TM9X
JCI 96% · single-stage · multi-speed / CT
York/Coleman/Luxaire 96% single-stage (TM9X / TM9E / TG9S). Same JCI LED flash family as TM9T — one fire rate, one PS. Not TM9V VS two-stage.
Not TM9V two-stage VS. Not TM9T two-stage multi-speed. Not TM8X 80%.
AFUE
96% single-stage condensing
Display
JCI LED 1–10 flash — confirm THIS door
This board
JCI / Coleman-York IFC · green / amber / red LED
- Same LED language as TM9V. Slow green idle, slow amber heat call, red counts 1–12, rapid red twinning, rapid amber weak flame, steady red control failure.
- 1/4 s on, 1/4 s off, 2 s pause between counts. Rapid colors are not counts.
- Two-stage 96%: two pressure switches. 3-red is still trap/PVC first.
- The difference is the blower — taps, not a VS CFM menu. Read the tap chart on THIS TM9T door.
Active code repeats until the fault clears or 24 V is removed. Write color + count before you cycle power.
Universal swap
Single-stage JCI 96%. WR single-stage kits only if this cabinet is actually that older silk.
Silk: 50A55 · 50A65
White-Rodgers
—ICM
—Honeywell
—- 50A55-843 assumed because York. TM9T two-stage board.
After you pull the dead card
- 1OEM York/JCI single-stage 96% IFC.
Field wiring
Written landings for York TM9X. Not a factory schematic.
Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC → transformer → R120V in, 24V out
- 2Call. Stat W → IFC W~24 VAC
- 3Draft. IFC → inducer → PS close120V motor, 24V prove
- 4Ignite. IFC → HSI120 VAC
- 5Gas. IFC → valve~24 VAC
- 6Flame. Rod → IFCµA DC
- 7Blow. IFC → heat speedAfter flame prove
This indoor
JCI 96% single-stage. Not TM9T two-stage.
24V single-stage heat
Door card is one-stage. Twin terminal empty unless the job is actually twinned.
Wall thermostat
Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.
- R24V hot from the IFC24V
- CCommon24V
- WHeat24V
- YCool — also starts the outdoor24V
- GFan24V
Furnace IFC
Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.
- RHot to the stat24V
- CCommon — must reach the outdoor24V
- WHeat call24V
- YCool in / cool out24V
- GBlower24V
- TWINEmpty unless twinned24V
Landing
- 24VIFC Rstat R
~24 VAC hot
- 24VIFC Cstat Coutdoor C
Common
- 24VStat WIFC W
Heat. Stays in this cabinet.
- 24VStat YIFC Youtdoor Y
Cool / contactor
- 24VStat GIFC G
Fan. Does not go outdoors.
IFC harness — single-stage heat
After W arrives. This is the gas train, not the thermostat strip.
Transformer + fuse
120V primary. 24V secondary. Dark stat = fuse / door / transformer first.
- L1 / N120V to the IFCLine
- XFMR24V to R24V
- FUSEOn the IFC24V
24V safety chain
Door, limit, rollout in series. Open anywhere kills heat.
- DOORInterlock24V
- LIMITMain limit — rise / no airflow24V
- ROLLOUTManual reset. Do not jumper and leave24V
Inducer + one pressure switch
W → inducer 120V → PS closes → IFC continues. One hose, one switch.
- IND120V from the IFC to the inducerLine
- PS24V prove back to the IFC24V
- HOSESingle hose. Do not add a second because two-stage boards have two.24V
HSI + single valve
Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.
- HSI120V hot-surface igniter — not 24VLine
- VALVE24V to the single solenoid24V
- FLAMEµA DC on the rod. Not a 24V circuit24V
PSC blower + run cap
Heat / cool / park taps on the motor. The cap is on this blower — not the outdoor dual can.
- HEATHeat speed tap24V
- COOLCool speed tap24V
- PARKUnused leads parked24V
- CAPRun capacitor on the blowerCap
Landing
- LineL1IFCinducer
120 VAC after W
- 24VIFCPSIFC
~24 VAC prove. Open PS = no ignition.
- LineIFCHSI
120 VAC during trial
- 24VIFCgas valve
~24 VAC after flame prove starts
- 24VFlame rodIFC
µA DC. Not 24V.
- LineIFCblower
120V tap + cap
Prove it
- 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
- W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.
Do not
- Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
- Do not hunt W2 / E8 / high-fire on a one-stage door.
- TWIN must be empty on a standalone.
9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.
Sequence
- 1
W1
Inducer low → low-fire PS must close (3-red / 2-red) → HSI → low-fire valve → flame → blower on the selected HEAT tap.
- 2
W2
Inducer high → high-fire PS → second solenoid. Blower may stay on the same heat tap — this is not a VS ramp.
- 3
Limit path
Wrong heat tap is the 4-red generator on TM9T. There is no CFM menu to ‘turn up’ — move the tap, then check static and rise.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
Slow green
Normal, no heat call
IFC powered, idle.
1 Confirm this is not a fault
On the York TM9X this readout (Slow green) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the York TM9X IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: No W at the IFC if the house is cold.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch JCI / Coleman-York IFC · green / amber / red LED through one cycle and write the first real fault that replaces this status word.
Expect: W1: Inducer low → low-fire PS must close (3-red / 2-red) → HSI → low-fire valve → flame → blower on the selected HEAT tap.
Slow amber
Normal, heat call
IFC sees W and is sequencing or running heat.
1 Confirm this is not a fault
On the York TM9X this readout (Slow amber) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the York TM9X IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: Stay and watch if burners are out.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch JCI / Coleman-York IFC · green / amber / red LED through one cycle and write the first real fault that replaces this status word.
Expect: W1: Inducer low → low-fire PS must close (3-red / 2-red) → HSI → low-fire valve → flame → blower on the selected HEAT tap.
Rapid red
Twinning / 24V phasing
TWIN miswire or 24 V phasing.
1 Is this cabinet actually twinned?
On a standalone York TM9X, nothing belongs on the TWIN terminal. A leftover jumper throws this. Nothing on TWIN unless the job is actually twinned.
Expect: TWIN empty on a single cabinet.
2 Twinned pair must be the same IFC family
Twinned units must be the same family and IFC revision. Mixing this plate with a communicating sister SKU will not twin.
Expect: Same model family, same IFC, kit installed per the twinning sheet.
3 Phasing and 24 V
Twinning errors that survive a correct kit are 24 V phasing or a broken twin lead. Measure both cabinets before you change an IFC.
Expect: In-phase 24 V. Continuous twin lead.
Rapid amber
Flame sense < 1.5 µA
Weak rod current. Normal ~3.7 µA; lockout < 0.1 µA.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on York TM9X during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod, ground, manifold. Read µA at the test pad.
Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live York TM9X display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
4 amber
Y without G
Cool call missing G.
1 Is the wheel free?
Spin the York TM9X blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Stat wiring. Not a PS code.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data.
Expect: Heat tap: Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
1 red
Flame sensed, no call for heat
Flame with valve de-energized.
1 Shut the gas cock first
On York TM9X the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Leaking valve is a hazard.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
2 red
Pressure switch stuck closed
PS made with inducer off.
1 Unplug the switch with the inducer off
On York TM9X this code is the switch made when the inducer is not running. Unplug that switch only. Unplug the switch. Water in the hose. Which of the two switches?
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
2 Water in the hose vs a welded switch
Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off.
Expect: Hose empty. Switch opens with no draft.
3 IFC input last
If the switch ohms open, the hose is dry, and the code does not change with the harness off, the York TM9X IFC input is shorted. Do not keep swapping switches.
Expect: Known-good open switch + open harness = code gone. If not, IFC.
3 red
PS failed to close after inducer
96% trap / collector / PVC / inducer — same draft physics as TM9V.
1 Prove inducer and the live code
Do not pull power — that clears the York TM9X active code. Write 3 red. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Trap, collector, hose on the correct tap, PVC ice/wind, inducer 120 VAC.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Two PS. High-fire-only 3-red is the high hose / vent capacity.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: LPS / HPS: Two NO switches. Never teed.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
4 red
Limit open
Airflow or overfire. On TM9T this is almost always the heat tap, not a VS menu.
1 Airflow before you touch the limit
On York TM9X a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Read the heat tap on the motor / IFC harness and match it to the TM9T tap chart and the rise range on the plate.
Expect: Heat tap: Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu.
2 Measure static and temperature rise
Total external static vs the York TM9X blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Do not open a TM9V CFM menu — there isn’t one.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Filter, wheel, coil, return, TES. A new media cabinet on a low heat tap will 4-red all winter.
Expect: Manifold on plate. Limit closed when cool.
5 red
Rollout open
Manual-reset rollout. Flame containment.
1 Treat this as flame outside the exchanger
Do not reset the York TM9X rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Exchanger, burners, flue, secondary. Reset only after the cause.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on York TM9X is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
6 red
PS opened 4 times this call
Intermittent draft drop. One-hour lockout.
1 Prove inducer and the live code
Do not pull power — that clears the York TM9X active code. Write 6 red. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Trap that refills, wind, hose, high-fire vent capacity.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: LPS / HPS: Two NO switches. Never teed.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
7 red
Flame not established after 3 tries
Ignition retries exceeded.
1 Watch one full try — do not reset
Write the York TM9X code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI glow and 120 VAC, gas, rod µA, ground.
