York
1 red
HazardFlame sensed, no call for heat
Flame with valve de-energized.
Walk 1 red in Diagnose
5 plates — walk the one on the cabinet
First check
1 Shut the gas cock first
On York TM8T the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Leaking valve.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
The rest of the walkthrough is Diagnose.
On the plates
- Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
- Rod shorted to ground or IFC flame circuit.
- Treat as hazard until the valve is proven closed.
- Shut the cock. Leaking valve is a hazard.
- Shut the cock. Leaking valve.