Daikin
b0
LockoutBlower motor not running
IFC commanded the serial ECM and does not see it run.
Walk b0 in Diagnose
4 plates — walk the one on the cabinet
First check
1 Reseat the serial plug
On Daikin DM80VC this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. 14-pin harness seated at motor and IFC.
Expect: Plug fully seated both ends. Correct motor for this cabinet.
The rest of the walkthrough is Diagnose.
On the plates
- 14-pin harness seated at motor and IFC.
- Wheel rub, open inductor on 3/4–1 HP motors, dead ECM.
- Do not install a GR9T96 tap motor.
- Harness, wheel, motor. Not a tap motor.