York
10 red
HazardFlame sensed, no call (some boards)
Same as 1-red on later revisions.
Walk 10 red in Diagnose
5 plates — walk the one on the cabinet
First check
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on York TM8T during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Door card. Valve leak.
Expect: Flame sense: Normal ~3.7 µA DC. Warning < 1.5 µA. Lockout < 0.1 µA.
The rest of the walkthrough is Diagnose.
On the plates
- Read the door card on THIS IFC. 1-red vs 10-red is a revision split, not two different physics.
- Gas valve leak / slow close. Shut the cock.
- Door card on THIS IFC. Valve leak.
- Door card. Valve leak.