TM8T
JCI 80% · two-stage or single · multi-speed · Cat I
York/Coleman/Luxaire 80% TM8T / TM8X. Metal vent. Same JCI LED as TM8V — not a VS motor on the T/X plates. 3-red is chimney draft.
Not TM8V 80% VS. Not TM9T 96%.
AFUE
80% · Cat I metal
This board
JCI / Coleman-York IFC · green / amber / red LED
- Same flash table as TM9V: slow green idle, slow amber heat, red 1–12, rapid red twinning, rapid amber <1.5 µA, 4 amber = Y without G, steady red = control.
- 3-red / 2-red / 6-red are still the pressure / draft switch — but the physics are metal-vent draft, not a drowned collector.
- 4-red is still limit + board fuse. Airflow path follows whatever blower this cabinet actually has (VS menu on TM8V, taps on some TM8X/Y).
Active LED repeats until cleared or 24 V is removed. Write color + count first.
Universal swap
80% JCI multi-speed. Not a 50A55 80% PSC drop-in unless that is the silk.
Silk: 50A55
White-Rodgers
—ICM
—Honeywell
—- 50A55-843 ‘because 80% and York’. TM8V VS board.
After you pull the dead card
- 1OEM York 80% IFC. Metal vent.
Field wiring
Written landings for York TM8T. Not a factory schematic.
Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC → transformer → R120V in, 24V out
- 2Call. Stat W → IFC W~24 VAC
- 3Draft. IFC → inducer → PS close120V motor, 24V prove
- 4Ignite. IFC → HSI120 VAC
- 5Gas. IFC → valve~24 VAC
- 6Flame. Rod → IFCµA DC
- 7Blow. IFC → heat speedAfter flame prove
This indoor
JCI 80% multi-speed. Metal vent.
24V single-stage heat
Door card is one-stage. Twin terminal empty unless the job is actually twinned.
Wall thermostat
Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.
- R24V hot from the IFC24V
- CCommon24V
- WHeat24V
- YCool — also starts the outdoor24V
- GFan24V
Furnace IFC
Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.
- RHot to the stat24V
- CCommon — must reach the outdoor24V
- WHeat call24V
- YCool in / cool out24V
- GBlower24V
- TWINEmpty unless twinned24V
Landing
- 24VIFC Rstat R
~24 VAC hot
- 24VIFC Cstat Coutdoor C
Common
- 24VStat WIFC W
Heat. Stays in this cabinet.
- 24VStat YIFC Youtdoor Y
Cool / contactor
- 24VStat GIFC G
Fan. Does not go outdoors.
IFC harness — single-stage heat
After W arrives. This is the gas train, not the thermostat strip.
Transformer + fuse
120V primary. 24V secondary. Dark stat = fuse / door / transformer first.
- L1 / N120V to the IFCLine
- XFMR24V to R24V
- FUSEOn the IFC24V
24V safety chain
Door, limit, rollout in series. Open anywhere kills heat.
- DOORInterlock24V
- LIMITMain limit — rise / no airflow24V
- ROLLOUTManual reset. Do not jumper and leave24V
Inducer + one pressure switch
W → inducer 120V → PS closes → IFC continues. One hose, one switch.
- IND120V from the IFC to the inducerLine
- PS24V prove back to the IFC24V
- HOSESingle hose. Do not add a second because two-stage boards have two.24V
HSI + single valve
Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.
- HSI120V hot-surface igniter — not 24VLine
- VALVE24V to the single solenoid24V
- FLAMEµA DC on the rod. Not a 24V circuit24V
PSC blower + run cap
Heat / cool / park taps on the motor. The cap is on this blower — not the outdoor dual can.
- HEATHeat speed tap24V
- COOLCool speed tap24V
- PARKUnused leads parked24V
- CAPRun capacitor on the blowerCap
Landing
- LineL1IFCinducer
120 VAC after W
- 24VIFCPSIFC
~24 VAC prove. Open PS = no ignition.
- LineIFCHSI
120 VAC during trial
- 24VIFCgas valve
~24 VAC after flame prove starts
- 24VFlame rodIFC
µA DC. Not 24V.
- LineIFCblower
120V tap + cap
Prove it
- 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
- W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.
Do not
- Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
- Do not hunt W2 / E8 / high-fire on a one-stage door.
- TWIN must be empty on a standalone.
9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.
Sequence
- 1
W1
Inducer → draft/pressure switch on the metal vent / inducer housing → HSI → low fire. No secondary drain to prime.
- 2
W2
High fire, still Category I. Wind and shared chimneys show up here as 3-red / 6-red.
- 3
Limit
80% coil-on-top jobs still 4-red. VS CFM on TM8V; taps on TM8X/Y.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
Slow green
Normal, no heat call
Idle, powered.
1 Confirm this is not a fault
On the York TM8T this readout (Slow green) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the York TM8T IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: W path if the house is cold.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch JCI / Coleman-York IFC · green / amber / red LED through one cycle and write the first real fault that replaces this status word.
Expect: W1: Inducer → draft/pressure switch on the metal vent / inducer housing → HSI → low fire. No secondary drain to prime.
Slow amber
Normal, heat call
Heat sequence running.
1 Confirm this is not a fault
On the York TM8T this readout (Slow amber) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the York TM8T IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: Status, not a fault.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch JCI / Coleman-York IFC · green / amber / red LED through one cycle and write the first real fault that replaces this status word.
Expect: W1: Inducer → draft/pressure switch on the metal vent / inducer housing → HSI → low fire. No secondary drain to prime.
Rapid red
Twinning / 24V phasing
TWIN circuit or 24 V phasing.
1 Is this cabinet actually twinned?
On a standalone York TM8T, nothing belongs on the TWIN terminal. A leftover jumper throws this. TWIN terminal empty on a standalone.
Expect: TWIN empty on a single cabinet.
2 Twinned pair must be the same IFC family
Twinned units must be the same family and IFC revision. Mixing this plate with a communicating sister SKU will not twin.
Expect: Same model family, same IFC, kit installed per the twinning sheet.
3 Phasing and 24 V
Twinning errors that survive a correct kit are 24 V phasing or a broken twin lead. Measure both cabinets before you change an IFC.
Expect: In-phase 24 V. Continuous twin lead.
Rapid amber
Flame sense < 1.5 µA
Weak µA. Normal ~3.7; lockout < 0.1.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on York TM8T during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Rod, ground, manifold.
Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live York TM8T display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
4 amber
Y without G
Cool call missing G.
1 Is the wheel free?
Spin the York TM8T blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Stat wiring.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data.
Expect: Command present. Motor amps in range, not locked.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
1 red
Flame sensed, no call for heat
Flame with valve off.
1 Shut the gas cock first
On York TM8T the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Leaking valve.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
2 red
Pressure switch stuck closed
Draft switch made with inducer off.
1 Unplug the switch with the inducer off
On York TM8T this code is the switch made when the inducer is not running. Unplug that switch only. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
2 Water in the hose vs a welded switch
Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Expect: Hose empty. Switch opens with no draft.
3 IFC input last
If the switch ohms open, the hose is dry, and the code does not change with the harness off, the York TM8T IFC input is shorted. Do not keep swapping switches. Unplug the switch. Water in the inducer hose from a long metal run can fake this — still not a 96% collector.
Expect: Known-good open switch + open harness = code gone. If not, IFC.
3 red
PS failed to close after inducer
Metal-vent draft will not prove. This is not a 96% trap call.
1 Prove inducer and the live code
Do not pull power — that clears the York TM8T active code. Write 3 red. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Inducer spinning and 120 VAC.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
4 red
Limit open
Airflow or overfire. Also check the board fuse.
1 Airflow before you touch the limit
On York TM8T a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). TM8V: VS heat CFM menu. TM8X/Y: taps if that is the motor in the cabinet.
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the York TM8T blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Filter, 80% A-coil on top, wheel.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Board fuse.
Expect: Manifold on plate. Limit closed when cool.
5 red
Rollout open
Flame containment. Manual reset.
1 Treat this as flame outside the exchanger
Do not reset the York TM8T rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Exchanger, burners, blocked metal flue. Reset only after the cause.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on York TM8T is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
6 red
PS opened 4 times this call
Intermittent metal-vent draft. One-hour lockout.
1 Prove inducer and the live code
Do not pull power — that clears the York TM8T active code. Write 6 red. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Wind, cold chimney, inducer wheel, hose. Not a trap siphon.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
7 red
Flame not established after 3 tries
Ignition retries exceeded.
1 Watch one full try — do not reset
Write the York TM8T code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI, gas, rod, ground.
Expect: W1 → W2 → Limit
2 Gas and the valve
Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence.
Expect: Inlet and manifold on the plate. 24 VAC only during trial.
3 Flame prove, then the lockout timer
Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.
Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
8 red
Flame lost 5 times
Flame dropped after prove.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on York TM8T during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. µA, gas, draft when the blower starts.
Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live York TM8T display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
9 red
Reversed polarity / grounding
L1/N or ground.
1 Hot and neutral at the IFC, not the disconnect
On York TM8T polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot/neutral at the IFC, burner ground.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
10 red
Flame sensed, no call (some boards)
Same as 1-red on later revisions.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on York TM8T during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Door card. Valve leak.
Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live York TM8T display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
11 red
Limit open >5 min · hard lockout
Blower never reclosed the limit.
1 Airflow before you touch the limit
On York TM8T a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Blower running? VS harness or tap motor actually spinning.
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the York TM8T blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).
Expect: Manifold on plate. Limit closed when cool.
12 red
Open igniter circuit
HSI path open.
1 Ohms at the igniter, then at the IFC
On York TM8T measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms and 120 VAC during trial.
Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
Steady red
Control failure
Internal IFC fault.
1 Write the live code and watch one cycle
On York TM8T read JCI / Coleman-York IFC · green / amber / red LED before you pull power. Write Steady red exactly. Watch one full sequence and note which step dies. Power and fuse, then the board.
Expect: W1: Inducer → draft/pressure switch on the metal vent / inducer housing → HSI → low fire. No secondary drain to prime.
2 Prove the circuit this code names
Use the York TM8T door card and the test points on this plate. Isolate the named switch, sensor, or output with a meter — do not swap the IFC first.
Expect: A measured open, short, or out-of-range reading — not a guess.
3 Confirm with a number, then the next part
If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.
Expect: Vent: Category I metal. Spillage at the inducer inlet / draft path is a fail. No PVC trap.
Workflows
3-red on TM8T
York 80%, no heat.
1 Prove the call and the live code
Metal vent. Chimney / inducer / common vent.
Expect: Write whatever JCI / Coleman-York IFC · green / amber / red LED is showing. Active LED repeats until cleared or 24 V is removed. Write color + count first.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
TM8V is the VS cousin — same 3-red, different motor.
Expect: W2: High fire, still Category I. Wind and shared chimneys show up here as 3-red / 6-red.
3 Confirm with a number, then the next part
TM8V is the VS cousin — same 3-red, different motor.
Expect: Vent: Category I metal. Spillage at the inducer inlet / draft path is a fail. No PVC trap. · Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Vent
Category I metal. Spillage at the inducer inlet / draft path is a fail. No PVC trap.
Flame sense
Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
LED
Same color language as TM9V. Physics behind 3-red are not.
Gotchas
- TM8V is already in the bench as 80% VS.
Related plates
Install this plate
Install York TM8T as JCI 80% · two-stage or single · multi-speed · Cat I.
JCI 80% · two-stage or single · multi-speed · Cat I
This plate — not the sister SKU
- Not TM8V 80% VS. Not TM9T 96%.
- TM8V is already in the bench as 80% VS.
IFC on this door
- Same flash table as TM9V: slow green idle, slow amber heat, red 1–12, rapid red twinning, rapid amber <1.5 µA, 4 amber = Y without G, steady red = control.
- 3-red / 2-red / 6-red are still the pressure / draft switch — but the physics are metal-vent draft, not a drowned collector.
- 4-red is still limit + board fuse. Airflow path follows whatever blower this cabinet actually has (VS menu on TM8V, taps on some TM8X/Y).
Hardware
- AFUE: 80% · Cat I metal
First fire
- 1Metal vent. Chimney / inducer / common vent.
- 2TM8V is the VS cousin — same 3-red, different motor.
Do not on York TM8T
- Not TM8V 80% VS. Not TM9T 96%.
- TM8V is already in the bench as 80% VS.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- York residential gas furnacesLiterature searchTM9 / TM8 family listing (Coleman / Luxaire share the JCI IFC). UPGNet holds the I/O.Open manufacturer PDF
- York / Bosch Home ComfortLiterature searchSearch York TM8T on the maker’s literature page.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Residential limited warranty
dealerYork furnace warranty
Registered TM8 / TM9 furnace warranty · Dealer claims portal
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal