R96VA
Two-stage · 96% · variable-speed · EcoNet-capable
Rheem/Ruud two-stage 96% variable-speed, EcoNet-capable. Same cabinet family as R96TA but a VS blower and an optional EcoNet data pair. Door cards on VA / Endeavor often split the low-pressure path: 45 = LPS open at HIGH inducer speed, 46 = LPS open at LOW inducer speed, 57 = high-pressure switch open.
Not R96TA (no 45-vs-46 split on many TA cards; CT motor not VS; EcoNet pair unused). Not R98V modulating Prestige — an EcoNet stat on R96VA is optional; on R98V it is native.
AFUE
96% two-stage condensing
Staging
Two-stage valve · two-speed inducer
Blower
Variable-speed ECM — not the TA CT / multi-speed motor
Control
2-digit IFC · EcoNet data pair optional
Tstat
24V W fallback on many jobs · EcoNet pair when used
Vent
PVC 2-pipe · 96% collector / trap (58/59 still apply)
Sister SKU
Ruud U96VA · R962V / Endeavor VA siblings
This board
Rheem 2-digit IFC (VA / Endeavor)
- Read THIS door card. VA / Endeavor often split low-pressure: 45 LPS open at HIGH inducer speed, 46 LPS open at LOW inducer speed, 57 high PS open, 93 internal.
- Also on this IFC: 10 one-hour lockout, 11 failed ignition, 12 low flame, 13 flame lost, 14 unexpected flame, 22 limit, 26 reversed polarity, 33 rollout, 58/59 condensate, 61 blower.
- Do not apply the R96TA rule ‘45 = all low PS’ blindly. On many VA cards 45 is high-inducer LPS, 46 is low-inducer LPS.
- EcoNet pair (when landed) is data, not 24V. A blank EcoNet stat is not automatically a dead IFC.
Write the two-digit code before a power cycle. Stat history if EcoNet is the thermostat. Board menu if equipped.
Universal swap
VS / EcoNet-capable. No 50A55. Old Rheem ICM numbers almost never apply.
Silk: 62-24084-82 · 62-24140-04
- 50A55-843 / 50M56X-843. R96TA CT board. R98V EcoNet modulating.
After you pull the dead card
- 1OEM VA / Endeavor IFC. If EcoNet is in play, stay on the OEM communicating card.
Field wiring
Written landings for Rheem R96VA. Not a factory schematic.
Rheem / Ruud R96V / R98V / R98MV / R972V / R801V. EcoNet on E1/E2. R96TA / R801S stay on the 24V furnace diagram.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC120V
- 2Call. Data pair or 24V W → IFCBus or 24V
- 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
- 4Ignite. IFC → HSI → valve120V igniter
- 5Blow. IFC → serial ECMNo tap, no cap
This indoor
96% VS. EcoNet E1/E2 or 24V. Not R96TA.
EcoNet communicating
EcoNet control and a communicating outdoor (RA19AY class).
EcoNet control
E1/E2 data. R and C still feed the control.
- R24V hot24V
- CCommon24V
- E1EcoNetData
- E2EcoNetData
EcoNet IFC
E1/E2 to the outdoor. 24V strip still exists for a conventional job.
- E1EcoNetData
- E2EcoNetData
- R24V24V
- CCommon24V
Landing
- DataControl E1/E2IFC E1/E2outdoor E1/E2
EcoNet data
24V on an EcoNet-capable IFC
Conventional stat. Leave E1/E2 empty.
Conventional stat
W/W2/Y/G on the 24V strip.
- RHot24V
- CCommon24V
- WHeat24V
- YCool24V
- GFan24V
Landing
- 24VStat WIFC W · Stat Youtdoor Y
~24 VAC
IFC harness — communicating two-stage
Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.
Transformer + fuse
24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.
- L1 / N120VLine
- R / C24V strip24V
- FUSEOn the IFC24V
24V safety chain
Limit / rollout / door still open the heat path. Codes are on THIS IFC language.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Two-speed inducer + dual PS
Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.
- IND LO/HITwo-speed inducerLine
- LPSLow prove24V
- HPSHigh prove24V
HSI + two-stage valve
Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.
- HSI120V igniterLine
- MV / HV24V low / high solenoids24V
- FLAMEµA DC24V
Serial variable-speed ECM
IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.
- SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
- CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V
Landing
- LineCallIFCinducerprove
Low then high
- LineIFCHSIvalve
120V igniter, 24V or serial valve
- 24VFlame rodIFC
µA DC
- DataIFCserial blower
No F-taps. No PSC cap.
Prove it
- EcoNet control lists this furnace.
- R96TA / R801S do not have this bus.
Do not
- Do not land 24V Y on E1.
- Do not read TA 45 onto a VA door.
E1 / E2 are the published EcoNet pair.
Sequence
- 1
W1 / low
Inducer low → 46 if the low-inducer LPS never closes (VA split). HSI → valve → 11/12/13 if flame fails.
- 2
W2 / high
Inducer high → 45 if the high-inducer LPS never closes on cards that split 45/46 → 57 if the high-pressure / exhaust switch never closes.
- 3
Water
58/59 still mean 96% drain. Pull water before you chase 45/46/57 parts.
- 4
EcoNet
Optional. Many VA jobs still run 24V W. Data-pair polarity matters only when the EcoNet stat is the control.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
10
One-hour lockout
Hardened ignition or PS retries.
1 Watch one full try — do not reset
Write the Rheem R96VA code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. Read the code under it (11, 45, 46, 57). Do not just wait the hour.
Expect: W1 / low → W2 / high → Water → EcoNet
2 Gas and the valve
Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence.
Expect: Manifold: Low and high vs plate.
3 Flame prove, then the lockout timer
Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.
Expect: Stable µA after light-off. No new PS/limit code.
11
Failed ignition
Trial without prove.
1 Watch one full try — do not reset
Write the Rheem R96VA code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI, gas, rod, 24 VAC at the valve.
Expect: W1 / low → W2 / high → Water → EcoNet
2 Gas and the valve
Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence. Same prove logic as TA — the motor and the 45/46 card are what changed.
Expect: Manifold: Low and high vs plate.
3 Flame prove, then the lockout timer
Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.
Expect: Stable µA after light-off. No new PS/limit code.
12
Low flame sense
Weak µA.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Rheem R96VA during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Rod, ground, manifold.
Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold: Low and high vs plate.
3 Prove it is not a switch opening
Watch the live Rheem R96VA display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
13
Flame lost
Dropped after prove.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Rheem R96VA during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Vent after blower-on, manifold, rod.
Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold: Low and high vs plate.
3 Prove it is not a switch opening
Watch the live Rheem R96VA display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
14
Unexpected flame
Flame with valve off.
1 Shut the gas cock first
On Rheem R96VA the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Leaking valve.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
22
Limit open
Overtemp / airflow.
1 Airflow before you touch the limit
On Rheem R96VA a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). VS heat CFM, filter, coil, rise.
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the Rheem R96VA blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. 61 if the VS motor is the cause — this is not a TA tap motor.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).
Expect: Manifold: Low and high vs plate.
26
Reversed polarity
L1/N or ground.
1 Hot and neutral at the IFC, not the disconnect
On Rheem R96VA polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot/neutral at the IFC. Chassis ground.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
33
Rollout
Flame containment. Manual reset.
1 Treat this as flame outside the exchanger
Do not reset the Rheem R96VA rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Exchanger, burners, flue. Do not keep resetting.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Rheem R96VA is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
45
Low PS open at HIGH inducer speed
On VA / Endeavor cards that split low-pressure: the LPS did not close while the inducer is on high. This is not TA ‘45 = all low PS.’
1 Prove inducer and the live code
Do not pull power — that clears the Rheem R96VA active code. Write 45. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Confirm the door card on THIS cabinet before you treat 45 as intake/low-fire.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. High-inducer LPS hose, inducer actually on high, vent load at high speed.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. 58/59 first if stored.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
46
Low PS open at LOW inducer speed
LPS did not close on low inducer. This is the VA low-fire / low-inducer half of the split TA never printed.
1 Prove inducer and the live code
Do not pull power — that clears the Rheem R96VA active code. Write 46. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Low-inducer LPS path, intake, trap, inducer low speed.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Do not swap the 45 switch first because a TA chart said ‘45 is low.’
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
57
High pressure switch OPEN
High-pressure / exhaust switch open.
1 Prove inducer and the live code
Do not pull power — that clears the Rheem R96VA active code. Write 57. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Exhaust, high-fire hose, inducer high.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. 46 vs 45 vs 57 are three different moments — write the order.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
58 / 59
Condensate / water
96% drain or water switch.
1 Float and the pan
On Rheem R96VA a drain / float code is water until proven otherwise. Pan full? Float stuck? Secondary drain piped? Trap, pump, slope, ice. Water first, then 45/46/57.
Expect: Pan dry after you clear it. Float moves freely.
2 Trap and the pump
Indoor trap primed and flowing. Condensate pump actually pumping, check valve not stuck. On a furnace, a drowned collector will also throw PS codes — clear both.
Expect: Trap flowing. Pump discharges. No water in the collector.
3 Then the switch circuit
If the pan is dry and the code stays, ohm the float / condensate switch and the IFC input. Do not jump a wet-switch input as a repair.
Expect: Switch closed when dry. Code gone.
61
Blower
VS motor / CFM fault.
1 Is the wheel free?
Spin the Rheem R96VA blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Harness, VS comms at the motor, static.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. A TA CT motor will not run correctly on this IFC.
Expect: Command present. Motor amps in range, not locked.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
93
Internal control
IFC self-fault.
1 Write the live code and watch one cycle
On Rheem R96VA read Rheem 2-digit IFC (VA / Endeavor) before you pull power. Write 93 exactly. Watch one full sequence and note which step dies. Stored stack first. Wet board, polarity (26), persistent input.
Expect: W1 / low: Inducer low → 46 if the low-inducer LPS never closes (VA split). HSI → valve → 11/12/13 if flame fails.
2 Prove the circuit this code names
Do not confuse 93 with an EcoNet-stat blank.
Expect: A measured open, short, or out-of-range reading — not a guess.
3 Confirm with a number, then the next part
If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.
Expect: Door card: 45 vs 46 printed as high-inducer LPS vs low-inducer LPS on VA/Endeavor. Photograph it.
Workflows
46 vs 45
No heat, no high fire, or a VA that ‘looks like a TA 45.’
1 Prove the call and the live code
Read the door card. On many VA / Endeavor boards 46 is LPS open at LOW inducer, 45 is LPS open at HIGH inducer.
Expect: Write whatever Rheem 2-digit IFC (VA / Endeavor) is showing. Write the two-digit code before a power cycle. Stat history if EcoNet is the thermostat. Board menu if equipped.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Do not apply R96TA ‘45 = all low PS’ blindly.
Expect: W2 / high: Inducer high → 45 if the high-inducer LPS never closes on cards that split 45/46 → 57 if the high-pressure / exhaust switch never closes.
3 Confirm with a number, then the next part
46 only: low inducer, intake, low LPS hose, trap. 45 only (VA split): high inducer actually running, high-inducer LPS path. 57: high-pressure / exhaust switch. 58/59 stored? Water first.
Expect: Door card: 45 vs 46 printed as high-inducer LPS vs low-inducer LPS on VA/Endeavor. Photograph it. · EcoNet pair: Data, not 24 VAC. Polarity. Unused pair on a 24V job should not be landed on W.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
EcoNet stat blank
Communicating stat dark or ‘no heat’ with an EcoNet pair landed.
1 Prove the call and the live code
R96VA still has 24V W fallback on many jobs. Confirm whether this house is EcoNet-as-thermostat or 24V with a spare data pair.
Expect: Write whatever Rheem 2-digit IFC (VA / Endeavor) is showing. Write the two-digit code before a power cycle. Stat history if EcoNet is the thermostat. Board menu if equipped.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
24 VAC at R/C. Then data-pair polarity — EcoNet is not W.
Expect: W2 / high: Inducer high → 45 if the high-inducer LPS never closes on cards that split 45/46 → 57 if the high-pressure / exhaust switch never closes.
3 Confirm with a number, then the next part
A blank stat is not a reason to convert the furnace to 24V and walk away if the job is supposed to be EcoNet. Board 2-digit codes still mean draft / ignition. 45/46/57 did not become comm codes.
Expect: Door card: 45 vs 46 printed as high-inducer LPS vs low-inducer LPS on VA/Endeavor. Photograph it. · EcoNet pair: Data, not 24 VAC. Polarity. Unused pair on a 24V job should not be landed on W.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Door card
45 vs 46 printed as high-inducer LPS vs low-inducer LPS on VA/Endeavor. Photograph it.
EcoNet pair
Data, not 24 VAC. Polarity. Unused pair on a 24V job should not be landed on W.
Motor
VS ECM. A TA CT motor is the wrong part.
Manifold
Low and high vs plate.
Gotchas
- R96TA techs will treat every 45 as intake/low-fire. On this door card 45 is often high-inducer LPS and 46 is low.
- EcoNet on R96VA is optional. EcoNet on R98V is the system. Do not use the Prestige playbook here.
- Ruud U96VA / R962V wear the same VA story.
- 58/59 still exist — this is still 96% PVC, not R802V metal vent.
Related plates
- rheem-r96taCT / multi-speed cousin. No 45-vs-46 split on many TA cards; 45 is the whole low/intake path. EcoNet pair unused.
- rheem-r98vModulating 98% Prestige / Endeavor. EcoNet stat is native, not optional. 45/57 are draft at a firing rate, not a two-switch tee.
- rheem-r802vTwo-stage 80% VS. Same 45/57 digits, metal Category I vent, no 58/59, no 46 split.
Install this plate
Install R96VA as two-stage 96% VS, EcoNet-capable. Many VA/Endeavor cards split 45 vs 46.
Cat IV PVC · two-stage · VS ECM · EcoNet optional · 24V W fallback · 45 vs 46 vs 57
Door card
- 45 = LPS at high inducer on many VA cards; 46 = LPS at low inducer. Read THIS sticker — do not import TA 45.
- 58/59 still apply (96% collector / trap).
- EcoNet pair when used; 24V W is normal. EcoNet on VA is optional — on R98V it is native.
First fire
- 1W1 (or EcoNet heat): watch 46-path low prove, then high (45/57).
- 2VS heat CFM from the IFC / EcoNet, not a TA CT tap.
Do not on Rheem R96VA
- Do not treat this as R98V modulating Prestige.
- Do not apply R96TA ‘45 is the whole low path’ to a VA card that splits 45/46.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- Rheem residential furnacesLiterature searchR96T / R96V / R801V / R802V / R98MV product cards. I/O is typically MyRheem / PTS dealer.Open manufacturer PDF
- Rheem supportLiterature searchOwner docs and registration. Full I/O is not hosted as a public PDF for most Endeavor plates.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Residential limited warranty
dealerRheem furnace warranty
Registered Endeavor / Classic furnace warranty · Dealer claims portal
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal