Amana
b0
LockoutECM blower not running
IFC commanded the serial ECM and does not detect it running.
Walk b0 in Diagnose
6 plates — walk the one on the cabinet
First check
1 Reseat the serial plug
On Amana AMVC96 this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. 14-pin harness seated at motor and IFC. No tap plugs on this motor.
Expect: Plug fully seated both ends. Correct motor for this cabinet.
The rest of the walkthrough is Diagnose.
On the plates
- 14-pin harness seated at motor and IFC. No tap plugs on this motor.
- 120 VAC to the motor, wheel free, no wet winding.
- Do not install an AR9T96 9-speed motor as a ‘cheaper ECM’ — it will not talk this serial bus.
- 14-pin harness at motor and IFC. No tap plugs.
- Do not install an AR9T96 9-speed or an AMVC96 motor of the wrong HP.
- Wheel free, 120 VAC to the motor.
- 14-pin harness at motor and control. No tap plugs.
- Do not install an AR9T96 9-speed motor in this air handler.