Models
Yorkfurnace

TM8V

York/JCI 80% · variable-speed · metal vent

York/JCI 80% variable-speed (TM8V) and the TM8X/TM8Y badge cousins. The LED speaks the same green/amber/red language as TM9V. 3-red is Category I metal-vent draft — not a 96% condensate trap.

Not TM9V / TM9T (96% PVC, collector, trap). Dumping a trap that is not there will not clear 3-red. Not Carrier 58STA/58CVA just because both are 80%.

AFUE

80% class · Category I metal vent · no PVC secondary

Staging

Two-stage on V/Y; confirm the plate — some TM8X/Y are single- or two-stage

Blower

TM8V = VS CFM menu; TM8X/Y may be tap or VS — read the motor

Control

Same-looking JCI multi-color LED IFC as the TM9 family

Vent

Metal B-vent / chimney. No condensate collector, no 96% trap

This board

JCI / Coleman-York IFC · green / amber / red LED

  • Same flash table as TM9V: slow green idle, slow amber heat, red 1–12, rapid red twinning, rapid amber <1.5 µA, 4 amber = Y without G, steady red = control.
  • 3-red / 2-red / 6-red are still the pressure / draft switch — but the physics are metal-vent draft, not a drowned collector.
  • 4-red is still limit + board fuse. Airflow path follows whatever blower this cabinet actually has (VS menu on TM8V, taps on some TM8X/Y).

Active LED repeats until cleared or 24 V is removed. Write color + count first.

Universal swap

No universal

80% VS. Not a 50A55 / S9200U 80% PSC drop-in.

Silk: 50A55 · 031-00662 · 031-01140

White-Rodgers

ICM

Honeywell

  • S9200U1000

    S9200U lists older York 031-00662 / 031-01140 / 031-01234 and 50A55-843. Current TM8V is VS — only if this cabinet is actually that older single-stage IFC.

  • 50A55-843 / S9200U1000 ‘because 80% and York’. TM9V 96% board.

After you pull the dead card

  1. 1OEM York 80% VS IFC. Prove metal-vent draft.

Field wiring

Written landings for York TM8V. Not a factory schematic.

Furnace · two-stage 24V
R / C / W1 / W2 / Y / GGas furnace

Two-stage conventional furnace. W1 low fire, W2 high fire. Outdoor staging is Y or Y1/Y2 — separate from the gas valve.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC → R120V / 24V
  2. 2Low. W1 → inducer LOW → LPS → HSI → valve LOWFirst fire
  3. 3High. W2 → inducer HIGH → HPS → valve HIGHSecond solenoid
  4. 4Flame. Rod → IFCµA DC both stages
  5. 5Blow. IFC → heat blowerAfter flame

This indoor

JCI 80% VS. Metal vent.

24V two-stage heat

Door has W1 and W2. Not Infinity. Not ComfortBridge.

Two-stage thermostat

A single-W stat never proves high fire. That is not a weak inducer.

  • R24V hot24V
  • CCommon24V
  • W1Low-fire heat24V
  • W2High-fire heat24V
  • Y / Y1Cool24V
  • Y2Outdoor high if the condenser is two-stage24V
  • GFan24V

Two-stage IFC

W2 is high fire. Do not tee the pressure-switch hoses because there are two stages.

  • RHot24V
  • CCommon to outdoor24V
  • W1Low fire24V
  • W2High fire24V
  • YCool out24V
  • GBlower / cool tap24V

Landing

  • 24VStat W1IFC W1

    Low fire

  • 24VStat W2IFC W2

    High fire. Missing W2 = stuck on low.

  • 24VStat YIFC Youtdoor Y

    Cool

  • 24VC throughout

    Common

IFC harness — two-stage heat

W1 then W2. Low-fire prove is not high-fire prove.

Transformer + fuse

Same 24V transformer as single-stage. Fuse still kills the whole strip.

  • L1 / N120VLine
  • XFMR24V to R24V
  • FUSEOn the IFC24V

24V safety chain

Door, limit, rollout. A limit trip is not an E9 / 32 pressure-switch story.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + two pressure switches

W1 = inducer low + LPS. W2 = inducer high + HPS. Separate hoses. Do not tee.

  • IND LO120V low-speed inducerLine
  • IND HI120V high-speed inducerLine
  • LPSLow-fire prove24V
  • HPSHigh-fire prove24V
  • HOSESOne hose per switch. Never tee LPS and HPS24V

HSI + two-stage valve

Igniter 120V. Low solenoid on W1. Second solenoid on W2 after HPS closes.

  • HSI120V igniterLine
  • MV / LO24V low-fire solenoid24V
  • HV / HI24V high-fire solenoid24V
  • FLAMEµA DC on the rod24V

Blower — read the motor

PSC has a cap. 9-speed has F-taps. Serial VS has a harness and no cap. Do not mix those playbooks.

  • PSCCap + 3–5 speed leads24V
  • 9-SPDF01–F09 taps24V
  • VSFat serial plug, no cap24V

Landing

  • LineW1IFCinducer LOWLPS

    120V inducer, 24V prove

  • LineIFCHSIvalve LOW

    120V igniter, 24V low solenoid

  • 24VW2inducer HIGHHPSvalve HIGH

    Missing W2 = stuck on low

  • 24VFlame rodIFC

    µA DC

  • LineIFCheat blower

    After flame. Motor class on this plate.

Prove it

  • W1 then W2 at the IFC under a 2-heat call.
  • If it never stages, W2 is missing at the board — not a bad gas valve until that is proven.

Do not

  • Do not convert this to Infinity by landing W on a random terminal.
  • Do not apply AMVC / ARVT ComfortBridge menus or a memory card.

926T / 59TP6 / AR9T96 / GR9T96 / S9V2 / EL296E class. Same landing on 80% metal-vent cousins — the vent is not the wire.

Sequence

  1. 1

    W1

    Inducer → draft/pressure switch on the metal vent / inducer housing → HSI → low fire. No secondary drain to prime.

  2. 2

    W2

    High fire, still Category I. Wind and shared chimneys show up here as 3-red / 6-red.

  3. 3

    Limit

    80% coil-on-top jobs still 4-red. VS CFM on TM8V; taps on TM8X/Y.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

Slow green

Normal, no heat call

info

Idle, powered.

  1. 1 Confirm this is not a fault

    On the York TM8V this readout (Slow green) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.

    Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.

    If fail: If the word never changes on a real call, the call is not reaching this IFC.

    If pass: The board is alive. Diagnose the comfort complaint, not this code.

  2. 2 Prove the call at the board

    Measure R to W / Y / G at the York TM8V IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.

    Expect: W path if the house is cold.

    If fail: Fix the stat, harness, or data pair before you change parts.

  3. 3 Watch one full sequence

    Leave power on. Watch JCI / Coleman-York IFC · green / amber / red LED through one cycle and write the first real fault that replaces this status word.

    Expect: W1: Inducer → draft/pressure switch on the metal vent / inducer housing → HSI → low fire. No secondary drain to prime.

Slow amber

Normal, heat call

info

Heat sequence running.

  1. 1 Confirm this is not a fault

    On the York TM8V this readout (Slow amber) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.

    Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.

    If fail: If the word never changes on a real call, the call is not reaching this IFC.

    If pass: The board is alive. Diagnose the comfort complaint, not this code.

  2. 2 Prove the call at the board

    Measure R to W / Y / G at the York TM8V IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.

    Expect: Status, not a fault.

    If fail: Fix the stat, harness, or data pair before you change parts.

  3. 3 Watch one full sequence

    Leave power on. Watch JCI / Coleman-York IFC · green / amber / red LED through one cycle and write the first real fault that replaces this status word.

    Expect: W1: Inducer → draft/pressure switch on the metal vent / inducer housing → HSI → low fire. No secondary drain to prime.

Rapid red

Twinning / 24V phasing

lockout

TWIN circuit or 24 V phasing.

  1. 1 Is this cabinet actually twinned?

    On a standalone York TM8V, nothing belongs on the TWIN terminal. A leftover jumper throws this. TWIN terminal empty on a standalone.

    Expect: TWIN empty on a single cabinet.

  2. 2 Twinned pair must be the same IFC family

    Twinned units must be the same family and IFC revision. Mixing this plate with a communicating sister SKU will not twin.

    Expect: Same model family, same IFC, kit installed per the twinning sheet.

  3. 3 Phasing and 24 V

    Twinning errors that survive a correct kit are 24 V phasing or a broken twin lead. Measure both cabinets before you change an IFC.

    Expect: In-phase 24 V. Continuous twin lead.

Rapid amber

Flame sense < 1.5 µA

warn

Weak µA. Normal ~3.7; lockout < 0.1.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on York TM8V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Rod, ground, manifold.

    Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold on the rating plate. Solid burner-box ground.

  3. 3 Prove it is not a switch opening

    Watch the live York TM8V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

4 amber

Y without G

warn

Cool call missing G.

  1. 1 Is the wheel free?

    Spin the York TM8V blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Stat wiring.

    Expect: Wheel free. Correct motor family for this IFC.

  2. 2 Command vs rotation

    Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data.

    Expect: Command present. Motor amps in range, not locked.

  3. 3 Static and the wrong motor

    High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.

    Expect: Static on the blower chart. Matching motor / shared-data card.

1 red

Flame sensed, no call for heat

hazard

Flame with valve off.

  1. 1 Shut the gas cock first

    On York TM8V the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Leaking valve.

    Expect: Flame dies when the cock is shut.

    If fail: Leaking valve. Replace. Do not leave the unit.

  2. 2 Rod and IFC flame circuit

    If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector.

    Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.

  3. 3 Confirm valve solenoids are actually off

    Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.

    Expect: 0 VAC at both solenoids after the call. No flame.

2 red

Pressure switch stuck closed

lockout

Draft switch made with inducer off.

  1. 1 Unplug the switch with the inducer off

    On York TM8V this code is the switch made when the inducer is not running. Unplug that switch only. Unplug the switch. Water in the inducer hose from a long metal run can fake this — still not a 96% collector.

    Expect: Code changes when the harness is open.

    If fail: Wrong switch, or the IFC input is shorted.

    If pass: Switch/hose path. Go to step 2.

  2. 2 Water in the hose vs a welded switch

    Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off.

    Expect: Hose empty. Switch opens with no draft.

  3. 3 IFC input last

    If the switch ohms open, the hose is dry, and the code does not change with the harness off, the York TM8V IFC input is shorted. Do not keep swapping switches.

    Expect: Known-good open switch + open harness = code gone. If not, IFC.

3 red

PS failed to close after inducer

lockout

Metal-vent draft will not prove. This is not a 96% trap call.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the York TM8V active code. Write 3 red. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer spinning and 120 VAC.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Chimney liner, cap, common-vent tables, bird nest, wind. Spillage at the inducer inlet is a fail.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. PS hose on the inducer housing, not a missing PVC collector.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

4 red

Limit open

warn

Airflow or overfire. Also check the board fuse.

  1. 1 Airflow before you touch the limit

    On York TM8V a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). TM8V: VS heat CFM menu. TM8X/Y: taps if that is the motor in the cabinet.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the York TM8V blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Filter, 80% A-coil on top, wheel.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Board fuse.

    Expect: Manifold on plate. Limit closed when cool.

5 red

Rollout open

hazard

Flame containment. Manual reset.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the York TM8V rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Exchanger, burners, blocked metal flue. Reset only after the cause.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on York TM8V is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

6 red

PS opened 4 times this call

lockout

Intermittent metal-vent draft. One-hour lockout.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the York TM8V active code. Write 6 red. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Wind, cold chimney, inducer wheel, hose. Not a trap siphon.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

7 red

Flame not established after 3 tries

lockout

Ignition retries exceeded.

  1. 1 Watch one full try — do not reset

    Write the York TM8V code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI, gas, rod, ground.

    Expect: W1 → W2 → Limit

  2. 2 Gas and the valve

    Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence.

    Expect: Inlet and manifold on the plate. 24 VAC only during trial.

  3. 3 Flame prove, then the lockout timer

    Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.

    Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

8 red

Flame lost 5 times

lockout

Flame dropped after prove.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on York TM8V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. µA, gas, draft when the blower starts.

    Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold on the rating plate. Solid burner-box ground.

  3. 3 Prove it is not a switch opening

    Watch the live York TM8V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

9 red

Reversed polarity / grounding

lockout

L1/N or ground.

  1. 1 Hot and neutral at the IFC, not the disconnect

    On York TM8V polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot/neutral at the IFC, burner ground.

    Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.

  2. 2 Burner-box and IFC ground

    Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.

    Expect: Near-zero ohms burner box to IFC ground screw.

  3. 3 Then flame and HSI

    Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.

    Expect: Code cleared. One clean light. µA in range.

10 red

Flame sensed, no call (some boards)

hazard

Same as 1-red on later revisions.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on York TM8V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Door card. Valve leak.

    Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold on the rating plate. Solid burner-box ground.

  3. 3 Prove it is not a switch opening

    Watch the live York TM8V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

11 red

Limit open >5 min · hard lockout

lockout

Blower never reclosed the limit.

  1. 1 Airflow before you touch the limit

    On York TM8V a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Blower running? VS harness or tap motor actually spinning.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the York TM8V blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).

    Expect: Manifold on plate. Limit closed when cool.

12 red

Open igniter circuit

lockout

HSI path open.

  1. 1 Ohms at the igniter, then at the IFC

    On York TM8V measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms and 120 VAC during trial.

    Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

Steady red

Control failure

lockout

Internal IFC fault.

  1. 1 Write the live code and watch one cycle

    On York TM8V read JCI / Coleman-York IFC · green / amber / red LED before you pull power. Write Steady red exactly. Watch one full sequence and note which step dies. Power and fuse, then the board.

    Expect: W1: Inducer → draft/pressure switch on the metal vent / inducer housing → HSI → low fire. No secondary drain to prime.

  2. 2 Prove the circuit this code names

    Use the York TM8V door card and the test points on this plate. Isolate the named switch, sensor, or output with a meter — do not swap the IFC first.

    Expect: A measured open, short, or out-of-range reading — not a guess.

  3. 3 Confirm with a number, then the next part

    If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.

    Expect: Vent: Category I metal. Spillage at the inducer inlet / draft path is a fail. No PVC trap.

Workflows

3-red on an 80% TM8

Inducer runs, no light-off, someone is hunting a 96% trap.

  1. 1 Prove the call and the live code

    Confirm the plate: TM8*, 80%, metal vent. If it says TM9 you are on the wrong chart.

    Expect: Write whatever JCI / Coleman-York IFC · green / amber / red LED is showing. Active LED repeats until cleared or 24 V is removed. Write color + count first.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    There is no secondary collector to dump. Look at the metal vent, cap, liner, and the inducer wheel.

    Expect: W2: High fire, still Category I. Wind and shared chimneys show up here as 3-red / 6-red.

  3. 3 Confirm with a number, then the next part

    Common-vented water heater: pull the venting tables before you condemn the switch. Hose to the inducer housing can hold flue condensate on a long cold metal run — still Category I physics. Then ohm the switch with the inducer up.

    Expect: Vent: Category I metal. Spillage at the inducer inlet / draft path is a fail. No PVC trap. · Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

No heat in HP weather (furnace only)

This furnace is the heat — not a Bosch/Daikin inverter call.

  1. 1 Prove the call and the live code

    LED first. 7-red / 12-red is ignition. 3-red is draft. 4-red is airflow.

    Expect: Write whatever JCI / Coleman-York IFC · green / amber / red LED is showing. Active LED repeats until cleared or 24 V is removed. Write color + count first.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Do not apply TM9V trap steps or Carrier 31 PVC steps.

    Expect: W2: High fire, still Category I. Wind and shared chimneys show up here as 3-red / 6-red.

  3. 3 Confirm with a number, then the next part

    VS CFM on TM8V only. Read the motor before you hunt a menu on a tap cabinet.

    Expect: Vent: Category I metal. Spillage at the inducer inlet / draft path is a fail. No PVC trap. · Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Vent

Category I metal. Spillage at the inducer inlet / draft path is a fail. No PVC trap.

Flame sense

Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.

LED

Same color language as TM9V. Physics behind 3-red are not.

Gotchas

  • Same-looking LED as TM9V is why techs dump a trap that does not exist.
  • TM8X / TM8Y share this page’s LED. Confirm VS vs taps on the motor before you adjust airflow.
  • Carrier 58STA 80% uses two-digit 31, not this green/amber/red chart.

Related plates

Install this plate

Install TM8V as York/JCI 80% VS. 3-red is metal-vent draft. No 96% trap.

Cat I metal vent · two-stage on V/Y (confirm plate) · VS CFM menu · same-looking LED as TM9

Vent

  • B-vent / chimney. Dumping a trap that is not there will not clear 3-red.
  • TM8X/Y may be tap or VS — read the motor on THIS plate.

First fire

  1. 1Confirm Cat I. Heat call. Spillage / CO fail = stop.

Do not on York TM8V

  • Do not apply TM9V collector / PVC steps.
  • Do not treat Carrier 58STA 31 as this JCI 3-red.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • York residential gas furnacesLiterature searchTM9 / TM8 family listing (Coleman / Luxaire share the JCI IFC). UPGNet holds the I/O.Open manufacturer PDF
  • York / Bosch Home ComfortLiterature searchSearch York TM8V on the maker’s literature page.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    dealer

    York furnace warranty

    Registered TM8 / TM9 furnace warranty · Dealer claims portal

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal