York
2 red
LockoutPressure switch stuck closed
Draft switch made with inducer off.
Walk 2 red in Diagnose
5 plates — walk the one on the cabinet
First check
1 Unplug the switch with the inducer off
On York TM8T this code is the switch made when the inducer is not running. Unplug that switch only. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
The rest of the walkthrough is Diagnose.
On the plates
- Unplug that switch. If the code changes, the switch is welded or the hose is holding residual draft / water.
- Two-stage: identify which switch (low vs high tap). Do not tee them.
- IFC input shorted — only after the switch ohms open.
- Unplug the switch. Water in the hose. Which of the two switches?
- Unplug the switch. Water in the inducer hose from a long metal run can fake this — still not a 96% collector.
- This is Category I metal vent. There is no 96% collector or PVC trap to prime.
- Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.