ComfortBridge / ComfortNet furnace
1 / 2 data — or 24V
Goodman / Amana / Daikin communicating two-stage. Outdoor on 1 and 2 when the outdoor talks. A 24V GSX16 still wants Y, not data.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC120V
- 2Call. Data pair or 24V W → IFCBus or 24V
- 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
- 4Ignite. IFC → HSI → valve120V igniter
- 5Blow. IFC → serial ECMNo tap, no cap
Communicating outdoor
GSXC / ASXC / GXV / DZ / FIT on the same bus. CoolCloud or Daikin One at the wall.
CoolCloud / Daikin One
Menus on the indoor. Do not put R/C on 1 and 2.
- 1DataData
- 2DataData
ComfortBridge / ComfortNet IFC
Memory card must match THIS cabinet (ARVT96 card is not AMVC96).
- 1Data to outdoorData
- 2Data to outdoorData
- R24V accessories24V
- CCommon24V
Landing
- DataIFC 1outdoor 1 · IFC 2outdoor 2
Data. Polarity matters.
24V outdoor on this IFC
GSX16 / GLXS4B / any contactor outdoor. Land Y. Leave 1/2 empty.
Conventional stat (allowed)
W1/W2/Y/G on the IFC 24V strip. Not on 1/2.
- RHot24V
- CCommon24V
- W1Heat24V
- YCool24V
- GFan24V
Landing
- 24VStat YIFC Youtdoor Y
~24 VAC. Data wire is a miswire.
IFC harness — communicating two-stage
Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.
Transformer + fuse
24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.
- L1 / N120VLine
- R / C24V strip24V
- FUSEOn the IFC24V
24V safety chain
Limit / rollout / door still open the heat path. Codes are on THIS IFC language.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Two-speed inducer + dual PS
Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.
- IND LO/HITwo-speed inducerLine
- LPSLow prove24V
- HPSHigh prove24V
HSI + two-stage valve
Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.
- HSI120V igniterLine
- MV / HV24V low / high solenoids24V
- FLAMEµA DC24V
Serial variable-speed ECM
IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.
- SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
- CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V
Landing
- LineCallIFCinducerprove
Low then high
- LineIFCHSIvalve
120V igniter, 24V or serial valve
- 24VFlame rodIFC
µA DC
- DataIFCserial blower
No F-taps. No PSC cap.
Prove it
- Indoor family first. Communicating outdoor = 1/2. Contactor outdoor = Y.
- Memory card / CoolCloud sees THIS furnace.
Do not
- Do not drop an ARVT96 card into AMVC96 or the other way around.
- Do not land 1/2 on a GR9T96.
1 and 2 are the published ComfortBridge / ComfortNet pair.