Lockout

Low PS open at HIGH inducer speed

On VA / Endeavor cards that split low-pressure: the LPS did not close while the inducer is on high. This is not TA ‘45 = all low PS.’

Walk 45 in Diagnose

8 plates — walk the one on the cabinet

First check

1 Prove inducer and the live code

Do not pull power — that clears the Rheem R801S active code. Write 45. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

Expect: 120 VAC at the inducer on a heat call. Wheel turning.

If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

The rest of the walkthrough is Diagnose.

On the plates

  • Intake pipe, low-fire hose, inducer low, trap.
  • Attic intakes ice. This is the Rheem 45 people confuse with Carrier lockout 45.
  • Do not treat 45 as ‘all pressure switches’ or as VA high-inducer LPS.
  • Confirm the door card on THIS cabinet before you treat 45 as intake/low-fire.
  • High-inducer LPS hose, inducer actually on high, vent load at high speed.
  • 58/59 first if stored.
  • Cap, liner, common-vented water heater, inducer wheel.
  • PS hose to the inducer housing.