E6
ProtectLow flame-sense µA
Flame is present but the micro-amp signal is below the IFC threshold.
Walk E6 in Diagnose
9 plates — walk the one on the cabinet
First check
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Amana AMVC96 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod with a non-scratch pad — not sandpaper.
Expect: Flame rod: µA per this IFC sticker, not the AR9T96 card. Rising while running is the goal.
The rest of the walkthrough is Diagnose.
On the plates
- Clean rod with a non-scratch pad — not sandpaper.
- Chassis ground to burner box and IFC.
- Manifold pressure / orifice / LP conversion.
- Manifold pressure / orifice / LP conversion (this plate uses LPM-33, not LPM-34).
- Clean rod with a non-scratch pad.
- Chassis ground, manifold, LP conversion (this plate uses LPM-31 with an LP switch — not LPM-33).
- Manifold / orifice / LP conversion (this plate is LPM-34 on every SKU).
- Clean rod, chassis ground.