GR9T80
Two-stage · 9-speed ECM · 80% Cat I
Goodman two-stage 80% with a 9-speed tap ECM and a single 7-seg IFC. Same E1/E2 vs E8/E9 split as GR9T96 — Category I metal vent instead of PVC. GD9T80 is downflow. This is not GRVT80 ComfortBridge and not GMS80 flash.
Not GR9T96 (96% PVC, dual PS on a collector). Not GRVT80 (ComfortBridge serial VS). Not GR9S80 (single-stage, one PS). Not AR9S80 (Amana single-stage 80% 9-speed).
AFUE
80% two-stage · Category I 4" metal vent
Staging
Two-stage valve · two-speed inducer · dual draft switches
Blower
9-speed ECM taps F01–F09 — not serial VS
Tstat
Conventional 24V W1/W2. No ComfortBridge pair.
Sister SKU
GD9T80 downflow · Amana AR9T80
This board
Single 7-seg two-stage IFC · 80% door
- E1/E2 low draft. E8/E9 high draft. Same tokens as GR9T96 — chimney physics.
- No E8/E9 on GR9S80 (one switch). No CoolCloud on this board.
- A2L pair codes only if this 80% is tied to an R-32 outdoor mitigation harness.
Standby hold >2 s plays last faults. Power cycle clears the live code.
Universal swap
If the silk is PCBBF132, 50M56-743. Still metal vent — not a 96% collector board.
Silk: PCBBF132 · PCBBF132S
White-Rodgers
- 50M56-743
Only if the silk is PCBBF132 / PCBBF132S. Photograph it — 80% doors are not all 132.
ICM
—Honeywell
—- 50A55-843 / 50M56U-843 / S9200U1000 — PSC single-stage will not drive this 9-speed or the second draft switch.
- A 96% PCBBF132 pulled from AR9T96 without checking the 80% door.
After you pull the dead card
- 1Kill power. Photograph the silk-screen part number on the dead board before you pull it.
- 2Match staging (1 vs 2 vs modulating), igniter (carbide / nitride / spark), and motor (PSC / ECMx / 9-speed tap / serial VS).
- 3Set heat-off delay and any 80+/90+ jumper to the door card. Prove one full try and flame µA before you leave.
- 4Prove metal-vent draft on both stages. Do not prime a trap.
Field wiring
Written landings for Goodman GR9T80. Not a factory schematic.
Two-stage conventional furnace. W1 low fire, W2 high fire. Outdoor staging is Y or Y1/Y2 — separate from the gas valve.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC → R120V / 24V
- 2Low. W1 → inducer LOW → LPS → HSI → valve LOWFirst fire
- 3High. W2 → inducer HIGH → HPS → valve HIGHSecond solenoid
- 4Flame. Rod → IFCµA DC both stages
- 5Blow. IFC → heat blowerAfter flame
This indoor
80% two-stage 9-speed. Same landing.
24V two-stage heat
Door has W1 and W2. Not Infinity. Not ComfortBridge.
Two-stage thermostat
A single-W stat never proves high fire. That is not a weak inducer.
- R24V hot24V
- CCommon24V
- W1Low-fire heat24V
- W2High-fire heat24V
- Y / Y1Cool24V
- Y2Outdoor high if the condenser is two-stage24V
- GFan24V
Two-stage IFC
W2 is high fire. Do not tee the pressure-switch hoses because there are two stages.
- RHot24V
- CCommon to outdoor24V
- W1Low fire24V
- W2High fire24V
- YCool out24V
- GBlower / cool tap24V
Landing
- 24VStat W1IFC W1
Low fire
- 24VStat W2IFC W2
High fire. Missing W2 = stuck on low.
- 24VStat YIFC Youtdoor Y
Cool
- 24VC throughout
Common
IFC harness — two-stage heat
W1 then W2. Low-fire prove is not high-fire prove.
Transformer + fuse
Same 24V transformer as single-stage. Fuse still kills the whole strip.
- L1 / N120VLine
- XFMR24V to R24V
- FUSEOn the IFC24V
24V safety chain
Door, limit, rollout. A limit trip is not an E9 / 32 pressure-switch story.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Two-speed inducer + two pressure switches
W1 = inducer low + LPS. W2 = inducer high + HPS. Separate hoses. Do not tee.
- IND LO120V low-speed inducerLine
- IND HI120V high-speed inducerLine
- LPSLow-fire prove24V
- HPSHigh-fire prove24V
- HOSESOne hose per switch. Never tee LPS and HPS24V
HSI + two-stage valve
Igniter 120V. Low solenoid on W1. Second solenoid on W2 after HPS closes.
- HSI120V igniterLine
- MV / LO24V low-fire solenoid24V
- HV / HI24V high-fire solenoid24V
- FLAMEµA DC on the rod24V
9-speed tap ECM
F01–F09 on the harness. Heat tap and cool tap are separate. Not a 14-pin serial motor and not a run cap.
- F01–F09Speed taps on the IFC / harness24V
- HEATDefault often F02 — F01 is an E3 generator on many 9-speed doors24V
- COOL / Y / GCool tap. Wrong tap freezes the coil and looks like LPS outdoors.24V
Landing
- LineW1IFCinducer LOWLPS
120V inducer, 24V prove
- LineIFCHSIvalve LOW
120V igniter, 24V low solenoid
- 24VW2inducer HIGHHPSvalve HIGH
Missing W2 = stuck on low
- 24VFlame rodIFC
µA DC
- LineIFCheat blower
After flame. Motor class on this plate.
Prove it
- W1 then W2 at the IFC under a 2-heat call.
- If it never stages, W2 is missing at the board — not a bad gas valve until that is proven.
Do not
- Do not convert this to Infinity by landing W on a random terminal.
- Do not apply AMVC / ARVT ComfortBridge menus or a memory card.
926T / 59TP6 / AR9T96 / GR9T96 / S9V2 / EL296E class. Same landing on 80% metal-vent cousins — the vent is not the wire.
Sequence
- 1
W1
IFC proves limits/rollout closed, starts inducer on low speed.
- 2
Prove low PS
Low-fire pressure switch must close. If it is already closed with inducer off → E1. If it never closes → E2.
- 3
HSI warm
Silicon nitride igniter ~17–27 s (OEM). Open igniter → En / E7.
- 4
Low-fire valve
First-stage solenoid opens. Flame must prove at the rod. Failures stack toward E0 lockout.
- 5
Blower delay
Heat-on delay, then ECM on the selected heat tap (not a communicating CFM request).
- 6
W2 / high fire
Inducer goes high. High-fire PS must close (E9 if open, E8 if it was already closed). Second-stage solenoid opens.
- 7
Satisfied
Valve off, inducer post-purge, blower heat-off delay. Unexpected flame after valve-off → E4.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
E0
Retry / recycle lockout
Too many failed ignition attempts or flame losses on this call.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Goodman GR9T80 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Watch one full try: inducer, HSI glow, valve click, flame, µA.
Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Gas supply and manifold (low then high).
Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
3 Prove it is not a switch opening
Watch the live Goodman GR9T80 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Ground and flame-rod cleanliness.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E1
Low-fire PS stuck closed
Low-stage pressure switch is made with the inducer off.
1 Unplug the switch with the inducer off
On Goodman GR9T80 this code is the switch made when the inducer is not running. Unplug that switch only. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
2 Water in the hose vs a welded switch
Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Expect: Hose empty. Switch opens with no draft.
3 IFC input last
If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Goodman GR9T80 IFC input is shorted. Do not keep swapping switches. Unplug the LPS. If code changes, switch is welded or hose is holding residual draft.
Expect: Known-good open switch + open harness = code gone. If not, IFC.
E2
Low-fire PS open
Inducer is on low and the low-fire switch will not close.
1 Prove inducer and the live code
Do not pull power — that clears the Goodman GR9T80 active code. Write E2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Inducer spinning? 120 VAC at inducer on a W1 call.
Expect: LPS / HPS: Both NO. Closed only when that inducer speed is making the collector setpoint. Two hoses — never tee.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E3
Open high limit
Primary limit opened. Airflow or overfire — not a charge problem.
1 Airflow before you touch the limit
On Goodman GR9T80 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, blower wheel, A-coil, heat-speed tap (9-speed: wrong tap is the #1 callback).
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the Goodman GR9T80 blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Static vs blower chart for this cabinet size.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Manifold pressure on low and high vs rating plate.
Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
E4
Flame when valve should be off
Rod sees flame with both solenoids de-energized.
1 Shut the gas cock first
On Goodman GR9T80 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Rod shorted to ground or IFC flame circuit.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
E5
Open fuse
3 A (typical) automotive fuse on the IFC is open.
1 Find the 24 V short before you replace the fuse
On Goodman GR9T80 an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. 24 V short on W, Y, G, humidifier, or EAC.
Expect: Fuse out. 24 V transformer still good. Harness isolated.
2 Replace the fuse with the harness off
New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC). Unplug tstat harness and replace fuse. If it blows again the short is on the board or gas valve harness.
Expect: Fuse holds with harness off. Dies when the shorted lead lands.
3 If it blows with the harness off
Short is on the Goodman GR9T80 IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.
Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.
E6
Low flame signal
Flame is present but µA is below the IFC threshold.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Goodman GR9T80 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod with a non-scratch pad — not sandpaper.
Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Chassis ground to burner box and IFC.
Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
3 Prove it is not a switch opening
Watch the live Goodman GR9T80 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Manifold pressure / orifice / LP conversion.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E7
Igniter relay fault
IFC did not see the igniter circuit behave as commanded.
1 Ohms at the igniter, then at the IFC
On Goodman GR9T80 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Igniter ohms cold (OEM — typically 30–115 Ω class, confirm sticker).
Expect: HSI: Nitride, 120 VAC during warm-up. Cold ohms per sticker — do not use a 80% Norton chart.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. 120 VAC to igniter during warm-up.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter. Cracked nitride element.
Expect: One clean light after a known-good igniter and a proven ground.
E8
High-fire PS stuck closed
High-stage pressure switch is made with the inducer not on high.
1 Prove the switch is made with inducer not on high
On Goodman GR9T80 this code means the high-fire switch is closed when it should be open. Do not treat it as the low-fire stuck-closed code. Write the live display, then unplug the high-fire switch only.
Expect: Code should change when the high-fire harness is open.
If fail: IFC input shorted or you unplugged the wrong switch.
2 Hose water and a welded switch
Water in the high-fire hose holds residual draft and fakes a closed switch. Route downhill to the collector. Ohm the switch with the hose off — a welded high-fire switch stays closed. This is Category I metal vent. There is no 96% collector or PVC trap to prime. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Expect: Hose dry. Switch opens with no draft.
3 Confirm the IFC is not commanding high
W2 shorted to W1, a communicating stat stuck on high, or an IFC that never drops inducer speed will keep this code alive. Measure W2 at the board and watch inducer speed after you open the high-fire harness. This is the second switch — do not confuse with E1.
Expect: Inducer on low (or off) with W2 open. High-fire switch ohms open.
E9
High-fire PS open
Inducer on high, high-fire switch never closes. Classic ‘runs on low, will not go high.’
1 Prove the high-fire call
Write the live Goodman GR9T80 code before you pull power. Confirm this IFC is actually commanded to high — W2 at the board, or the staging timer has expired. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: R to W2 ~24 VAC (conventional) or a high-stage request on a communicating stat.
If fail: No high request → thermostat / staging / menu. Not a high-fire pressure switch.
If pass: Go to step 2. Do not jump the high-fire switch to ‘see if it runs.’
2 Prove the inducer actually went high
Listen and amp the inducer on low vs high. No speed-up → IFC high output or inducer winding. Speed-up and this code still live → high-fire PS path (hose, switch, vent). Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Expect: LPS / HPS: Both NO. Closed only when that inducer speed is making the collector setpoint. Two hoses — never tee.
If fail: Measure 120 VAC on the high-speed inducer lead during the high call. 0 V = IFC. Voltage + dead motor = inducer.
3 Isolate the HIGH hose and switch
High-fire hose on the high tap only — a tee with the low switch is the common first-install miss on this dual-switch plate. Blow the hose, confirm it is dry and downhill to the collector. Ohm the high-fire switch: it is NO and must close only on high draft. Inducer actually changes speed on W2? Listen / amp it.
Expect: LPS / HPS: Both NO. Closed only when that inducer speed is making the collector setpoint. Two hoses — never tee.
If fail: Welded open, cracked hose, or water in the line. Replace the failed part — do not leave a jumper.
If pass: Switch and hose good → step 4 (vent / condensate / IFC).
4 Vent, condensate, and the IFC input
High fire needs more draft than a low-fire code ever saw. Check PVC size on this cabinet, shared chase, wind, ice, bird screen, and condensate backing into the collector only on high. If the switch closes on known draft and the code stays, the Goodman GR9T80 IFC input is the last call.
Expect: Clear vent, dry collector, known-good switch, then IFC.
EA
Line polarity / ground
L1/N reversed or chassis ground missing. HSI and flame sense both suffer.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Goodman GR9T80 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Hot and neutral at the IFC, not just the disconnect.
Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Burner box to IFC ground screw.
Expect: Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
3 Prove it is not a switch opening
Watch the live Goodman GR9T80 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Twinned jobs — follow the twinning kit, then look at EEJ.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
Eb / Ec
Gas valve circuit
Internal (Eb) or external (Ec) gas-valve electrical fault.
1 Coil ohms and 24 VAC during trial only
On Goodman GR9T80 measure each solenoid. 24 VAC should appear only during trial / the commanded stage. Valve coil ohms, 24 VAC at the harness during trial.
Expect: Coil ohms per the valve sticker. 24 VAC only when the IFC commands that stage.
2 Do not energize a leaking valve
If the unexpected-flame code is also in history, shut the cock and replace the valve. Applying 24 V as a ‘test’ and walking away is a gas leak. Do not apply 24 V to a leaking valve as a ‘test’ and walk away.
Expect: No flame with the cock shut and solenoids de-energized.
3 IFC relay vs the valve
Voltage at the harness and a dead coil = valve. No voltage during a known trial = IFC relay or a lockout that never opened the valve (look at the live code).
Expect: Known trial + 24 VAC + good coil = flame. Otherwise IFC.
Ed
Open rollout
Manual-reset rollout opened. Treat as flame outside the exchanger until proven otherwise. Door chart may render this as a distinctive 7-seg character — confirm on the unit sticker.
1 Treat this as flame outside the exchanger
Do not reset the Goodman GR9T80 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Primary exchanger cracks, burner alignment, crossover. Blocked secondary / condensate / flue.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Goodman GR9T80 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave. Reset only after the cause is fixed. Recurring rollout is a CO / fire call.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
En
Igniter open
Igniter circuit measures open.
1 Ohms at the igniter, then at the IFC
On Goodman GR9T80 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms at the igniter plug, then at the IFC.
Expect: HSI: Nitride, 120 VAC during warm-up. Cold ohms per sticker — do not use a 80% Norton chart.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Harness rub-through on the collector.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
EEH
Grounding error
IFC failed its ground check (sister to EA).
1 Hot and neutral at the IFC, not the disconnect
On Goodman GR9T80 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Green ground to cabinet and IFC.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Painted screw, missing star washer.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
EEJ
Twin error
Twinning miswire or twin terminal active on a standalone unit.
1 Is this cabinet actually twinned?
On a standalone Goodman GR9T80, nothing belongs on the TWIN terminal. A leftover jumper throws this. If not twinned, nothing should be on the TWIN terminal.
Expect: TWIN empty on a single cabinet.
2 Twinned pair must be the same IFC family
Twinned units must be the same family and IFC revision. Mixing this plate with a communicating sister SKU will not twin. Twinned pair must be same family / same IFC revision.
Expect: Same model family, same IFC, kit installed per the twinning sheet.
3 Phasing and 24 V
Twinning errors that survive a correct kit are 24 V phasing or a broken twin lead. Measure both cabinets before you change an IFC.
Expect: In-phase 24 V. Continuous twin lead.
LE1 / UE2
Circulator current
ECM current too low (LE1) or unexpected (UE2).
1 Is the wheel free?
Spin the Goodman GR9T80 blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Expect: ECM taps: Factory defaults from SS p.8: fan F03, Y1/Y F04, Y2 F05, heat low F01, heat high F02. Rise is cabinet-specific (15–45 on 0303AN through 35–65 on 80–120 kBtu).
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call. Harness seated at motor and IFC. 9-speed ECM is tap-driven — a half-seated plug throws these.
Expect: Static on the blower chart. Matching motor / shared-data card.
FE3 / LE4 / SE5 / rE6
A2L mitigation
Leak / comm / relay alarm from the A2L board when paired with R-32 or R-454B outdoor.
1 Confirm this pair is actually A2L
On Goodman GR9T80 FE3 / LE4 / SE5 / rE6-class codes are only valid when this furnace is tied to an R-32 or R-454B outdoor. On R-410A this is a miswired mitigation harness — not a leaking indoor coil.
Expect: Outdoor refrigerant from the outdoor nameplate, not from memory.
If fail: Remove / correct the mitigation harness. Do not condemn the IFC.
2 Sensor location and the mitigation blower
If it is a real A2L pair, follow the OEM mitigation sequence: sensor location, ventilation blower, relay. This is Category I metal vent. There is no 96% collector or PVC trap to prime. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Expect: Sensor seated where the I/O shows. Mitigation blower runs on a test.
3 Do not bypass mitigation
Never jump an A2L alarm to get heat. Find the leak or the failed sensor. Recurring mitigation with a clean sensor is a refrigerant leak until proven otherwise.
Expect: Alarm clears only after the leak/sensor is fixed.
Workflows
Runs on low, no high (E9)
Comfort complaint or E9.
1 Prove the call and the live code
W2 actually closed? Inducer actually speed up?
Expect: Write whatever Single 7-seg two-stage IFC · 80% door is showing. Standby hold >2 s plays last faults. Power cycle clears the live code.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
High-fire draft switch hose on the high tap only. Do not tee.
Expect: Prove low PS: Low-fire pressure switch must close. If it is already closed with inducer off → E1. If it never closes → E2.
3 Confirm with a number, then the next part
Chimney / B-vent / common vent that passed on low will fail on high. 9-speed heat tap is F01/F02 class — wrong tap is E3, not E9.
Expect: Flame rod: Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal. · Manifold low / high: Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Flame rod
Typically ≥ 1.0 µA DC on this IFC family — confirm door chart. Rising while running is the goal.
Manifold low / high
Natural ~1.6–1.9 / 3.2–3.5 in. w.c. class — rating plate wins. Clock input if in doubt.
LPS / HPS
Both NO. Closed only when that inducer speed is making the collector setpoint. Two hoses — never tee.
HSI
Nitride, 120 VAC during warm-up. Cold ohms per sticker — do not use a 80% Norton chart.
ECM taps
Factory defaults from SS p.8: fan F03, Y1/Y F04, Y2 F05, heat low F01, heat high F02. Rise is cabinet-specific (15–45 on 0303AN through 35–65 on 80–120 kBtu).
Gotchas
- GR9T96 techs dump a trap. There is none. E2 is a chimney.
- GRVT80 is the ComfortBridge 80% — triple display + memory card. Wrong chart if you see idle/Ht1.
Related plates
Install this plate
Install Goodman GR9T80 as Two-stage · 9-speed ECM · 80% Cat I.
Two-stage · 9-speed ECM · 80% Cat I
This plate — not the sister SKU
- Not GR9T96 (96% PVC, dual PS on a collector). Not GRVT80 (ComfortBridge serial VS). Not GR9S80 (single-stage, one PS). Not AR9S80 (Amana single-stage 80% 9-speed).
- GR9T96 techs dump a trap. There is none. E2 is a chimney.
- GRVT80 is the ComfortBridge 80% — triple display + memory card. Wrong chart if you see idle/Ht1.
IFC on this door
- E1/E2 low draft. E8/E9 high draft. Same tokens as GR9T96 — chimney physics.
- No E8/E9 on GR9S80 (one switch). No CoolCloud on this board.
- A2L pair codes only if this 80% is tied to an R-32 outdoor mitigation harness.
Hardware
- AFUE: 80% two-stage · Category I 4" metal vent
- Staging: Two-stage valve · two-speed inducer · dual draft switches
- Blower: 9-speed ECM taps F01–F09 — not serial VS
- Tstat: Conventional 24V W1/W2. No ComfortBridge pair.
- Sister SKU: GD9T80 downflow · Amana AR9T80
First fire
- 1W2 actually closed? Inducer actually speed up?
- 2High-fire draft switch hose on the high tap only. Do not tee.
- 3Chimney / B-vent / common vent that passed on low will fail on high.
- 49-speed heat tap is F01/F02 class — wrong tap is E3, not E9.
Do not on Goodman GR9T80
- Not GR9T96 (96% PVC, dual PS on a collector). Not GRVT80 (ComfortBridge serial VS). Not GR9S80 (single-stage, one PS). Not AR9S80 (Amana single-stage 80% 9-speed).
- GR9T96 techs dump a trap. There is none. E2 is a chimney.
- GRVT80 is the ComfortBridge 80% — triple display + memory card. Wrong chart if you see idle/Ht1.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- Goodman literature libraryLiterature searchSearch the exact plate (GR9T960804CN, GR9S960603BN). Full I/O PDFs are often dealer-gated.Open manufacturer PDF
- Goodman literature libraryLiterature searchSearch Goodman GR9T80 on the maker’s literature page.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
PWCFURNUQNTE
warranty sheetGoodman gas furnace limited warranty — unit-replacement certificate
Registered furnace — parts / heat exchanger / unit replacement terms · Limited warranty certificate
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal