TM9V
York/JCI 96% · two-stage · variable-speed
York/Coleman/Luxaire TM9V is a two-stage 96% condensing furnace with a variable-speed blower. The IFC uses a green/amber/red LED behind the blower-door sight glass — not Carrier two-digit 31 and not Amana E2. V in the model is the VS CFM menu, not a tap bank.
Not TM9T (same 96% two-stage flash language, multi-speed taps). Not TM8V (80% metal vent — 3-red is draft, not a PVC trap). Not Carrier 59TP6 (31/33/34). Not Amana AR9T96 (E0–E9).
AFUE
Two-stage 96% condensing · PVC 2-pipe
Staging
Two-stage gas valve · two-speed inducer · two pressure switches
Blower
Variable-speed ECM · CFM set in the IFC menu, not heat/cool taps
Ignition
120 VAC hot-surface igniter · flame rod with test pad
Control
JCI / Coleman-York multi-color LED IFC · conventional 24V tstat
Badge
Coleman TM9V and Luxaire TM9V use this same IFC
Example SKU
TM9V080B12MP11 — read the full plate, not just TM9
This board
JCI / Coleman-York IFC · green / amber / red LED
- LED is behind the clear viewport in the blower door. Do not pull power to read it.
- Slow green = idle, no heat call. Slow amber = normal heat call. These are status, not faults.
- Red counts are 1/4 s on, 1/4 s off, then a 2 s pause. Six red, pause, six red = code 6. Rapid red is twinning / 24V phasing, not a count. Rapid amber is weak flame sense, not a count.
- Two-stage 96%: two pressure switches. 2-red / 3-red / 6-red are the active-stage PS path — confirm which inducer speed is running.
- Coleman and Luxaire door cards match this TM9V chart. The badge is cosmetic.
Active code repeats until the fault clears or 24 V is removed. Write color + count (or rapid/steady) before you cycle power. 6-red and 7-red lock out ~1 hour then retry.
Universal swap
Two-stage VS. 50M56U / 50A55 / S9200U are single-stage PSC — they do not belong on this blower.
Silk: 50A55 · 50A65 · 21D64-2 · 031-00662 · 031-01140
White-Rodgers
—ICM
—Honeywell
- S9200U1000
S9200U lists older York 031-00662 / 031-01140 / 031-01234 and 50A55-843. Current TM9V is two-stage VS — only if this cabinet is actually that older single-stage IFC.
- 50A55-843 / 50M56U-843 / 50M56X-843.
- ICM2813 SureLight (Lennox). TM9T multi-speed board assumed without reading silk.
After you pull the dead card
- 1OEM York/JCI two-stage VS IFC. A York 50A55 cousin is a different, older single-stage furnace.
Field wiring
Written landings for York TM9V. Not a factory schematic.
Two-stage conventional furnace. W1 low fire, W2 high fire. Outdoor staging is Y or Y1/Y2 — separate from the gas valve.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC → R120V / 24V
- 2Low. W1 → inducer LOW → LPS → HSI → valve LOWFirst fire
- 3High. W2 → inducer HIGH → HPS → valve HIGHSecond solenoid
- 4Flame. Rod → IFCµA DC both stages
- 5Blow. IFC → heat blowerAfter flame
This indoor
JCI 96% VS two-stage.
24V two-stage heat
Door has W1 and W2. Not Infinity. Not ComfortBridge.
Two-stage thermostat
A single-W stat never proves high fire. That is not a weak inducer.
- R24V hot24V
- CCommon24V
- W1Low-fire heat24V
- W2High-fire heat24V
- Y / Y1Cool24V
- Y2Outdoor high if the condenser is two-stage24V
- GFan24V
Two-stage IFC
W2 is high fire. Do not tee the pressure-switch hoses because there are two stages.
- RHot24V
- CCommon to outdoor24V
- W1Low fire24V
- W2High fire24V
- YCool out24V
- GBlower / cool tap24V
Landing
- 24VStat W1IFC W1
Low fire
- 24VStat W2IFC W2
High fire. Missing W2 = stuck on low.
- 24VStat YIFC Youtdoor Y
Cool
- 24VC throughout
Common
IFC harness — two-stage heat
W1 then W2. Low-fire prove is not high-fire prove.
Transformer + fuse
Same 24V transformer as single-stage. Fuse still kills the whole strip.
- L1 / N120VLine
- XFMR24V to R24V
- FUSEOn the IFC24V
24V safety chain
Door, limit, rollout. A limit trip is not an E9 / 32 pressure-switch story.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Two-speed inducer + two pressure switches
W1 = inducer low + LPS. W2 = inducer high + HPS. Separate hoses. Do not tee.
- IND LO120V low-speed inducerLine
- IND HI120V high-speed inducerLine
- LPSLow-fire prove24V
- HPSHigh-fire prove24V
- HOSESOne hose per switch. Never tee LPS and HPS24V
HSI + two-stage valve
Igniter 120V. Low solenoid on W1. Second solenoid on W2 after HPS closes.
- HSI120V igniterLine
- MV / LO24V low-fire solenoid24V
- HV / HI24V high-fire solenoid24V
- FLAMEµA DC on the rod24V
Blower — read the motor
PSC has a cap. 9-speed has F-taps. Serial VS has a harness and no cap. Do not mix those playbooks.
- PSCCap + 3–5 speed leads24V
- 9-SPDF01–F09 taps24V
- VSFat serial plug, no cap24V
Landing
- LineW1IFCinducer LOWLPS
120V inducer, 24V prove
- LineIFCHSIvalve LOW
120V igniter, 24V low solenoid
- 24VW2inducer HIGHHPSvalve HIGH
Missing W2 = stuck on low
- 24VFlame rodIFC
µA DC
- LineIFCheat blower
After flame. Motor class on this plate.
Prove it
- W1 then W2 at the IFC under a 2-heat call.
- If it never stages, W2 is missing at the board — not a bad gas valve until that is proven.
Do not
- Do not convert this to Infinity by landing W on a random terminal.
- Do not apply AMVC / ARVT ComfortBridge menus or a memory card.
926T / 59TP6 / AR9T96 / GR9T96 / S9V2 / EL296E class. Same landing on 80% metal-vent cousins — the vent is not the wire.
Sequence
- 1
W1
Limits/rollout proved closed. Inducer starts on low. Low-fire PS must close (3-red if it never does; 2-red if it was already closed with the inducer off).
- 2
HSI / trial
Igniter warms, first-stage solenoid opens. Flame must prove at the rod. Three failed tries → 7-red lockout. Open igniter circuit → 12-red.
- 3
Blower
Heat-on delay, then VS blower at the IFC heat-CFM setting. This is not a TM9T tap. Wrong CFM is how 4-red starts.
- 4
W2 / high fire
Inducer goes high. High-fire PS must close (still presented as 3-red / 6-red, not a separate E9). Second-stage solenoid opens.
- 5
Flame / limits
Flame lost 5 times → 8-red. Limit open → 4-red (also check the board fuse). Limit open >5 min → 11-red hard lockout. Rollout → 5-red.
- 6
Satisfied
Valve off, inducer post-purge, blower heat-off delay. Flame with no call → 1-red (some boards also use 10-red).
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
Slow green
Normal, no heat call
IFC powered, idle. Not a fault.
1 Confirm this is not a fault
On the York TM9V this readout (Slow green) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the York TM9V IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: If the house is cold, the call never reached W. Check R/W at the IFC, door switch, and the thermostat.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch JCI / Coleman-York IFC · green / amber / red LED through one cycle and write the first real fault that replaces this status word.
Expect: W1: Limits/rollout proved closed. Inducer starts on low. Low-fire PS must close (3-red if it never does; 2-red if it was already closed with the inducer off).
Slow amber
Normal, heat call
IFC sees W and is running or sequencing a heat cycle.
1 Confirm this is not a fault
On the York TM9V this readout (Slow amber) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the York TM9V IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: If burners are out while amber is slow, you caught it between trials or the fault has not latched yet. Stay and watch.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch JCI / Coleman-York IFC · green / amber / red LED through one cycle and write the first real fault that replaces this status word.
Expect: W1: Limits/rollout proved closed. Inducer starts on low. Low-fire PS must close (3-red if it never does; 2-red if it was already closed with the inducer off).
Rapid red
Twinning / 24V phasing
TWIN circuit miswired or 24 V phasing between twinned IFCs is wrong.
1 Is this cabinet actually twinned?
On a standalone York TM9V, nothing belongs on the TWIN terminal. A leftover jumper throws this. Standalone TM9V: nothing belongs on the TWIN terminal.
Expect: TWIN empty on a single cabinet.
2 Twinned pair must be the same IFC family
Twinned units must be the same family and IFC revision. Mixing this plate with a communicating sister SKU will not twin. Twinned pair must be the same JCI family / same IFC revision. Check 24 V phasing per the twinning kit.
Expect: Same model family, same IFC, kit installed per the twinning sheet.
3 Phasing and 24 V
Twinning errors that survive a correct kit are 24 V phasing or a broken twin lead. Measure both cabinets before you change an IFC.
Expect: In-phase 24 V. Continuous twin lead.
Rapid amber
Flame sense < 1.5 µA
Flame is present but current is below the warning threshold. Normal on this IFC is ~3.7 µA DC. Lockout territory is < 0.1 µA.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on York TM9V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Read µA at the IFC flame-sense test pad during a run.
Expect: Flame sense: Normal ~3.7 µA DC at the IFC test pad. Warning (rapid amber) < 1.5 µA. Lockout < 0.1 µA.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Clean the rod with a non-scratch pad — not sandpaper.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live York TM9V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Chassis ground to burner box and IFC. Reversed polarity will also show as 9-red.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
4 amber
Y without G
Thermostat is presenting Y and not G. IFC will not assume a fan call the way some 80% boards do.
1 Is the wheel free?
Spin the York TM9V blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Stat wiring: Y and G both need to make on a cool call, or use a stat that ties them.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. A cooling-only miswire here is not a pressure-switch problem.
Expect: Heat CFM: IFC VS menu matched to the rise range on the rating plate. Not TM9T taps.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
1 red
Flame sensed, no call for heat
Rod sees flame with the gas valve de-energized.
1 Shut the gas cock first
On York TM9V the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Rod shorted to ground or IFC flame circuit.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Treat as hazard until the valve is proven closed.
Expect: 0 VAC at both solenoids after the call. No flame.
2 red
Pressure switch stuck closed
A PS is made with the inducer off.
1 Unplug the switch with the inducer off
On York TM9V this code is the switch made when the inducer is not running. Unplug that switch only. Unplug that switch. If the code changes, the switch is welded or the hose is holding residual draft / water.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
2 Water in the hose vs a welded switch
Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Two-stage: identify which switch (low vs high tap). Do not tee them.
Expect: Hose empty. Switch opens with no draft.
3 IFC input last
If the switch ohms open, the hose is dry, and the code does not change with the harness off, the York TM9V IFC input is shorted. Do not keep swapping switches. IFC input shorted — only after the switch ohms open.
Expect: Known-good open switch + open harness = code gone. If not, IFC.
3 red
PS failed to close after inducer
Inducer is running and the prove switch will not close. On this 96% that is almost always trap / collector / PVC, not a bad switch.
1 Prove inducer and the live code
Do not pull power — that clears the York TM9V active code. Write 3 red. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer spinning? 120 VAC at the inducer on the call.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Dump the condensate trap and open the collector. TM9V 96% will not make pressure with a full trap.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. PVC intake/exhaust — bird screen, ice, long run, wind, slope back to the collector.
Expect: LPS / HPS: Two NO switches, two hoses, two ports. Closed only when that inducer speed is making the collector setpoint.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
4 red
Limit open
Primary limit (and on some boards the 24 V fuse path) is open. Airflow or overfire — not a charge problem.
1 Airflow before you touch the limit
On York TM9V a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). This is TM9V: heat CFM lives in the VS menu. Do not look for TM9T taps.
Expect: Heat CFM: IFC VS menu matched to the rise range on the rating plate. Not TM9T taps.
2 Measure static and temperature rise
Total external static vs the York TM9V blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Filter, blower wheel, A-coil, return size, total external static vs the TM9V blower chart.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Also check the automotive fuse on the IFC — 4-red on this family includes an open board fuse.
Expect: Manifold on plate. Limit closed when cool.
5 red
Rollout open
Manual-reset rollout opened. Treat as flame outside the exchanger until proven otherwise.
1 Treat this as flame outside the exchanger
Do not reset the York TM9V rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Primary exchanger cracks, burner alignment, crossover. Blocked secondary / condensate / flue.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on York TM9V is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave. Reset only after the cause is fixed. Recurring 5-red is a CO / fire call.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
6 red
PS opened 4 times this call
Draft proved, then dropped four times on this W. One-hour lockout, then retry.
1 Prove inducer and the live code
Do not pull power — that clears the York TM9V active code. Write 6 red. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Same physics as 3-red — trap, hose, vent, wind — but intermittent. Watch a full call; do not just ohm a cold switch.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Condensate backing into the collector only after several minutes.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. High-fire only? Then the high-fire hose / vent capacity is the path.
Expect: LPS / HPS: Two NO switches, two hoses, two ports. Closed only when that inducer speed is making the collector setpoint.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
7 red
Flame not established after 3 tries
Three ignition trials without prove. One-hour-class lockout.
1 Watch one full try — do not reset
Write the York TM9V code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. Watch one full try: inducer, HSI glow, valve click, flame, µA.
Expect: W1 → HSI / trial → Blower → W2 / high fire → Flame / limits → Satisfied
2 Gas and the valve
Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence. Gas supply and manifold (low then high). Gas cock, LP tank, meter lock.
Expect: Inlet and manifold on the plate. 24 VAC only during trial.
3 Flame prove, then the lockout timer
Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets. Igniter 120 VAC and ohms. Open circuit is 12-red — if you have 7-red the igniter usually glowed.
Expect: Flame sense: Normal ~3.7 µA DC at the IFC test pad. Warning (rapid amber) < 1.5 µA. Lockout < 0.1 µA.
8 red
Flame lost 5 times
Flame proved, then dropped five times on this cycle.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on York TM9V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. µA while running — want ~3.7 µA, warning <1.5, drop-out <0.1.
Expect: Flame sense: Normal ~3.7 µA DC at the IFC test pad. Warning (rapid amber) < 1.5 µA. Lockout < 0.1 µA.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Gas pressure sag when other appliances fire. Valve that will not hold.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live York TM9V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Draft that collapses when the blower comes on (limit/PS cluster).
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
9 red
Reversed polarity / grounding
L1/N reversed or chassis ground missing. HSI and flame sense both suffer.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on York TM9V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Hot and neutral at the IFC, not just the disconnect.
Expect: Flame sense: Normal ~3.7 µA DC at the IFC test pad. Warning (rapid amber) < 1.5 µA. Lockout < 0.1 µA.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Burner box to IFC ground screw. Painted screw, missing star washer.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live York TM9V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Flame probe not shorted to chassis.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
10 red
Flame sensed, no call (some boards)
Same family as 1-red on later JCI revisions — flame with valve off.
1 Shut the gas cock first
On York TM9V the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Read the door card on THIS IFC. 1-red vs 10-red is a revision split, not two different physics.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Gas valve leak / slow close. Shut the cock.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
11 red
Limit open >5 min · hard lockout
Limit stayed open long enough that the IFC assumes the blower never moved air.
1 Airflow before you touch the limit
On York TM9V a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Blower actually running on the heat call? VS motor harness and IFC CFM setting.
Expect: Heat CFM: IFC VS menu matched to the rise range on the rating plate. Not TM9T taps.
2 Measure static and temperature rise
Total external static vs the York TM9V blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Wheel off the shaft, seized motor, or a door-switch/fuse that killed the motor while the limit was open.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Cycle 24 VAC only after airflow is restored. Repeating 11-red is not a bad limit.
Expect: Manifold on plate. Limit closed when cool.
12 red
Open igniter circuit
IFC measured an open HSI path before or during trial.
1 Ohms at the igniter, then at the IFC
On York TM9V measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms at the igniter plug, then at the IFC. Cracked nitride is common.
Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Harness rub-through on the collector.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter. Loose/disconnected igniter plug after a heat-exchanger job.
Expect: One clean light after a known-good igniter and a proven ground.
Steady red
Control failure
Internal IFC fault. The LED stays on continuously — not a counted flash.
1 Write the live code and watch one cycle
On York TM9V read JCI / Coleman-York IFC · green / amber / red LED before you pull power. Write Steady red exactly. Watch one full sequence and note which step dies. Confirm it is truly steady, not a fast count you missed.
Expect: W1: Limits/rollout proved closed. Inducer starts on low. Low-fire PS must close (3-red if it never does; 2-red if it was already closed with the inducer off).
2 Prove the circuit this code names
120 VAC and 24 VAC present, fuse good, then replace the control. The IFC is not field-repairable.
Expect: A measured open, short, or out-of-range reading — not a guess.
3 Confirm with a number, then the next part
If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.
Expect: Flame sense: Normal ~3.7 µA DC at the IFC test pad. Warning (rapid amber) < 1.5 µA. Lockout < 0.1 µA.
Workflows
3-red no heat (trap / PVC)
Inducer runs, no ignition, LED counts 3 red.
1 Prove the call and the live code
Write 3-red before you pull power. This is PS failed to close after the inducer, not Carrier 31 and not Amana E2.
Expect: Write whatever JCI / Coleman-York IFC · green / amber / red LED is showing. Active code repeats until the fault clears or 24 V is removed. Write color + count (or rapid/steady) before you cycle power. 6-red and 7-red lock out ~1 hour then retry.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Prove inducer 120 VAC and spinning. Silent inducer is not a switch.
Expect: HSI / trial: Igniter warms, first-stage solenoid opens. Flame must prove at the rod. Three failed tries → 7-red lockout. Open igniter circuit → 12-red.
3 Confirm with a number, then the next part
Open the trap and the collector. TM9V 96% drowns overnight — that is the winter call. Hose dry and on the correct tap for the speed that is running. Two PS, no tee. PVC intake/exhaust: ice, bird screen, sag holding water, wind cap.
Expect: Flame sense: Normal ~3.7 µA DC at the IFC test pad. Warning (rapid amber) < 1.5 µA. Lockout < 0.1 µA. · LED: Color + count or rapid/steady. Slow green/amber are status.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
4-red limit on a TM9V
Heat starts, then drops. 4-red or 11-red.
1 Prove the call and the live code
This is variable-speed. Heat CFM is in the IFC menu — not TM9T taps and not a 9-speed Amana harness.
Expect: Write whatever JCI / Coleman-York IFC · green / amber / red LED is showing. Active code repeats until the fault clears or 24 V is removed. Write color + count (or rapid/steady) before you cycle power. 6-red and 7-red lock out ~1 hour then retry.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Also check the board fuse. 4-red on this JCI IFC includes an open fuse.
Expect: HSI / trial: Igniter warms, first-stage solenoid opens. Flame must prove at the rod. Three failed tries → 7-red lockout. Open igniter circuit → 12-red.
3 Confirm with a number, then the next part
Filter, coil, return, TES vs the TM9V chart for this cabinet. Rise vs plate. Overfire trips a clean-filter TM9V. 11-red means the limit stayed open >5 min — prove the blower is actually moving air before you change a limit.
Expect: Flame sense: Normal ~3.7 µA DC at the IFC test pad. Warning (rapid amber) < 1.5 µA. Lockout < 0.1 µA. · LED: Color + count or rapid/steady. Slow green/amber are status.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Identify V vs T vs X
Plate is dirty or the last tech mixed York 96% boards.
1 Prove the call and the live code
Last letter on the plate: V = this page (VS CFM menu). T = TM9T taps (other chart). X = newer control — do not force this LED chart onto an X without reading that door card.
Expect: Write whatever JCI / Coleman-York IFC · green / amber / red LED is showing. Active code repeats until the fault clears or 24 V is removed. Write color + count (or rapid/steady) before you cycle power. 6-red and 7-red lock out ~1 hour then retry.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Motor: serial/VS harness and a CFM menu = TM9V. Tap plugs on the motor = TM9T.
Expect: HSI / trial: Igniter warms, first-stage solenoid opens. Flame must prove at the rod. Three failed tries → 7-red lockout. Open igniter circuit → 12-red.
3 Confirm with a number, then the next part
Coleman / Luxaire sticker does not change the letter. TM8* is 80% — leave this page. LED is green/amber/red. If you see Carrier 31 or Amana E2 you are on the wrong family.
Expect: Flame sense: Normal ~3.7 µA DC at the IFC test pad. Warning (rapid amber) < 1.5 µA. Lockout < 0.1 µA. · LED: Color + count or rapid/steady. Slow green/amber are status.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Flame sense
Normal ~3.7 µA DC at the IFC test pad. Warning (rapid amber) < 1.5 µA. Lockout < 0.1 µA.
LED
Color + count or rapid/steady. Slow green/amber are status.
LPS / HPS
Two NO switches, two hoses, two ports. Closed only when that inducer speed is making the collector setpoint.
Heat CFM
IFC VS menu matched to the rise range on the rating plate. Not TM9T taps.
Board fuse
Intact 24 V automotive fuse. Open fuse can present as 4-red.
Gotchas
- Do not apply Carrier 31 or Amana E2 to this LED. Slow green is idle, not a code.
- TM9T looks identical in the basement and uses this same flash table — airflow checks are taps, not the VS menu.
- TM8V / TM8Y 80% uses the same-looking LED and 3-red is metal-vent draft, not a 96% trap.
- 4-red includes the board fuse. Replacing a limit without checking the fuse and the VS CFM setting is the callback.
- 1-red and 10-red are the same flame-no-call physics on different board dates. Read the sticker in this cabinet.
Related plates
Install this plate
Install TM9V as York/JCI 96% two-stage VS. Multi-color LED IFC. Coleman / Luxaire TM9V share it.
Cat IV PVC · two-stage · dual PS · VS CFM menu · 24V · example TM9V080B12MP11
IFC & vent
- JCI multi-color LED. 3-red on this 96% is trap / PVC / inducer — not TM8V chimney.
- CFM lives in the IFC menu, not heat/cool taps (those are TM9T).
- Read the full plate (TM9V080B12MP11), not just TM9.
First fire
- 1Set VS heat CFM, prime the trap, W1 then W2, both PS hoses.
Do not on York TM9V
- Do not apply Carrier 59TP6 31/33/34 or Amana E1/E9 to this LED.
- Do not use the TM9T tap playbook on this VS motor.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- York residential gas furnacesLiterature searchTM9 / TM8 family listing (Coleman / Luxaire share the JCI IFC). UPGNet holds the I/O.Open manufacturer PDF
- York / Bosch Home ComfortLiterature searchSearch York TM9V on the maker’s literature page.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Residential limited warranty
dealerYork furnace warranty
Registered TM8 / TM9 furnace warranty · Dealer claims portal
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal