Amana
b2
LockoutMotor HP mismatch vs shared-data set
Connected motor horsepower does not match the value in the furnace shared-data set. Furnace will not operate.
Walk b2 in Diagnose
4 plates — walk the one on the cabinet
First check
1 Read the plug / card on THIS cabinet
On Amana AMVC96 the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Wrong replacement motor for this cabinet size.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
The rest of the walkthrough is Diagnose.
On the plates
- Wrong replacement motor for this cabinet size.
- Wrong memory card after an IFC swap (see d0/d4). An AMVC96 card is the usual miss on this new plate.
- Wrong memory card after an IFC swap (see d0/d4).
- Do not ‘make it work’ with a different HP ECM — ComfortBridge CFM tables are card-specific.
- Wrong replacement motor for this cabinet (AVPTC37 vs 59, etc.).
- Wrong memory card after a control swap (see d0/d4).
Plates that use b2
Same number, other makers
b2 on Amana is not the same code on these plates.