Goodman
EA
LockoutLine polarity / ground
L1/N reversed or chassis ground missing. HSI and flame sense both suffer.
Walk EA in Diagnose
9 plates — walk the one on the cabinet
First check
1 Hot and neutral at the IFC, not the disconnect
On Goodman GMEC96 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot and neutral at the IFC.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
The rest of the walkthrough is Diagnose.
On the plates
- Hot and neutral at the IFC, not just the disconnect.
- Burner box to IFC ground screw.
- Twinned jobs — follow the twinning kit, then look at EEJ.
- Hot and neutral at the IFC.
- 24V transformer leads swapped on a replacement IFC.
- Hot and neutral at the IFC. Burner-box ground screw.
- Burner-box ground screw.
Plates that use EA
Same number, other makers
EA on Goodman is not the same code on these plates.