Rheem
11
LockoutFailed ignition
Trial without prove.
Walk 11 in Diagnose
8 plates — walk the one on the cabinet
First check
1 Watch one full try — do not reset
Write the Rheem R801S code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI, gas, rod, 24 VAC at the valve.
Expect: W → Limits
The rest of the walkthrough is Diagnose.
On the plates
- HSI glow and 120 VAC during warm-up.
- Gas cock, 24 VAC at the valve, manifold vs plate.
- Rod, ground, crossover.
- HSI, gas, rod, 24 VAC at the valve.
- Same prove logic as TA — the motor and the 45/46 card are what changed.
Plates that use 11
Same number, other makers
11 on Rheem is not the same code on these plates.