Daikin
EA
LockoutReversed polarity / ground
115 V L1/N reversed, 24 V transformer reversed, or poor chassis ground.
Walk EA in Diagnose
4 plates — walk the one on the cabinet
First check
1 Hot and neutral at the IFC, not the disconnect
On Daikin DM80VC polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot/neutral at the IFC, not just the disconnect.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
The rest of the walkthrough is Diagnose.
On the plates
- Hot/neutral at the IFC, not just the disconnect.
- Burner box ground screw.
- Hot/neutral at the IFC.
Plates that use EA
Same number, other makers
EA on Daikin is not the same code on these plates.