 2outdoor 2
Data. Polarity matters.
24V outdoor on this IFC
GSX16 / GLXS4B / any contactor outdoor. Land Y. Leave 1/2 empty.
Conventional stat (allowed)
W1/W2/Y/G on the IFC 24V strip. Not on 1/2.
- RHot24V
- CCommon24V
- W1Heat24V
- YCool24V
- GFan24V
Landing
- 24VStat YIFC Youtdoor Y
~24 VAC. Data wire is a miswire.
IFC harness — communicating two-stage
Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.
Transformer + fuse
24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.
- L1 / N120VLine
- R / C24V strip24V
- FUSEOn the IFC24V
24V safety chain
Limit / rollout / door still open the heat path. Codes are on THIS IFC language.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Two-speed inducer + dual PS
Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.
- IND LO/HITwo-speed inducerLine
- LPSLow prove24V
- HPSHigh prove24V
HSI + two-stage valve
Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.
- HSI120V igniterLine
- MV / HV24V low / high solenoids24V
- FLAMEµA DC24V
Serial variable-speed ECM
IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.
- SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
- CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V
Landing
- LineCallIFCinducerprove
Low then high
- LineIFCHSIvalve
120V igniter, 24V or serial valve
- 24VFlame rodIFC
µA DC
- DataIFCserial blower
No F-taps. No PSC cap.
Prove it
- Indoor family first. Communicating outdoor = 1/2. Contactor outdoor = Y.
- Memory card / CoolCloud sees THIS furnace.
Do not
- Do not drop an ARVT96 card into AMVC96 or the other way around.
- Do not land 1/2 on a GR9T96.
1 and 2 are the published ComfortBridge / ComfortNet pair.
Sequence
- 1
Call
Communicating stat requests heat capacity, or a single-stage 24V stat closes W. CFM still comes from the IFC tables, not taps.
- 2
Prove limits
IFC proves primary/aux/rollout closed. Open limit → E3. Open 24V fuse → E5. No 115V / door switch / internal → EE.
- 3
Low inducer / LPS
Two-speed inducer starts low. Low-stage PS must close. Already closed with inducer off → E1. Never closes → E2.
- 4
HSI / low-fire valve
Silicon nitride warm-up, then first-stage solenoid. Open igniter / no-ground → E7. Flame must prove. Failures stack toward E0.
- 5
Blower
Serial ECM ramps to the IFC heat CFM table. SS rec. high-heat CFM is cabinet-specific (1025 on 0403BN through 2150 on 1205DN). Silent motor → b0/b1. Do not hang an AR9T96 9-speed motor on this harness.
- 6
High fire
Communicating capacity or W2 / staging timer. Inducer goes high. High-stage PS must close (E9 if open, E8 if already closed). Second-stage solenoid opens.
- 7
Satisfied
Valve off, inducer post-purge, blower heat-off delay. Unexpected flame after valve-off → E4.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
idle / Ht1 / Ht2 / CF / CL1 / CL2
Status, not a fault
Normal run states on the triple display. idle = standby. Ht1 / Ht2 = low / high heat. CF = continuous fan. CL1 / CL2 = cooling stage.
1 Confirm this is not a fault
On the Amana ARVT96 this readout (idle / Ht1 / Ht2 / CF / CL1 / CL2) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the Amana ARVT96 IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: Do not replace the board because it says Ht1 or CF.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch ComfortBridge IFC · three 7-segment digits + UP/MENU/DOWN · CoolCloud through one cycle and write the first real fault that replaces this status word.
Expect: Call: Communicating stat requests heat capacity, or a single-stage 24V stat closes W. CFM still comes from the IFC tables, not taps.
E0
System / ignition lockout
Control failed to sense flame after retries and shut off gas.
1 Watch one full try — do not reset
Write the Amana ARVT96 code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. Watch one full try: inducer, HSI glow, valve click, flame, µA.
Expect: Call → Prove limits → Low inducer / LPS → HSI / low-fire valve → Blower → High fire → Satisfied
2 Gas and the valve
Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence. Gas supply and manifold (low then high).
Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
3 Flame prove, then the lockout timer
Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets. Ground and flame-rod cleanliness.
Expect: Stable µA after light-off. No new PS/limit code.
E1
Low-stage PS stuck closed
Low-stage pressure switch is made with the inducer off.
1 Unplug the switch with the inducer off
On Amana ARVT96 this code is the switch made when the inducer is not running. Unplug that switch only. Unplug the LPS. If the code changes, the switch is welded or the hose is holding residual draft.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
2 Water in the hose vs a welded switch
Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Hose routed downhill? Water fakes a closed switch.
Expect: Hose empty. Switch opens with no draft.
3 IFC input last
If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Amana ARVT96 IFC input is shorted. Do not keep swapping switches. IFC input shorted — only after the switch ohms open.
Expect: Known-good open switch + open harness = code gone. If not, IFC.
E2
Low-stage PS stuck open
Inducer is on low and the low-stage switch will not close.
1 Prove inducer and the live code
Do not pull power — that clears the Amana ARVT96 active code. Write E2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer spinning? 120 VAC at the inducer on a heat call.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Collector box, inducer outlet, and condensate trap — this 96% will not make pressure with a full trap.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. PVC intake/exhaust (bird screen, ice, long run, wind).
Expect: LPS / HPS: Both NO. Two hoses, two taps, never teed. Closed only when that inducer speed is making the collector setpoint.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E3
Open primary / aux / rollout limit
A limit opened. Airflow or overfire. On this plate, heat ESP above 0.5" is a documented hard limit.
1 Treat this as flame outside the exchanger
Do not reset the Amana ARVT96 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. IFC heat CFM vs the SS rec. CFM for this SKU — not a 9-speed tap. Total external static in HEAT. SS p.7: do not operate above 0.5" w.c. ESP in heating. 0.5–0.8" tables are cooling only.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Amana ARVT96 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave. Filter, wheel, coil, return size. Bottom-return flanges unfolded (SS: ~18% loss if left folded).
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
E4
Flame sensed with no call for heat
Rod sees flame with both solenoids de-energized.
1 Shut the gas cock first
On Amana ARVT96 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Rod shorted to ground or IFC flame circuit.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
E5
Open 24V fuse
Low-voltage fuse on the IFC is open.
1 Find the 24 V short before you replace the fuse
On Amana ARVT96 an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. 24 V short on W, Y, G, humidifier, EAC, or a leftover data pair landed on R/C.
Expect: Fuse out. 24 V transformer still good. Harness isolated.
2 Replace the fuse with the harness off
New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC). Unplug the tstat / data harness and replace the fuse.
Expect: Fuse holds with harness off. Dies when the shorted lead lands.
3 If it blows with the harness off
Short is on the Amana ARVT96 IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.
Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.
E6
Low flame-sense µA
Flame is present but the micro-amp signal is below the IFC threshold.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Amana ARVT96 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod with a non-scratch pad — not sandpaper.
Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Chassis ground to burner box and IFC.
Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
3 Prove it is not a switch opening
Watch the live Amana ARVT96 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Manifold / orifice / LP conversion (this plate is LPM-34 on every SKU).
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E7
Igniter open / no-ground
Igniter is open, not connected, or the IFC failed its ground check.
1 Ohms at the igniter, then at the IFC
On Amana ARVT96 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Nitride ohms per sticker. 120 VAC during warm-up.
Expect: HSI: Nitride, 120 VAC during warm-up. Cold ohms per sticker.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Burner-box ground screw and painted-cabinet star washer.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
E8
High-stage PS stuck closed
High-stage pressure switch is made with the inducer not on high. Furnace runs low only.
1 Unplug the switch with the inducer off
On Amana ARVT96 this code is the switch made when the inducer is not running. Unplug that switch only. This is the second switch — do not confuse with E1.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
2 Water in the hose vs a welded switch
Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Welded HPS or water-filled hose.
Expect: Hose empty. Switch opens with no draft.
3 IFC input last
If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Amana ARVT96 IFC input is shorted. Do not keep swapping switches. IFC calling high when it should be low — W2 shorted to W1 on 24V fallback.
Expect: Known-good open switch + open harness = code gone. If not, IFC.
E9
High-stage PS stuck open
Inducer on high, high-stage switch never closes. Classic ‘runs on low, will not go high.’
1 Prove inducer and the live code
Do not pull power — that clears the Amana ARVT96 active code. Write E9. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer actually changes speed on a high-fire request? Listen / amp it.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. HPS hose on the high-fire tap, not teed to the low switch.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Vent capacity / wind / shared chase. High fire needs more draft than E2 ever saw.
Expect: LPS / HPS: Both NO. Two hoses, two taps, never teed. Closed only when that inducer speed is making the collector setpoint.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
EA
Reversed polarity / poor ground
L1/N reversed or chassis ground missing. Furnace will not operate.
1 Hot and neutral at the IFC, not the disconnect
On Amana ARVT96 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot and neutral at the IFC, not just the disconnect.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Burner box to IFC ground screw.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
EE
No 115V to control / internal / door switch
No line voltage reaching the IFC, door switch open, or an internal control condition. This is power, not a ComfortBridge data-pair code.
1 Measure at the IFC under load
On Amana ARVT96 line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. Furnace switch, breaker, and blower-door switch fully made.
Expect: Voltage in the rating-plate window under load.
2 Drop, breaker, and the whip
Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. 115 VAC at L1/N on the IFC.
Expect: Minimal drop. Tight lugs. Correct breaker size.
3 Transformer 24 V last
If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call. If the IFC is alive and the stat is dark, that is the data pair — not EE.
Expect: 24 V holds under load. Line stays in window.
b0
ECM blower not running
IFC commanded the serial ECM and does not detect it running.
1 Reseat the serial plug
On Amana ARVT96 this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. 14-pin harness seated at motor and IFC. No tap plugs on this motor.
Expect: Plug fully seated both ends. Correct motor for this cabinet.
2 Power and the data pair at the motor
Line voltage at the motor, then the serial/data pair continuity. A half-seated plug or a pinched harness throws comm on a good motor. 120 VAC to the motor, wheel free, no wet winding.
Expect: Line voltage present. Data pair not shorted to chassis.
3 Motor vs IFC serial driver
Known-good motor still throws this code = Amana ARVT96 IFC serial driver. Known-good IFC still throws it = motor module. Do not put a PSC or 9-speed tap motor on a serial IFC. Do not install an AR9T96 9-speed motor as a ‘cheaper ECM’ — it will not talk this serial bus.
Expect: One clean CFM request after a known-good pair.
b1
ECM communications lost
IFC cannot communicate with the variable-speed blower.
1 Reseat the serial plug
On Amana ARVT96 this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. Same 14-pin harness — pins bent, corrosion, half-seated.
Expect: Plug fully seated both ends. Correct motor for this cabinet.
2 Power and the data pair at the motor
Line voltage at the motor, then the serial/data pair continuity. A half-seated plug or a pinched harness throws comm on a good motor. Motor vs IFC: if a known-good motor still b1s, the IFC serial driver is the fault.
Expect: Line voltage present. Data pair not shorted to chassis.
3 Motor vs IFC serial driver
Known-good motor still throws this code = Amana ARVT96 IFC serial driver. Known-good IFC still throws it = motor module. Do not put a PSC or 9-speed tap motor on a serial IFC.
Expect: One clean CFM request after a known-good pair.
b2
Motor HP mismatch vs shared-data set
Connected motor horsepower does not match the value in the furnace shared-data set.
1 Read the plug / card on THIS cabinet
On Amana ARVT96 the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Wrong replacement motor for this cabinet size.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
2 Reseat, then confirm the menu
Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. Wrong memory card after an IFC swap (see d0/d4). An AMVC96 card is the usual miss on this new plate.
Expect: IFC recognizes the plug. No size-mismatch code.
3 Do not run it mismatched
A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint.
Expect: One clean sequence on the correct identity.
b3 / b9
Motor limiting / low indoor airflow
b3 = folding back on power/speed/temp. b9 = airflow below calculated minimum.
1 Airflow before you touch the limit
On Amana ARVT96 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, coil, TES. Heat ESP must stay ≤ 0.5" on this SS — a brick duct is b9 / E3, not a bad motor.
Expect: Heat CFM: SS rec. high-heat: 0403BN 1025 · 0603BN 1200 · 0803BN 1400 · 0804CN 1760 · 1005CN 1770 · 1005DN 2000 · 1205DN 2150.
2 Measure static and temperature rise
Total external static vs the Amana ARVT96 blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. IFC heat CFM vs the SS rec. CFM for this SKU (1025–2150).
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Return undersized or a 5" media cabinet the installer added.
Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
b4 / b5 / b7
Motor trip / locked rotor / failed start
b4 = lost rotor or overload. b5 = locked rotor after start attempts. b7 = failed to start / missing parameters.
1 Is the wheel free?
Spin the Amana ARVT96 blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Wheel rub, debris, seized bearings.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Static so high the motor cannot start the wheel — prove TES before a motor.
Expect: Heat CFM: SS rec. high-heat: 0403BN 1025 · 0603BN 1200 · 0803BN 1400 · 0804CN 1760 · 1005CN 1770 · 1005DN 2000 · 1205DN 2150.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call. Harness intermittents look like b7. Prove the 14-pin before a motor or IFC.
Expect: Static on the blower chart. Matching motor / shared-data card.
d0 / d4
Shared data / memory card
d0 = IFC has no shared-data set (replacement board, missing card). d4 = card rejected (wrong model card).
1 Read the plug / card on THIS cabinet
On Amana ARVT96 the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. After an IFC swap the ARVT96 memory card must be installed and seated.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
2 Reseat, then confirm the menu
Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. An AMVC96, AMVM97, AVPTC, or AR9T96 card is d4 on this plate. The card is labeled for THIS model, not ‘any ComfortBridge 96%.’
Expect: IFC recognizes the plug. No size-mismatch code.
3 Do not run it mismatched
A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint. Do not run the furnace on empty shared data and guess CFM.
Expect: One clean sequence on the correct identity.
Workflows
Identify ARVT96 vs AMVC96 vs AR9T96
First minute. Badge says Amana 96% and the last tech mixed boards.
1 Prove the call and the live code
Plate ARVT96 / ADVT96 = stay here. ComfortBridge + CoolCloud + two-stage VS. Memory card says ARVT96.
Expect: Write whatever ComfortBridge IFC · three 7-segment digits + UP/MENU/DOWN · CoolCloud is showing. IFC menu fault history (not the AR9T96 2-second hold). Step UP/MENU/DOWN to last faults. Write the exact token off THIS door card. Power cycle can clear the active display; stored history lives in constant memory.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Plate AMVC96 = older ComfortBridge two-stage. Same E/b/d language, different card and no 0.5" heat-ESP callout on that older SS. Use that chart if the plate is AMVC96.
Expect: Prove limits: IFC proves primary/aux/rollout closed. Open limit → E3. Open 24V fuse → E5. No 115V / door switch / internal → EE.
3 Confirm with a number, then the next part
Plate AR9T96 = 9-speed taps, single 7-seg, 2-second recall hold, no menu buttons. Wrong page. Plate AR9S96 = one PS, E0–E7, heat F02. Wrong page. Do not drop an AMVC96 memory card into this IFC and expect it to commission. d4.
Expect: Data pair: OEM communicating voltage / polarity — never 24 VAC between the data pins. Single-stage 24V fallback is legal; CFM still from IFC tables. · Motor harness: 14-pin serial ECM, fully seated. No tap plugs. Do not hang an AR9T96 9-speed here.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
No heat on ComfortBridge or 24V
Stat calling heat, furnace idle or locked, or the display is dark.
1 Prove the call and the live code
Photograph the triple display and the stat before you pull a wire. Status vs E-code vs b-code vs d0 vs EE.
Expect: Write whatever ComfortBridge IFC · three 7-segment digits + UP/MENU/DOWN · CoolCloud is showing. IFC menu fault history (not the AR9T96 2-second hold). Step UP/MENU/DOWN to last faults. Write the exact token off THIS door card. Power cycle can clear the active display; stored history lives in constant memory.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Communicating or single-stage 24V? SS says any single-stage thermostat is legal. Leftover data wires on R/C still take the bus down.
Expect: Prove limits: IFC proves primary/aux/rollout closed. Open limit → E3. Open 24V fuse → E5. No 115V / door switch / internal → EE.
3 Confirm with a number, then the next part
If communicating: data-pair polarity and splices (never 24 VAC between the data pins). Door switch / 115 VAC (EE). 24V fuse (E5). W or communicating heat present? Inducer on low? Silent → inducer / IFC. Running and E2 → trap, hose, LPS, vent. E1 with inducer off → unplug LPS.
Expect: Data pair: OEM communicating voltage / polarity — never 24 VAC between the data pins. Single-stage 24V fallback is legal; CFM still from IFC tables. · Motor harness: 14-pin serial ECM, fully seated. No tap plugs. Do not hang an AR9T96 9-speed here.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
E3 / b9 — heat ESP over 0.5"
Limits, low CFM, or a noisy heat call on a new ARVT96.
1 Prove the call and the live code
SS p.7 hard limit: do not operate above 0.5" w.c. ESP in heating. The 0.5–0.8" numbers on the sheet are cooling only.
Expect: Write whatever ComfortBridge IFC · three 7-segment digits + UP/MENU/DOWN · CoolCloud is showing. IFC menu fault history (not the AR9T96 2-second hold). Step UP/MENU/DOWN to last faults. Write the exact token off THIS door card. Power cycle can clear the active display; stored history lives in constant memory.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Measure TES on a high-heat call. Above 0.5" → return/filter/coil/duct, not a ‘bad VS motor.’
Expect: Prove limits: IFC proves primary/aux/rollout closed. Open limit → E3. Open 24V fuse → E5. No 115V / door switch / internal → EE.
3 Confirm with a number, then the next part
Confirm IFC heat CFM against the SS rec. for this SKU (1025 on 0403BN up to 2150 on 1205DN). Bottom return: unfold the flanges. SS notes ~18% airflow loss if you leave them folded. Airflows over ~1600 CFM need two-side return or side+bottom, min 20×25 filter (0804C and larger).
Expect: Data pair: OEM communicating voltage / polarity — never 24 VAC between the data pins. Single-stage 24V fallback is legal; CFM still from IFC tables. · Motor harness: 14-pin serial ECM, fully seated. No tap plugs. Do not hang an AR9T96 9-speed here.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
E2 / E9 draft (dual PS still exist)
No heat, or runs on low only. Display E2 or E9.
1 Prove the call and the live code
ComfortBridge did not delete the dual pressure switches. E2 is low-fire prove, E9 is high-fire prove — two hoses, two taps, never teed.
Expect: Write whatever ComfortBridge IFC · three 7-segment digits + UP/MENU/DOWN · CoolCloud is showing. IFC menu fault history (not the AR9T96 2-second hold). Step UP/MENU/DOWN to last faults. Write the exact token off THIS door card. Power cycle can clear the active display; stored history lives in constant memory.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Trap and collector first. A drowned 96% looks like E2 overnight and E9 on the first cold morning that actually calls high.
Expect: Prove limits: IFC proves primary/aux/rollout closed. Open limit → E3. Open 24V fuse → E5. No 115V / door switch / internal → EE.
3 Confirm with a number, then the next part
Inducer actually on (E2) or actually on high (E9)? 120 VAC and a speed change. Hoses: LPS on the low tap, HPS on the high tap. Water fakes E1/E8. Cracked hose fakes E2/E9. Vent/intake: bird screen, ice, long 2" on a 100–120 kBtu high fire, wind on a sidewall pair.
Expect: Data pair: OEM communicating voltage / polarity — never 24 VAC between the data pins. Single-stage 24V fallback is legal; CFM still from IFC tables. · Motor harness: 14-pin serial ECM, fully seated. No tap plugs. Do not hang an AR9T96 9-speed here.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
d0 after a board swap
Replacement IFC, display d0 or d4, motor will not run.
1 Prove the call and the live code
A replacement ComfortBridge IFC ships without this furnace’s shared-data set. d0 is expected until the ARVT96 card is in.
Expect: Write whatever ComfortBridge IFC · three 7-segment digits + UP/MENU/DOWN · CoolCloud is showing. IFC menu fault history (not the AR9T96 2-second hold). Step UP/MENU/DOWN to last faults. Write the exact token off THIS door card. Power cycle can clear the active display; stored history lives in constant memory.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Install the ARVT96 memory card. Seat it fully. An AMVC96 ‘96% ComfortBridge’ card is d4 on this plate.
Expect: Prove limits: IFC proves primary/aux/rollout closed. Open limit → E3. Open 24V fuse → E5. No 115V / door switch / internal → EE.
3 Confirm with a number, then the next part
d4 = wrong card. AMVM97, AVPTC, AR9T96, or a generic 96% card will be rejected. After the card takes, verify CoolCloud outdoor type and heat CFM against the SS rec. for this SKU before you leave.
Expect: Data pair: OEM communicating voltage / polarity — never 24 VAC between the data pins. Single-stage 24V fallback is legal; CFM still from IFC tables. · Motor harness: 14-pin serial ECM, fully seated. No tap plugs. Do not hang an AR9T96 9-speed here.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Data pair
OEM communicating voltage / polarity — never 24 VAC between the data pins. Single-stage 24V fallback is legal; CFM still from IFC tables.
Motor harness
14-pin serial ECM, fully seated. No tap plugs. Do not hang an AR9T96 9-speed here.
Heat ESP
≤ 0.5" w.c. in heating (SS p.7 hard limit). 0.5–0.8" is cooling only.
Heat CFM
SS rec. high-heat: 0403BN 1025 · 0603BN 1200 · 0803BN 1400 · 0804CN 1760 · 1005CN 1770 · 1005DN 2000 · 1205DN 2150.
LPS / HPS
Both NO. Two hoses, two taps, never teed. Closed only when that inducer speed is making the collector setpoint.
Manifold low / high
Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
HSI
Nitride, 120 VAC during warm-up. Cold ohms per sticker.
Memory card
Seated ARVT96 card after any IFC swap. AMVC96 card is d4.
Gotchas
- Techs treat ARVT96 like AR9T96 and start looking for heat taps. There are none. Triple display + 14-pin serial motor + CoolCloud.
- Techs treat ARVT96 like AMVC96 and drop in the older memory card. d4, silent blower. The card is labeled ARVT96.
- 0.5" heat ESP is a hard limit on this SS, not a suggestion. A duct that ‘ran fine’ on a 9-speed AR9T96 can E3/b9 here.
- Furnaces ship on high-speed cooling. Installer must set CoolCloud / menu CFM. Leaving it on high heat CFM in a tight return is an E3 call.
- LPM-34 is the LP kit on every ARVT96 / ADVT96 SKU. Not LPM-33 (AR9S96) and not LPM-30 (AR9T96 0303AN).
- Single-stage thermostat is legal. That does not turn this into a tap furnace. CFM still comes from the IFC tables.
- Bottom return: unfold the flanges. SS notes ~18% airflow loss — looks like a limit/noise call on a brand-new install.
- Door card on THIS cabinet wins. The spec-sheet wiring page has the ComfortBridge menu, not a printable E-table.
Related plates
- amana-amvc96Older ComfortBridge two-stage VS cousin. Same E/b/d language — different memory card and no 0.5" heat-ESP hard limit on that plate.
- amana-ar9t969-speed tap, conventional 24V, single 7-seg. Do not use that chart on this communicating VS IFC.
- amana-ar9s96Single-stage 9-speed sister — one PS, 0140F20003-B, E0–E7. Not ComfortBridge.
- amana-amvm97Modulating ComfortBridge cousin — 0–100% valve and variable inducer. Do not apply two-stage staging tests.
- goodman-gmvc96Goodman ComfortBridge two-stage twin of AMVC96 — not this newer ARVT96 plate.
Install this plate
Install ARVT96 as ComfortBridge communicating two-stage VS. The ARVT96 memory card is part of the furnace. Heat ESP stays at or under 0.5".
Cat IV PVC · ComfortBridge data pair · CoolCloud · 14-pin serial ECM · dual PS · 24V single-stage fallback · 0.5" heat-ESP hard limit
Cabinet & air
- Move the ARVT96 memory / shared-data card with the IFC. An AMVC96 card is d4 on this plate.
- No tap card. Heat CFM comes from IFC tables. SS rec. high-heat CFM: 0403BN 1025 · 0603BN 1200 · 0803BN 1400 · 0804CN 1760 · 1005CN 1770 · 1005DN 2000 · 1205DN 2150.
- HARD LIMIT: do not operate above 0.5" w.c. ESP in heating (SS p.7). The 0.5–0.8" numbers are cooling only.
- Ships high-speed cooling. Installer must set CoolCloud / menu CFM (~400 CFM/ton).
- Bottom return: unfold the flanges (~18% loss if you don't). ADVT96 downflow uses CFSB17/21/24.
Vent & condensate
- Same Cat IV PVC / trap / collector rules as the other Amana 96%s. Dual PS still exist — E1/E2 vs E8/E9 physics did not go away because the display is triple 7-seg.
- Do not tee the two pressure-switch hoses. Communicating does not change draft prove.
- 72950 2" concentric (not 1205D) / 72951 3". Horizontal drain 0270F20723 (upflow) / 0270F20670 (downflow).
Control wiring
- ComfortBridge / CoolCloud preferred. Data pair is not 24V. Landing R/C on the data terminals kills the bus.
- SS: compatible with any single-stage thermostat. 24V W fallback is legal. CFM still comes from IFC tables, not thermostat G and not 9-speed taps.
- LP kit is LPM-34 on every ARVT96 / ADVT96 SKU. High altitude HASFK-1/2/3 (1005DN TBD).
- Door card on THIS cabinet wins. Spec-sheet wiring is the ComfortBridge UP/MENU/DOWN IFC — not an AR9T96 tap card.
First fire
- 1Confirm the ARVT96 shared-data card is seated for this cabinet before you gas it. AMVC96 card = d4.
- 2CoolCloud / menu: set outdoor type and heat CFM to the SS rec. for this SKU. Idle / Ht1 / Ht2 / CF are status, not faults.
- 3Measure TES on high heat. If you are over 0.5" ESP, fix the duct/return — do not leave it.
- 4W or communicating heat: low-fire prove, then high. Watch E1/E2 vs E8/E9 — not b0 (that is the serial blower).
Do not on Amana ARVT96
- Do not drop a 9-speed or X-13 motor on the 14-pin serial plug.
- Do not treat this as AR9T96. Single 7-seg E0–E9 recall (2-second hold) is the other board.
- Do not install an AMVC96 memory card and expect it to commission. The card is ARVT96.
- Do not run heat above 0.5" w.c. ESP. The 0.5–0.8" table is cooling only.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- Amana literature libraryLiterature searchGas furnace / air-handler PDFs. Match the plate, not just the Amana badge.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Standard limited warranty
warranty sheetAmana furnace heat-exchanger / unit-replacement terms
Registered residential furnace warranty terms · Limited warranty certificate
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal