R801V
80% · variable-speed · metal vent
Rheem 80% variable-speed, Category I metal vent. Same 2-digit language as the 96% IFCs (11, 22, 45, 57) but the physics are chimney and inducer — not PVC intake, not a collector, not a condensate trap. This furnace does not share 58/59 condensate with R96TA / R96VA.
Not R96TA / R96VA. A 45 here is chimney / liner / common-vent / inducer, not a drowned 96% collector. Not R802V (two-stage 80% — 45 vs 57 are low vs high draft on metal vent). If you see 58/59, you are on a 96% or a mis-applied board.
AFUE
80%
Staging
Single-stage 80% VS (R802V is the two-stage sibling)
Vent
Metal Category I — chimney, liner, common vent
Blower
VS ECM
Drain
No secondary / no 96% trap — 58/59 not expected
Sister SKU
Ruud U801V
This board
Rheem 2-digit IFC (80% VS)
- Digits match the 96% list. Physics do not. 45 / 57 are metal-vent draft, not PVC intake/exhaust.
- 11 failed ignition, 12 low flame, 13 flame lost, 14 unexpected flame, 22 limit, 26 reversed polarity, 33 rollout, 45 draft / low PS, 57 high draft / PS, 61 blower, 10 one-hour lockout.
- No 58/59 condensate pair on this furnace. Those codes belong to 96% drain / water switches. Seeing them means the wrong cabinet or the wrong board.
Write the two-digit code before a power cycle.
Universal swap
80% VS. Not a 50A55 80% drop-in. Old ICM288/292A only if that exact 62- number is on the board.
Silk: 62-24084-82 · 62-24140-04
- 50A55-843 ‘because 80%’. R802V two-stage board. A 96% Rheem IFC.
After you pull the dead card
- 1OEM 80% VS IFC. Prove metal-vent draft after the swap.
Field wiring
Written landings for Rheem R801V. Not a factory schematic.
Rheem / Ruud R96V / R98V / R98MV / R972V / R801V. EcoNet on E1/E2. R96TA / R801S stay on the 24V furnace diagram.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC120V
- 2Call. Data pair or 24V W → IFCBus or 24V
- 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
- 4Ignite. IFC → HSI → valve120V igniter
- 5Blow. IFC → serial ECMNo tap, no cap
This indoor
80% VS EcoNet. Metal vent.
EcoNet communicating
EcoNet control and a communicating outdoor (RA19AY class).
EcoNet control
E1/E2 data. R and C still feed the control.
- R24V hot24V
- CCommon24V
- E1EcoNetData
- E2EcoNetData
EcoNet IFC
E1/E2 to the outdoor. 24V strip still exists for a conventional job.
- E1EcoNetData
- E2EcoNetData
- R24V24V
- CCommon24V
Landing
- DataControl E1/E2IFC E1/E2outdoor E1/E2
EcoNet data
24V on an EcoNet-capable IFC
Conventional stat. Leave E1/E2 empty.
Conventional stat
W/W2/Y/G on the 24V strip.
- RHot24V
- CCommon24V
- WHeat24V
- YCool24V
- GFan24V
Landing
- 24VStat WIFC W · Stat Youtdoor Y
~24 VAC
IFC harness — communicating two-stage
Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.
Transformer + fuse
24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.
- L1 / N120VLine
- R / C24V strip24V
- FUSEOn the IFC24V
24V safety chain
Limit / rollout / door still open the heat path. Codes are on THIS IFC language.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Two-speed inducer + dual PS
Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.
- IND LO/HITwo-speed inducerLine
- LPSLow prove24V
- HPSHigh prove24V
HSI + two-stage valve
Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.
- HSI120V igniterLine
- MV / HV24V low / high solenoids24V
- FLAMEµA DC24V
Serial variable-speed ECM
IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.
- SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
- CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V
Landing
- LineCallIFCinducerprove
Low then high
- LineIFCHSIvalve
120V igniter, 24V or serial valve
- 24VFlame rodIFC
µA DC
- DataIFCserial blower
No F-taps. No PSC cap.
Prove it
- EcoNet control lists this furnace.
- R96TA / R801S do not have this bus.
Do not
- Do not land 24V Y on E1.
- Do not read TA 45 onto a VA door.
E1 / E2 are the published EcoNet pair.
Sequence
- 1
W
Inducer → metal-vent prove (45/57 if the draft switch never closes) → HSI → valve. Chimney, liner, and common vent matter.
- 2
Limits
22 is airflow / overtemp. A coil on top of an 80% is still a dirty A-coil.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
10
One-hour lockout
Hardened ignition or draft retries.
1 Prove inducer and the live code
Do not pull power — that clears the Rheem R801V active code. Write 10. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Read the code that led here (11 / 45 / 57).
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
11
Failed ignition
Trial without prove.
1 Watch one full try — do not reset
Write the Rheem R801V code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI, gas, rod, 24 VAC at the valve.
Expect: W → Limits
2 Gas and the valve
Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence.