Expect: W1 → W2 → Limit path
2 Gas and the valve
Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence.
Expect: Inlet and manifold on the plate. 24 VAC only during trial.
3 Flame prove, then the lockout timer
Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.
Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
8 red
Flame lost 5 times
Flame dropped after prove.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on York TM9X during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. µA, gas sag, draft collapse when the blower starts on that heat tap.
Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live York TM9X display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
9 red
Reversed polarity / grounding
L1/N or chassis ground.
1 Hot and neutral at the IFC, not the disconnect
On York TM9X polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot/neutral at the IFC, burner ground.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
10 red
Flame sensed, no call (some boards)
Same as 1-red on later revisions.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on York TM9X during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Door card on THIS IFC. Valve leak.
Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live York TM9X display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
11 red
Limit open >5 min · hard lockout
Blower never moved enough air to reclose the limit.
1 Airflow before you touch the limit
On York TM9X a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Is the tap motor actually running? Capacitor / ECM module / wheel.
Expect: Heat tap: Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu.
2 Measure static and temperature rise
Total external static vs the York TM9X blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Heat tap too low for this cabinet + coil.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Cycle 24 VAC only after airflow is real.
Expect: Manifold on plate. Limit closed when cool.
12 red
Open igniter circuit
HSI path open.
1 Ohms at the igniter, then at the IFC
On York TM9X measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms at the plug and at the IFC. Cracked nitride.
Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
Steady red
Control failure
Internal IFC fault.
1 Write the live code and watch one cycle
On York TM9X read JCI / Coleman-York IFC · green / amber / red LED before you pull power. Write Steady red exactly. Watch one full sequence and note which step dies. Power and fuse first, then replace the control.
Expect: W1: Inducer low → low-fire PS must close (3-red / 2-red) → HSI → low-fire valve → flame → blower on the selected HEAT tap.
2 Prove the circuit this code names
Use the York TM9X door card and the test points on this plate. Isolate the named switch, sensor, or output with a meter — do not swap the IFC first.
Expect: A measured open, short, or out-of-range reading — not a guess.
3 Confirm with a number, then the next part
If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.
Expect: Heat tap: Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu.
Workflows
3-red on TM9X
York 96% single-stage.
1 Prove the call and the live code
One PS. Trap / PVC. Same flash chart idea as TM9T, no high-fire.
Expect: Write whatever JCI / Coleman-York IFC · green / amber / red LED is showing. Active code repeats until the fault clears or 24 V is removed. Write color + count before you cycle power.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
TM9V is VS two-stage — different motor, still this LED language on many cabinets.
Expect: W2: Inducer high → high-fire PS → second solenoid. Blower may stay on the same heat tap — this is not a VS ramp.
3 Confirm with a number, then the next part
TM9V is VS two-stage — different motor, still this LED language on many cabinets.
Expect: Heat tap: Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu. · Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Heat tap
Matches the TM9T chart and the rating-plate rise (typically 35–65°F). Not a VS menu.
Flame sense
Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
LPS / HPS
Two NO switches. Never teed.
Gotchas
- TM9T is two-stage multi-speed. Count solenoids.
Related plates
Install this plate
Install York TM9X as JCI 96% · single-stage · multi-speed / CT.
JCI 96% · single-stage · multi-speed / CT
This plate — not the sister SKU
- Not TM9V two-stage VS. Not TM9T two-stage multi-speed. Not TM8X 80%.
- TM9T is two-stage multi-speed. Count solenoids.
IFC on this door
- Same LED language as TM9V. Slow green idle, slow amber heat call, red counts 1–12, rapid red twinning, rapid amber weak flame, steady red control failure.
- 1/4 s on, 1/4 s off, 2 s pause between counts. Rapid colors are not counts.
- Two-stage 96%: two pressure switches. 3-red is still trap/PVC first.
- The difference is the blower — taps, not a VS CFM menu. Read the tap chart on THIS TM9T door.
Hardware
- AFUE: 96% single-stage condensing
- Display: JCI LED 1–10 flash — confirm THIS door
First fire
- 1One PS. Trap / PVC. Same flash chart idea as TM9T, no high-fire.
- 2TM9V is VS two-stage — different motor, still this LED language on many cabinets.
Do not on York TM9X
- Not TM9V two-stage VS. Not TM9T two-stage multi-speed. Not TM8X 80%.
- TM9T is two-stage multi-speed. Count solenoids.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- York residential gas furnacesLiterature searchTM9 / TM8 family listing (Coleman / Luxaire share the JCI IFC). UPGNet holds the I/O.Open manufacturer PDF
- York / Bosch Home ComfortLiterature searchSearch York TM9X on the maker’s literature page.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Residential limited warranty
dealerYork furnace warranty
Registered TM8 / TM9 furnace warranty · Dealer claims portal
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal