York
Rapid amber
ProtectFlame sense < 1.5 µA
Weak rod current. Normal ~3.7 µA; lockout < 0.1 µA.
Walk Rapid amber in Diagnose
5 plates — walk the one on the cabinet
First check
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on York TM8T during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Rod, ground, manifold.
Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
The rest of the walkthrough is Diagnose.
On the plates
- Read µA at the IFC flame-sense test pad during a run.
- Clean the rod with a non-scratch pad — not sandpaper.
- Chassis ground to burner box and IFC. Reversed polarity will also show as 9-red.
- Manifold / orifice / LP conversion if the flame is lazy.
- Clean rod, ground, manifold. Read µA at the test pad.
- Rod, ground, manifold.