Models
Rheemfurnace

R801S

Classic 80 · single- or two-stage · PSC / CT · Cat I

Rheem/Ruud 80% S-suffix (R801S single, R802S two-stage). Metal vent. PSC or CT — not the R801V VS EcoNet motor. 45 is chimney draft.

Not R801V / R802V VS EcoNet 80%. Not R96TA 96%.

AFUE

80% · Cat I metal

Blower

PSC or CT. Not R801V constant CFM.

This board

Rheem 2-digit IFC (80% VS)

  • Digits match the 96% list. Physics do not. 45 / 57 are metal-vent draft, not PVC intake/exhaust.
  • 11 failed ignition, 12 low flame, 13 flame lost, 14 unexpected flame, 22 limit, 26 reversed polarity, 33 rollout, 45 draft / low PS, 57 high draft / PS, 61 blower, 10 one-hour lockout.
  • No 58/59 condensate pair on this furnace. Those codes belong to 96% drain / water switches. Seeing them means the wrong cabinet or the wrong board.

Write the two-digit code before a power cycle.

Universal swap

Read the silk

Classic 80% Rheem. 50A55 / S9200U only if the silk is already that module.

Silk: 50A55 · 62-24084-82

White-Rodgers

  • 50A55-843

    If the silk is already a 50A50 / 50A55.

ICM

Honeywell

  • S9200U1000

    If the silk is already a 50A55 (S9200U lists 50A55-843).

  • R801V VS EcoNet board. A 96% Rheem IFC.

After you pull the dead card

  1. 1Kill power. Photograph the silk-screen part number on the dead board before you pull it.
  2. 2Match staging (1 vs 2 vs modulating), igniter (carbide / nitride / spark), and motor (PSC / ECMx / 9-speed tap / serial VS).
  3. 3Set heat-off delay and any 80+/90+ jumper to the door card. Prove one full try and flame µA before you leave.
  4. 4Metal vent. Prove draft.

Field wiring

Written landings for Rheem R801S. Not a factory schematic.

Furnace · single-stage 24V
R / C / W / Y / GGas furnace

Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC → transformer → R120V in, 24V out
  2. 2Call. Stat W → IFC W~24 VAC
  3. 3Draft. IFC → inducer → PS close120V motor, 24V prove
  4. 4Ignite. IFC → HSI120 VAC
  5. 5Gas. IFC → valve~24 VAC
  6. 6Flame. Rod → IFCµA DC
  7. 7Blow. IFC → heat speedAfter flame prove

This indoor

Classic 80% 24V. E1/E2 stay empty.

24V single-stage heat

Door card is one-stage. Twin terminal empty unless the job is actually twinned.

Wall thermostat

Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.

  • R24V hot from the IFC24V
  • CCommon24V
  • WHeat24V
  • YCool — also starts the outdoor24V
  • GFan24V

Furnace IFC

Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.

  • RHot to the stat24V
  • CCommon — must reach the outdoor24V
  • WHeat call24V
  • YCool in / cool out24V
  • GBlower24V
  • TWINEmpty unless twinned24V

Landing

  • 24VIFC Rstat R

    ~24 VAC hot

  • 24VIFC Cstat Coutdoor C

    Common

  • 24VStat WIFC W

    Heat. Stays in this cabinet.

  • 24VStat YIFC Youtdoor Y

    Cool / contactor

  • 24VStat GIFC G

    Fan. Does not go outdoors.

IFC harness — single-stage heat

After W arrives. This is the gas train, not the thermostat strip.

Transformer + fuse

120V primary. 24V secondary. Dark stat = fuse / door / transformer first.

  • L1 / N120V to the IFCLine
  • XFMR24V to R24V
  • FUSEOn the IFC24V

24V safety chain

Door, limit, rollout in series. Open anywhere kills heat.

  • DOORInterlock24V
  • LIMITMain limit — rise / no airflow24V
  • ROLLOUTManual reset. Do not jumper and leave24V

Inducer + one pressure switch

W → inducer 120V → PS closes → IFC continues. One hose, one switch.

  • IND120V from the IFC to the inducerLine
  • PS24V prove back to the IFC24V
  • HOSESingle hose. Do not add a second because two-stage boards have two.24V

HSI + single valve

Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.

  • HSI120V hot-surface igniter — not 24VLine
  • VALVE24V to the single solenoid24V
  • FLAMEµA DC on the rod. Not a 24V circuit24V

PSC blower + run cap

Heat / cool / park taps on the motor. The cap is on this blower — not the outdoor dual can.

  • HEATHeat speed tap24V
  • COOLCool speed tap24V
  • PARKUnused leads parked24V
  • CAPRun capacitor on the blowerCap

Landing

  • LineL1IFCinducer

    120 VAC after W

  • 24VIFCPSIFC

    ~24 VAC prove. Open PS = no ignition.

  • LineIFCHSI

    120 VAC during trial

  • 24VIFCgas valve

    ~24 VAC after flame prove starts

  • 24VFlame rodIFC

    µA DC. Not 24V.

  • LineIFCblower

    120V tap + cap

Prove it

  • 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
  • W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.

Do not

  • Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
  • Do not hunt W2 / E8 / high-fire on a one-stage door.
  • TWIN must be empty on a standalone.

9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.

Sequence

  1. 1

    W

    Inducer → metal-vent prove (45/57 if the draft switch never closes) → HSI → valve. Chimney, liner, and common vent matter.

  2. 2

    Limits

    22 is airflow / overtemp. A coil on top of an 80% is still a dirty A-coil.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

10

One-hour lockout

lockout

Hardened ignition or draft retries.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Rheem R801S active code. Write 10. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Read the code that led here (11 / 45 / 57).

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

11

Failed ignition

lockout

Trial without prove.

  1. 1 Watch one full try — do not reset

    Write the Rheem R801S code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI, gas, rod, 24 VAC at the valve.

    Expect: W → Limits

  2. 2 Gas and the valve

    Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence.

    Expect: Manifold: Single-stage vs plate.

  3. 3 Flame prove, then the lockout timer

    Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.

    Expect: Stable µA after light-off. No new PS/limit code.

12

Low flame sense

warn

Weak µA.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Rheem R801S during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Rod, ground, manifold.

    Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold: Single-stage vs plate.

  3. 3 Prove it is not a switch opening

    Watch the live Rheem R801S display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

13

Flame lost

warn

Dropped after prove.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Rheem R801S during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Draft after blower-on, rod, gas.

    Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.

    Expect: Manifold: Single-stage vs plate.

  3. 3 Prove it is not a switch opening

    Watch the live Rheem R801S display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

14

Unexpected flame

hazard

Flame with valve off.

  1. 1 Shut the gas cock first

    On Rheem R801S the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Leaking valve.

    Expect: Flame dies when the cock is shut.

    If fail: Leaking valve. Replace. Do not leave the unit.

  2. 2 Rod and IFC flame circuit

    If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector.

    Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.

  3. 3 Confirm valve solenoids are actually off

    Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.

    Expect: 0 VAC at both solenoids after the call. No flame.

22

Limit open

warn

Airflow / overtemp.

  1. 1 Airflow before you touch the limit

    On Rheem R801S a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, VS heat CFM, coil on top of the 80%, rise.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Rheem R801S blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).

    Expect: Manifold: Single-stage vs plate.

26

Reversed polarity

lockout

L1/N or ground.

  1. 1 Hot and neutral at the IFC, not the disconnect

    On Rheem R801S polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot/neutral at the IFC.

    Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.

  2. 2 Burner-box and IFC ground

    Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.

    Expect: Near-zero ohms burner box to IFC ground screw.

  3. 3 Then flame and HSI

    Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.

    Expect: Code cleared. One clean light. µA in range.

33

Rollout

hazard

Flame containment. Manual reset.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Rheem R801S rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Exchanger, burners, flue / chimney. Spillage is a fail.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Rheem R801S is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

45

Draft / pressure switch OPEN

lockout

Metal-vent draft not proven. Chimney, liner, common vent, inducer — not a PVC intake and not a 96% trap.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Rheem R801S active code. Write 45. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Cap, liner, common-vented water heater, inducer wheel.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

57

High draft / pressure switch OPEN

lockout

Second draft prove on this 80% IFC language. Still metal vent, still not PVC.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Rheem R801S active code. Write 57. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Inducer, hose, chimney capacity.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

61

Blower

lockout

VS motor / CFM.

  1. 1 Is the wheel free?

    Spin the Rheem R801S blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Harness, static, wheel.

    Expect: Wheel free. Correct motor family for this IFC.

  2. 2 Command vs rotation

    Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data.

    Expect: Command present. Motor amps in range, not locked.

  3. 3 Static and the wrong motor

    High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.

    Expect: Static on the blower chart. Matching motor / shared-data card.

Workflows

45 on R801S

80% Rheem, no heat.

  1. 1 Prove the call and the live code

    Metal vent. 45 is draft / chimney. No 58/59 condensate pair.

    Expect: Write whatever Rheem 2-digit IFC (80% VS) is showing. Write the two-digit code before a power cycle.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    R801V is the VS EcoNet 80% — different motor, same chimney physics.

    Expect: Limits: 22 is airflow / overtemp. A coil on top of an 80% is still a dirty A-coil.

  3. 3 Confirm with a number, then the next part

    R801V is the VS EcoNet 80% — different motor, same chimney physics.

    Expect: Vent: Cat I metal. Spillage is a fail. No PVC intake story. · Drain: No 58/59. No collector trap. If those codes appear, wrong unit or wrong board.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Vent

Cat I metal. Spillage is a fail. No PVC intake story.

Drain

No 58/59. No collector trap. If those codes appear, wrong unit or wrong board.

Manifold

Single-stage vs plate.

Gotchas

  • R801V is already in the bench as the VS 80%. This is the S-suffix PSC/CT.

Related plates

Install this plate

Install Rheem R801S as Classic 80 · single- or two-stage · PSC / CT · Cat I.

Classic 80 · single- or two-stage · PSC / CT · Cat I

This plate — not the sister SKU

  • Not R801V / R802V VS EcoNet 80%. Not R96TA 96%.
  • R801V is already in the bench as the VS 80%. This is the S-suffix PSC/CT.

IFC on this door

  • Digits match the 96% list. Physics do not. 45 / 57 are metal-vent draft, not PVC intake/exhaust.
  • 11 failed ignition, 12 low flame, 13 flame lost, 14 unexpected flame, 22 limit, 26 reversed polarity, 33 rollout, 45 draft / low PS, 57 high draft / PS, 61 blower, 10 one-hour lockout.
  • No 58/59 condensate pair on this furnace. Those codes belong to 96% drain / water switches. Seeing them means the wrong cabinet or the wrong board.

Hardware

  • AFUE: 80% · Cat I metal
  • Blower: PSC or CT. Not R801V constant CFM.

First fire

  1. 1Metal vent. 45 is draft / chimney. No 58/59 condensate pair.
  2. 2R801V is the VS EcoNet 80% — different motor, same chimney physics.

Do not on Rheem R801S

  • Not R801V / R802V VS EcoNet 80%. Not R96TA 96%.
  • R801V is already in the bench as the VS 80%. This is the S-suffix PSC/CT.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • Rheem residential furnacesLiterature searchR96T / R96V / R801V / R802V / R98MV product cards. I/O is typically MyRheem / PTS dealer.Open manufacturer PDF
  • Rheem supportLiterature searchOwner docs and registration. Full I/O is not hosted as a public PDF for most Endeavor plates.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    dealer

    Rheem furnace warranty

    Registered Endeavor / Classic furnace warranty · Dealer claims portal

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal