Models
Rheemfurnace

R96TA

Two-stage · 96% · multi-speed / CT · 2-digit IFC

Rheem/Ruud two-stage 96% with a constant-torque / multi-speed blower and a 2-digit IFC. Not EcoNet-required. 45 is low-pressure switch OPEN (intake / low-fire path on this TA board). 57 is high-pressure switch OPEN (exhaust / high-fire path). Rheem 45 is not Carrier 45 (Carrier 45 is control lockout).

Not R96VA / U96VA (variable-speed, EcoNet-capable; many VA/Endeavor door cards split low-pressure into 45 vs 46). Not R801V / R802V (80% metal Category I vent — same-looking digits, different 45/57 physics, no 58/59 condensate). Not R98V modulating Prestige.

AFUE

96% two-stage condensing

Staging

Two-stage valve · two-speed inducer

Blower

Multi-speed / constant-torque (CT) — not VS, not EcoNet motor

Display

2-digit IFC · door card in the blower

Tstat

Conventional 24V W1/W2 — EcoNet pair unused

Vent

PVC 2-pipe (intake + exhaust) · 96% collector / trap

Sister SKU

Ruud U96TA · R96TA060 and other TA cabinets

This board

Rheem/Ruud 2-digit IFC (TA / CT)

  • 0 or blank = standby (info). H = heating (status). These are not faults.
  • 10 one-hour ignition/PS lockout, 11 failed ignition, 12 low flame sense, 13 flame lost, 14 unexpected flame, 22 limit open, 26 reversed polarity, 33 rollout, 45 low PS OPEN, 57 high PS OPEN, 58/59 condensate / water, 61 blower, 93 internal control.
  • Carrier techs: 45 here is not Carrier 45. Carrier 45 is control lockout. Rheem 45 is the low-pressure switch open — intake / low-fire path on this TA board.
  • Codes sequence. 45 then 57 on the same call is inducer/vent, not two failed boards.

Display repeats the active code. Some boards store last faults in a menu — write what you see first. Power cycle clears the live code, not the cause.

Universal swap

No universal

Current TA / CT 2-digit IFC. ICM288 is 62-24084-82 HSI only. ICM292A is 62-24140-04 DSI only. Neither is this plate until the silk says so.

Silk: 62-24084-82 · 62-24140-04

White-Rodgers

ICM

Honeywell

  • 50A55-843. ICM288/292A ordered because the cabinet says Rheem.
  • R96VA EcoNet VS board. R98V modulating board.

After you pull the dead card

  1. 1Photograph the Rheem 62-xxxxx number. If it is not 62-24084-82 or 62-24140-04, order the OEM TA IFC.

Field wiring

Written landings for Rheem R96TA. Not a factory schematic.

Furnace · two-stage 24V
R / C / W1 / W2 / Y / GGas furnace

Two-stage conventional furnace. W1 low fire, W2 high fire. Outdoor staging is Y or Y1/Y2 — separate from the gas valve.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC → R120V / 24V
  2. 2Low. W1 → inducer LOW → LPS → HSI → valve LOWFirst fire
  3. 3High. W2 → inducer HIGH → HPS → valve HIGHSecond solenoid
  4. 4Flame. Rod → IFCµA DC both stages
  5. 5Blow. IFC → heat blowerAfter flame

This indoor

96% CT two-stage. E1/E2 stay empty. Not R96VA.

24V two-stage heat

Door has W1 and W2. Not Infinity. Not ComfortBridge.

Two-stage thermostat

A single-W stat never proves high fire. That is not a weak inducer.

  • R24V hot24V
  • CCommon24V
  • W1Low-fire heat24V
  • W2High-fire heat24V
  • Y / Y1Cool24V
  • Y2Outdoor high if the condenser is two-stage24V
  • GFan24V

Two-stage IFC

W2 is high fire. Do not tee the pressure-switch hoses because there are two stages.

  • RHot24V
  • CCommon to outdoor24V
  • W1Low fire24V
  • W2High fire24V
  • YCool out24V
  • GBlower / cool tap24V

Landing

  • 24VStat W1IFC W1

    Low fire

  • 24VStat W2IFC W2

    High fire. Missing W2 = stuck on low.

  • 24VStat YIFC Youtdoor Y

    Cool

  • 24VC throughout

    Common

IFC harness — two-stage heat

W1 then W2. Low-fire prove is not high-fire prove.

Transformer + fuse

Same 24V transformer as single-stage. Fuse still kills the whole strip.

  • L1 / N120VLine
  • XFMR24V to R24V
  • FUSEOn the IFC24V

24V safety chain

Door, limit, rollout. A limit trip is not an E9 / 32 pressure-switch story.

  • DOORInterlock24V
  • LIMITMain limit24V
  • ROLLOUTManual reset24V

Two-speed inducer + two pressure switches

W1 = inducer low + LPS. W2 = inducer high + HPS. Separate hoses. Do not tee.

  • IND LO120V low-speed inducerLine
  • IND HI120V high-speed inducerLine
  • LPSLow-fire prove24V
  • HPSHigh-fire prove24V
  • HOSESOne hose per switch. Never tee LPS and HPS24V

HSI + two-stage valve

Igniter 120V. Low solenoid on W1. Second solenoid on W2 after HPS closes.

  • HSI120V igniterLine
  • MV / LO24V low-fire solenoid24V
  • HV / HI24V high-fire solenoid24V
  • FLAMEµA DC on the rod24V

Constant-torque ECM

Tap / profile motor. Not serial VS. Not a PSC cap.

  • TAPSHeat / cool / adjust profiles on the IFC24V
  • COMMONMotor common back to the IFC24V

Landing

  • LineW1IFCinducer LOWLPS

    120V inducer, 24V prove

  • LineIFCHSIvalve LOW

    120V igniter, 24V low solenoid

  • 24VW2inducer HIGHHPSvalve HIGH

    Missing W2 = stuck on low

  • 24VFlame rodIFC

    µA DC

  • LineIFCheat blower

    After flame. Motor class on this plate.

Prove it

  • W1 then W2 at the IFC under a 2-heat call.
  • If it never stages, W2 is missing at the board — not a bad gas valve until that is proven.

Do not

  • Do not convert this to Infinity by landing W on a random terminal.
  • Do not apply AMVC / ARVT ComfortBridge menus or a memory card.

926T / 59TP6 / AR9T96 / GR9T96 / S9V2 / EL296E class. Same landing on 80% metal-vent cousins — the vent is not the wire.

Sequence

  1. 1

    W1

    Inducer low → 45 if the low/intake switch never closes → HSI → valve → 11 if no prove, 12/13 if flame is weak or drops.

  2. 2

    W2

    Inducer high → 57 if the high/exhaust switch never closes. Second-stage solenoid.

  3. 3

    Water

    58/59 point at the 96% drain / water switch. Do this before you replace 45/57 switches.

  4. 4

    Satisfied

    Valve off, post-purge, blower delay. Flame with the valve off is 14.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

0 / blank

Standby

info

No call. Info, not a fault.

  1. 1 Confirm this is not a fault

    On the Rheem R96TA this readout (0 / blank) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.

    Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.

    If fail: If the word never changes on a real call, the call is not reaching this IFC.

    If pass: The board is alive. Diagnose the comfort complaint, not this code.

  2. 2 Prove the call at the board

    Measure R to W / Y / G at the Rheem R96TA IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.

    Expect: Not a lockout. Confirm W1 at the IFC if the house is cold.

    If fail: Fix the stat, harness, or data pair before you change parts.

  3. 3 Watch one full sequence

    Leave power on. Watch Rheem/Ruud 2-digit IFC (TA / CT) through one cycle and write the first real fault that replaces this status word.

    Expect: W1: Inducer low → 45 if the low/intake switch never closes → HSI → valve → 11 if no prove, 12/13 if flame is weak or drops.

H

Heating

info

Status — a heat call is running.

  1. 1 Confirm this is not a fault

    On the Rheem R96TA this readout (H) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.

    Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.

    If fail: If the word never changes on a real call, the call is not reaching this IFC.

    If pass: The board is alive. Diagnose the comfort complaint, not this code.

  2. 2 Prove the call at the board

    Measure R to W / Y / G at the Rheem R96TA IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.

    Expect: Not a fault. If comfort is poor, watch for 45/57/22 while it runs.

    If fail: Fix the stat, harness, or data pair before you change parts.

  3. 3 Watch one full sequence

    Leave power on. Watch Rheem/Ruud 2-digit IFC (TA / CT) through one cycle and write the first real fault that replaces this status word.

    Expect: W1: Inducer low → 45 if the low/intake switch never closes → HSI → valve → 11 if no prove, 12/13 if flame is weak or drops.

10

One-hour ignition / PS lockout

lockout

Hardened ignition or pressure-switch retries. The board parked itself for about an hour.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Rheem R96TA active code. Write 10. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Read the code that led here (11 / 45 / 57). Do not just wait the hour.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Watch one full try after a controlled reset.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

11

Failed ignition

lockout

Trial without flame prove.

  1. 1 Watch one full try — do not reset

    Write the Rheem R96TA code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI glow and 120 VAC during warm-up.

    Expect: W1 → W2 → Water → Satisfied

  2. 2 Gas and the valve

    Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence. Gas cock, 24 VAC at the valve, manifold vs plate.

    Expect: Manifold: Low and high vs the Rheem rating plate.

  3. 3 Flame prove, then the lockout timer

    Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets. Rod, ground, crossover.

    Expect: Flame sense: µA per the door card. Rising while running is the goal.

12

Low flame sense

warn

Flame is present but µA is weak.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Rheem R96TA during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Rod oxide — non-scratch pad, not sandpaper.

    Expect: Flame sense: µA per the door card. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Chassis ground to burner box and IFC.

    Expect: Manifold: Low and high vs the Rheem rating plate.

  3. 3 Prove it is not a switch opening

    Watch the live Rheem R96TA display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Manifold / orifice / LP conversion.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

13

Flame lost

warn

Proved, then dropped.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Rheem R96TA during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Venting that starves the flame after light-off and blower-on.

    Expect: Flame sense: µA per the door card. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Manifold sag under load.

    Expect: Manifold: Low and high vs the Rheem rating plate.

  3. 3 Prove it is not a switch opening

    Watch the live Rheem R96TA display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Rod position and ground.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

14

Unexpected flame

hazard

Flame sense with the valve off.

  1. 1 Shut the gas cock first

    On Rheem R96TA the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Leaking valve — replace, do not jump.

    Expect: Flame dies when the cock is shut.

    If fail: Leaking valve. Replace. Do not leave the unit.

  2. 2 Rod and IFC flame circuit

    If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Rod shorted or IFC flame circuit.

    Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.

  3. 3 Confirm valve solenoids are actually off

    Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.

    Expect: 0 VAC at both solenoids after the call. No flame.

22

Limit open

warn

Overtemp / airflow.

  1. 1 Airflow before you touch the limit

    On Rheem R96TA a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, coil, heat tap on this CT motor (61 if the motor is the cause).

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Rheem R96TA blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Rise vs plate. Overfire.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).

    Expect: Manifold: Low and high vs the Rheem rating plate.

26

Reversed polarity

lockout

L1/N swapped or chassis ground missing. HSI and flame sense both suffer.

  1. 1 Measure µA while it is running

    Do not clean first and guess. Series-µA the rod on Rheem R96TA during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Hot and neutral at the IFC, not just the disconnect.

    Expect: Flame sense: µA per the door card. Rising while running is the goal.

  2. 2 Rod, ground, then gas

    Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Burner-box ground screw. Painted screw, missing star washer.

    Expect: Manifold: Low and high vs the Rheem rating plate.

  3. 3 Prove it is not a switch opening

    Watch the live Rheem R96TA display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.

    Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.

33

Rollout

hazard

Flame containment. Manual reset.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Rheem R96TA rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Exchanger, burners, flue, blocked secondary / collector. Reset only after the cause is fixed. Recurring 33 is a CO / fire call.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Rheem R96TA is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

45

Low pressure switch OPEN

lockout

Intake / low-fire draft not proven on this TA board. One switch, one hose — not the VA 45-vs-46 split.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Rheem R96TA active code. Write 45. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Intake pipe, low-fire hose, inducer low, trap.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Attic intakes ice. This is the Rheem 45 people confuse with Carrier lockout 45.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Do not treat 45 as ‘all pressure switches’ or as VA high-inducer LPS.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

57

High pressure switch OPEN

lockout

Exhaust / high-fire draft not proven.

  1. 1 Prove the high-fire call

    Write the live Rheem R96TA code before you pull power. Confirm this IFC is actually commanded to high — W2 at the board, or the staging timer has expired. Exhaust termination, high-fire hose, inducer high speed.

    Expect: R to W2 ~24 VAC (conventional) or a high-stage request on a communicating stat.

    If fail: No high request → thermostat / staging / menu. Not a high-fire pressure switch.

    If pass: Go to step 2. Do not jump the high-fire switch to ‘see if it runs.’

  2. 2 Prove the inducer actually went high

    Listen and amp the inducer on low vs high. No speed-up → IFC high output or inducer winding. Speed-up and this code still live → high-fire PS path (hose, switch, vent). 45 then 57 together: shared collector/vent problem, not two switches.

    Expect: Inducer current and collector draft rise on high.

    If fail: Measure 120 VAC on the high-speed inducer lead during the high call. 0 V = IFC. Voltage + dead motor = inducer.

  3. 3 Isolate the HIGH hose and switch

    High-fire hose on the high tap only — a tee with the low switch is the common first-install miss on this dual-switch plate. Blow the hose, confirm it is dry and downhill to the collector. Ohm the high-fire switch: it is NO and must close only on high draft.

    Expect: NO switch. Opens with hose off. Closes on high collector draft.

    If fail: Welded open, cracked hose, or water in the line. Replace the failed part — do not leave a jumper.

    If pass: Switch and hose good → step 4 (vent / condensate / IFC).

  4. 4 Vent, condensate, and the IFC input

    High fire needs more draft than a low-fire code ever saw. Check PVC size on this cabinet, shared chase, wind, ice, bird screen, and condensate backing into the collector only on high. If the switch closes on known draft and the code stays, the Rheem R96TA IFC input is the last call.

    Expect: Clear vent, dry collector, known-good switch, then IFC.

58 / 59

Condensate / water switch

lockout

96% drain or water switch.

  1. 1 Float and the pan

    On Rheem R96TA a drain / float code is water until proven otherwise. Pan full? Float stuck? Secondary drain piped? Trap, pump, slope, froze drain. Fix water before 45/57 parts.

    Expect: Pan dry after you clear it. Float moves freely.

  2. 2 Trap and the pump

    Indoor trap primed and flowing. Condensate pump actually pumping, check valve not stuck. On a furnace, a drowned collector will also throw PS codes — clear both. If 58/59 is stored with 45/57, pull the drain first — water makes both pressure switches lie.

    Expect: Trap flowing. Pump discharges. No water in the collector.

  3. 3 Then the switch circuit

    If the pan is dry and the code stays, ohm the float / condensate switch and the IFC input. Do not jump a wet-switch input as a repair.

    Expect: Switch closed when dry. Code gone.

61

Blower

lockout

Motor / CFM fault on the CT / multi-speed blower.

  1. 1 Is the wheel free?

    Spin the Rheem R96TA blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Harness, tap/profile, capacitor only if this cabinet is still PSC vintage.

    Expect: Wheel free. Correct motor family for this IFC.

  2. 2 Command vs rotation

    Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Do not apply VA ECM-comm checks to this CT motor.

    Expect: Command present. Motor amps in range, not locked.

  3. 3 Static and the wrong motor

    High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.

    Expect: Static on the blower chart. Matching motor / shared-data card.

93

Internal control

lockout

IFC self-fault.

  1. 1 Write the live code and watch one cycle

    On Rheem R96TA read Rheem/Ruud 2-digit IFC (TA / CT) before you pull power. Write 93 exactly. Watch one full sequence and note which step dies. Write every stored code first. 93 after 11/45/57 is often a drowned or hammered board, not a first-swap.

    Expect: W1: Inducer low → 45 if the low/intake switch never closes → HSI → valve → 11 if no prove, 12/13 if flame is weak or drops.

  2. 2 Prove the circuit this code names

    Line voltage, polarity (26), wet control from a 96% leak.

    Expect: A measured open, short, or out-of-range reading — not a guess.

  3. 3 Confirm with a number, then the next part

    If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.

    Expect: 45 vs 57: Two different switches. Two different hoses. TA does not use code 46.

Workflows

45 then 57

Gurgling inducer, no high fire, or no heat.

  1. 1 Prove the call and the live code

    58/59 stored? Pull the drain first. Water makes both pressure switches lie.

    Expect: Write whatever Rheem/Ruud 2-digit IFC (TA / CT) is showing. Display repeats the active code. Some boards store last faults in a menu — write what you see first. Power cycle clears the live code, not the cause.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    45 only: intake and low-fire hose. 57 only: exhaust and high-fire hose.

    Expect: W2: Inducer high → 57 if the high/exhaust switch never closes. Second-stage solenoid.

  3. 3 Confirm with a number, then the next part

    Both: inducer wheel, collector, shared PVC. Do not replace the IFC because you used a Carrier 45 definition. Carrier 45 is control lockout. Rheem 45 is low PS open. Do not apply an R96VA door card here. TA has no 45-vs-46 split — 45 is the low/intake path, not ‘LPS at high inducer speed.’

    Expect: 45 vs 57: Two different switches. Two different hoses. TA does not use code 46. · Manifold: Low and high vs the Rheem rating plate.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

11 into 10

No heat, one-hour lockout, or intermittent light-off.

  1. 1 Prove the call and the live code

    10 is hardened retries. Find the live code under it (11, 12/13, 45, 57).

    Expect: Write whatever Rheem/Ruud 2-digit IFC (TA / CT) is showing. Display repeats the active code. Some boards store last faults in a menu — write what you see first. Power cycle clears the live code, not the cause.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Stay for a full trial: inducer, HSI, valve click, flame, µA.

    Expect: W2: Inducer high → 57 if the high/exhaust switch never closes. Second-stage solenoid.

  3. 3 Confirm with a number, then the next part

    26 present? Fix polarity/ground before you condemn the igniter or rod. Do not sit on hourly resets.

    Expect: 45 vs 57: Two different switches. Two different hoses. TA does not use code 46. · Manifold: Low and high vs the Rheem rating plate.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

45 vs 57

Two different switches. Two different hoses. TA does not use code 46.

Manifold

Low and high vs the Rheem rating plate.

Flame sense

µA per the door card. Rising while running is the goal.

Polarity

L1 hot, N neutral at the IFC. 26 if reversed.

Gotchas

  • Ruud U96TA is the same IFC. R96TA060 is a cabinet size, not a different chart.
  • R96VA looks like this cabinet and is not this board story — VS motor, optional EcoNet pair, and many VA cards split 45/46.
  • R801V / R802V can show a 45 that is metal-vent draft, not a PVC intake. They do not share 58/59.
  • Rheem 45 ≠ Carrier 45. Swapping the IFC for a ‘control lockout’ is how TA boards get wasted.

Related plates

Install this plate

Install R96TA as 24V two-stage 96% CT. EcoNet pair unused. 45 is the whole low/intake path — no 45-vs-46 split.

Cat IV PVC · two-stage · CT / multi-speed · 2-digit IFC · 24V W1/W2

IFC vs sister

  • Door card 45 = low / intake PS. Many TA cards do not split 45 vs 46 the way R96VA does.
  • 58/59 are condensate on this 96% collector. Prime the trap.
  • CT motor, not the VA serial VS. EcoNet terminals stay empty on a straight 24V job.

Vent

  • PVC 2-pipe. Ruud U96TA is the badge twin.
  • Use the R96T I/O (MyRheem / PTS dealer) for pipe lengths — public site does not host the full I/O PDF.

First fire

  1. 1W1 then W2. 45/57 are low vs high draft. 58/59 = drain.
  2. 2Set CT heat profile. Rise vs the R96TA chart.

Do not on Rheem R96TA

  • Do not read R96VA 45-vs-46 onto this TA card.
  • Do not apply Bryant/Carrier 45 (control lockout) to Rheem 45 (low PS).

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • R96TA product pageProduct pageClassic Plus 96% two-stage CT (R96T / R96TA).Open manufacturer PDF
  • Rheem residential furnacesLiterature searchR96T / R96V / R801V / R802V / R98MV product cards. I/O is typically MyRheem / PTS dealer.Open manufacturer PDF
  • Rheem supportLiterature searchOwner docs and registration. Full I/O is not hosted as a public PDF for most Endeavor plates.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    dealer

    Rheem furnace warranty

    Registered Endeavor / Classic furnace warranty · Dealer claims portal

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal