Rheem
10
LockoutOne-hour lockout
Hardened ignition or draft retries.
Walk 10 in Diagnose
8 plates — walk the one on the cabinet
First check
1 Prove inducer and the live code
Do not pull power — that clears the Rheem R801S active code. Write 10. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Read the code that led here (11 / 45 / 57). Do not just wait the hour.
- Watch one full try after a controlled reset.
- Read the code under it (11, 45, 46, 57). Do not just wait the hour.
- Read the code that led here (11 / 45 / 57).
- Read 11 / 45 / 57 underneath.
- This is Category I metal vent. There is no 96% collector or PVC trap to prime.
- Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.