11 red

Lockout

Limit open >5 min · hard lockout

Blower never moved enough air to reclose the limit.

Walk 11 red in Diagnose

5 plates — walk the one on the cabinet

First check

1 Airflow before you touch the limit

On York TM8T a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Blower running? VS harness or tap motor actually spinning.

Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

The rest of the walkthrough is Diagnose.

On the plates

  • Blower actually running on the heat call? VS motor harness and IFC CFM setting.
  • Wheel off the shaft, seized motor, or a door-switch/fuse that killed the motor while the limit was open.
  • Cycle 24 VAC only after airflow is restored. Repeating 11-red is not a bad limit.
  • Is the tap motor actually running? Capacitor / ECM module / wheel.
  • Heat tap too low for this cabinet + coil.
  • Cycle 24 VAC only after airflow is real.
  • Blower running? VS harness or tap motor actually spinning.