Expect: Manifold: Single-stage vs plate.
3 Flame prove, then the lockout timer
Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.
Expect: Stable µA after light-off. No new PS/limit code.
12
Low flame sense
Weak µA.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Rheem R801V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Rod, ground, manifold.
Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold: Single-stage vs plate.
3 Prove it is not a switch opening
Watch the live Rheem R801V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
13
Flame lost
Dropped after prove.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Rheem R801V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Draft after blower-on, rod, gas.
Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold: Single-stage vs plate.
3 Prove it is not a switch opening
Watch the live Rheem R801V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
14
Unexpected flame
Flame with valve off.
1 Shut the gas cock first
On Rheem R801V the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Leaking valve.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
22
Limit open
Airflow / overtemp.
1 Airflow before you touch the limit
On Rheem R801V a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, VS heat CFM, coil on top of the 80%, rise.
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the Rheem R801V blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).
Expect: Manifold: Single-stage vs plate.
26
Reversed polarity
L1/N or ground.
1 Hot and neutral at the IFC, not the disconnect
On Rheem R801V polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot/neutral at the IFC.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
33
Rollout
Flame containment. Manual reset.
1 Treat this as flame outside the exchanger
Do not reset the Rheem R801V rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Exchanger, burners, flue / chimney. Spillage is a fail.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Rheem R801V is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
45
Draft / pressure switch OPEN
Metal-vent draft not proven. Chimney, liner, common vent, inducer — not a PVC intake and not a 96% trap.
1 Prove inducer and the live code
Do not pull power — that clears the Rheem R801V active code. Write 45. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Cap, liner, common-vented water heater, inducer wheel.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. PS hose to the inducer housing.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Do not cut a condensate trap. There is no secondary drain.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
57
High draft / pressure switch OPEN
Second draft prove on this 80% IFC language. Still metal vent, still not PVC.
1 Prove inducer and the live code
Do not pull power — that clears the Rheem R801V active code. Write 57. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer, hose, chimney capacity.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. On two-stage 80% this split is the R802V story — confirm you are not on that cabinet.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
61
Blower
VS motor / CFM.
1 Is the wheel free?
Spin the Rheem R801V blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Harness, static, wheel.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data.
Expect: Command present. Motor amps in range, not locked.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
Workflows
45 on R801V
No heat, inducer running, or a tech looking for a 96% trap.
1 Prove the call and the live code
This furnace has no secondary drain and does not use 58/59. Do not cut a condensate trap.
Expect: Write whatever Rheem 2-digit IFC (80% VS) is showing. Write the two-digit code before a power cycle.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Look at the metal vent and the inducer. Cap, liner, common vent, spillage.
Expect: Limits: 22 is airflow / overtemp. A coil on top of an 80% is still a dirty A-coil.
3 Confirm with a number, then the next part
Then the PS hose to the inducer housing. Common-vented water heater: run the tables before you change the switch. If the data plate is R802V, leave this page — 45 vs 57 are staged metal-vent draft there.
Expect: Vent: Cat I metal. Spillage is a fail. No PVC intake story. · Drain: No 58/59. No collector trap. If those codes appear, wrong unit or wrong board.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Vent
Cat I metal. Spillage is a fail. No PVC intake story.
Drain
No 58/59. No collector trap. If those codes appear, wrong unit or wrong board.
Manifold
Single-stage vs plate.
Gotchas
- U801V is the Ruud twin.
- R802V is the two-stage 80% sibling — same metal vent, 45 vs 57 as low vs high draft. It is not this chart.
- R96TA 45 is PVC intake / low-fire. Copying that playbook here wastes a day in the chimney.
- 58/59 on this job means you are not on an R801V — or someone installed a 96% board.
Related plates
Install this plate
Install R801V as 80% VS metal-vent. 45 is chimney / inducer. No 58/59 condensate pair.
Cat I metal vent · single-stage 80% VS · no secondary / no 96% trap
Vent
- Category I. 45 here is draft, not a drowned 96% collector.
- Ultra Low NOx SKUs have extra setup — read the plate. Do not use an R96T orifice chart.
First fire
- 1Confirm Cat I. W call. 45 must close. No trap to prime.
Do not on Rheem R801V
- Do not apply R96TA 58/59 drain steps.
- Do not treat R802V staged 45-vs-57 as this single-stage 80%.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- R801V product pageProduct pageEndeavor Classic 80% VS (UH shown). Confirm Ultra Low NOx vs standard on the plate.Open manufacturer PDF
- Rheem residential furnacesLiterature searchR96T / R96V / R801V / R802V / R98MV product cards. I/O is typically MyRheem / PTS dealer.Open manufacturer PDF
- Rheem supportLiterature searchOwner docs and registration. Full I/O is not hosted as a public PDF for most Endeavor plates.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Residential limited warranty
dealerRheem furnace warranty
Registered Endeavor / Classic furnace warranty · Dealer claims portal
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal