York
8 red
LockoutFlame lost 5 times
Flame dropped after prove.
Walk 8 red in Diagnose
5 plates — walk the one on the cabinet
First check
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on York TM8T during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. µA, gas, draft when the blower starts.
Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
The rest of the walkthrough is Diagnose.
On the plates
- µA while running — want ~3.7 µA, warning <1.5, drop-out <0.1.
- Gas pressure sag when other appliances fire. Valve that will not hold.
- Draft that collapses when the blower comes on (limit/PS cluster).
- µA, gas sag, draft collapse when the blower starts on that heat tap.
- µA, gas, draft when the blower starts.