Goodman
E6
ProtectLow flame signal
Flame is present but the micro-amp signal is below the IFC threshold.
Walk E6 in Diagnose
9 plates — walk the one on the cabinet
First check
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Goodman GMEC96 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod, chassis ground, manifold / LP conversion.
Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.
The rest of the walkthrough is Diagnose.
On the plates
- Clean rod with a non-scratch pad — not sandpaper.
- Chassis ground to burner box and IFC.
- Manifold pressure / orifice / LP conversion.
- Clean rod with a non-scratch pad.
- Manifold / orifice / LP conversion.
- Clean rod, chassis ground, manifold / LP conversion.
- Clean rod, burner-box ground. µA should rise as rate climbs; flat µA at every percent is rod/ground, not the valve.
- Light-off rate too lean (valve / orifice / LP). Do not crank a two-stage manifold chart onto this modulator.