Precedent high-efficiency G/E · Reliatel · under 15 t

High-efficiency Precedent gas/electric. Same Reliatel diagnosis as YSC. Do not steal a YSC blower table — static and heat size differ.

Not YSC standard-efficiency blower charts. Not Voyager. Not Symbio unless that board is in the box.

Chart, codes, and first check stay open. The rest of the walkthrough is Diagnose — sign in on that button.

Size

Precedent high-efficiency, under 15 t on this chart.

Controls

Reliatel unless the control box is Symbio 700.

This board

Reliatel — Precedent YHC

  • Same Reliatel heat-fail / cool-fail / fan-fail as YSC.
  • Charging and blower tables are YHC, not YSC.

Reliatel last fail. Confirm YHC on the rating plate.

Field wiring

Written landings for Trane YHC. Not a factory schematic.

Packaged rooftop · gas / electric 24V
R / C / Y1 / Y2 / W1 / W2 / G · economizer in the hoodR-410A

One cabinet. Occupied/G is the indoor fan. Y1 is mechanical cool — unless the economizer takes the call. W is gas heat on the IGC, not on the compressor contactor.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC. Packaged: Y1 may go to the economizer, not the contactor; VFD enable is 24V, speed is 0–10 V.

Open manufacturer wiring diagram

Cabinet sequence

  1. 1Power. Disconnect → L1/L2/(L3) → unit transformer → RLine / 24V
  2. 2Fan. G / occupied → indoor blower proveBelt, ECM, or current switch
  3. 3Econo. Y1 → economizer module → damperMay satisfy cool with compressor off
  4. 4Cool. Y1 → contactor coil through HPS/LPS → compressor + OD fan~24 VAC coil
  5. 5Heat. W → IGC → inducer → PS → HSI → valve → flameHeat section only
  6. 6VFD. EN + 0–10 V → drive → indoor motorEnable 24V, speed analog

This indoor

Precedent YHC Reliatel. Same 24V, different blower table.

24V thermostat or DDC

Conventional stat or a BAS landing R C Y1 Y2 W G. Not Infinity ABCD.

Wall / DDC

Unoccupied with G open looks like a dead unit. Occupied first.

  • R24V hot from the unit transformer24V
  • CCommon24V
  • Y1Mechanical cool stage 124V
  • Y2Cool stage 2 if this cabinet is two-stage24V
  • W1Gas heat — goes to the IGC, not the contactor24V
  • W2Heat stage 2 if equipped24V
  • GIndoor fan / occupied24V

Unit controller

Cool, fan, economizer, safeties. Heat is handed to the IGC.

  • Y1 outContactor coil through HPS / LPS24V
  • G outIndoor blower / VFD enable24V
  • W outHeat call to IGC24V

IGC / ignition module

Burner compartment. LED is heat-only.

  • WHeat call from the unit board24V
  • MVGas valve 24V during trial24V
  • PSDraft / pressure switch24V
  • LIMLimit / rollout in series24V

Economizer (JADE W7220 / W7212 / factory FDD)

Damper can satisfy Y without the compressor. FDD lives on this module, not on the IGC.

  • ACTActuator 2–10 V (modulating) or 24 V floating — match the actuator that is on the shaft24V
  • FBKActuator feedback pot. JADE ACT RANGE is this sliding off the shaft24V
  • OA TOutside-air thermistor / SYLK OA sensor24V
  • RA TReturn-air thermistor when differential / enthalpy is used24V
  • MATMixed-air sensor — after the damper, before the evap24V
  • CO2DCV 0–10 V. Failed high = damper open all day24V
  • 24V / COMModule power from the unit transformer24V

Indoor-fan VFD (EcoBlue / Reliatel / aftermarket drive)

Enable and speed reference are 24V / 0–10 V from the unit board. Line is 3-phase at the drive.

  • L1 L2 L3Line at the drive — same 3-phase as the unitLine
  • U V WMotor leads. Megger with the drive disconnectedLine
  • ENEnable 24 VAC (or digital). No enable = board never asked24V
  • AI / 0–10Speed reference. 0 V with enable is a wire/board24V
  • ALMDrive fault contact back to the unit board24V

Landing

  • 24VStat Gunit boardindoor blower

    Occupied / fan. Prove this before heat or cool.

  • 24VStat Y1unit boardeconomizer OR contactor coil

    Mechanical cool only if the damper is not taking the call.

  • 24VContactor coil through HPS (LPS)

    ~24 VAC when the board commands the compressor

  • 24VStat Wunit boardIGC WinducerPSHSIvalve

    Heat path. Independent of Y.

  • 24VOA T / RA T / MAT / CO2economizer moduleACT 2–10 Vdamper

    FDD sensors and actuator. Not 24V Y.

  • LineUnit board EN + 0–10 VVFDindoor motor

    Enable 24V, speed analog, line 3-phase at the drive

  • LineL1 L2 L3disconnectcontactors / VFD

    Line. 3-phase rotation on 6–15 t.

Prove it

  • G / occupied: indoor fan running and proving.
  • Y1 at the unit board. Damper position vs command before you chase the contactor.
  • W at the IGC, then the heat LED.
  • VFD: enable 24V and 0–10 V under a high-fan call. Photograph the drive code before you cycle power.

Do not

  • Do not treat this as a split furnace + condenser. There is no line set.
  • Do not jump rollout, smoke detector, or fan-prove and walk away.
  • Do not apply a 59-series / GR9T96 door card to this IGC.
  • Do not throw a dual run cap at a VFD motor. Do not raise FLA to hide a dirty roof.

Written landings, not a factory schematic. Open the manufacturer wiring diagram from the plate’s literature link — FieldBench does not host or redraw it.

Sequence

  1. 1

    Call

    Occupied / G starts the indoor fan. Y1 is cool. W is gas heat. They are different boards in the same box.

  2. 2

    Fan

    Indoor blower must prove (belt, ECM, or current switch) before some controllers allow heat or cool.

  3. 3

    Econo

    If OA is below the economizer setpoint, the damper takes the cool call. Compressor stays off. That is not a dead contactor.

  4. 4

    Cool

    Y1 → unit board → compressor contactor through HPS (and LPS when equipped). OD fan on the same call or on head pressure.

  5. 5

    Heat

    W → IGC / ignition module: inducer → pressure switch → HSI → valve → flame rod → indoor blower on delay.

Faults on this IFC

Code, meaning, and the first check. Walk the rest in Diagnose — that is the seat.

Heat fail

Reliatel heat fail

lockout

Heat section did not prove.

1 Write the live code and watch one cycle

On Trane YHC read Reliatel — Precedent YHC before you pull power. Write Heat fail exactly. Watch one full sequence and note which step dies. Ignition module path. Reliatel reports the fail — the IGC/IGN still has the LED.

Expect: Call: Occupied / G starts the indoor fan. Y1 is cool. W is gas heat. They are different boards in the same box.

Walk the rest of Heat fail2 more checks after sign-in

Cool fail

Reliatel cool fail

lockout

Mechanical cool did not prove.

1 Write the live code and watch one cycle

On Trane YHC read Reliatel — Precedent YHC before you pull power. Write Cool fail exactly. Watch one full sequence and note which step dies. Economizer first, then contactor / HPS.

Expect: Call: Occupied / G starts the indoor fan. Y1 is cool. W is gas heat. They are different boards in the same box.

Walk the rest of Cool fail2 more checks after sign-in

Fan fail

Reliatel fan fail

lockout

Indoor fan did not prove.

1 Write the live code and watch one cycle

On Trane YHC read Reliatel — Precedent YHC before you pull power. Write Fan fail exactly. Watch one full sequence and note which step dies. YHC often has a different motor/VFD than YSC. Use this blower table.

Expect: Call: Occupied / G starts the indoor fan. Y1 is cool. W is gas heat. They are different boards in the same box.

Walk the rest of Fan fail2 more checks after sign-in

HPS

High pressure

lockout

Discharge / liquid opened the high-pressure switch.

1 Prove inducer and the live code

Do not pull power — that clears the Trane YHC active code. Write HPS. Is the inducer spinning on this call? Silent inducer is not a pressure switch. OD coil packed. Fan running and correct rotation on 3-phase.

Expect: 120 VAC at the inducer on a heat call. Wheel turning.

If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

Walk the rest of HPS2 more checks after sign-in

LPS

Low pressure / freeze

lockout

Suction dropped out the low-pressure switch.

1 Prove inducer and the live code

Do not pull power — that clears the Trane YHC active code. Write LPS. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Charge / leak. Filters and indoor coil first — a dirty rooftop ices like a starved piston.

Expect: 120 VAC at the inducer on a heat call. Wheel turning.

If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

Walk the rest of LPS2 more checks after sign-in

Contactor

No start / hum

lockout

Y1 at the board, compressor not running.

1 Is Y actually at the contactor?

On Trane YHC a silent outdoor is often no Y. Measure 24 VAC coil-to-C at the contactor on a cool call. 24 VAC across the coil. Then dual cap (if this chassis has one) or VFD / two-stage unload.

Expect: ~24 VAC at the coil when the indoor is calling.

If fail: Indoor Y / IFC / stat — not a capacitor.

Walk the rest of Contactor2 more checks after sign-in

Smoke

Smoke / firestat

hazard

Supply or return smoke detector, or a firestat, has the unit locked out.

1 Which detector tripped

On Trane YHC supply and return smoke, or a firestat, shut the unit down. Find which device is open before you reset. Welding and a dirty return nuisance-trip these. Reset only after you know why it tripped. Welding and dirty returns nuisance-trip these.

Expect: The tripped detector identified. Space not actually in alarm.

Walk the rest of Smoke2 more checks after sign-in

Phase

Phase loss / rotation

lockout

Three-phase monitor opened.

1 Three legs at the disconnect and the contactor

On Trane YHC measure L1 L2 L3 at the disconnect and at the compressor contactor. A phase monitor trips on loss, imbalance, or reverse rotation. Measure all three legs at the disconnect and at the contactor.

Expect: All three legs, nameplate voltage ±10%, phase monitor closed.

Walk the rest of Phase2 more checks after sign-in

Econo

Economizer FDD

warn

Start here when the hood is the complaint. Title 24 FDD classes: sensor, not-economizing, false-economizing, damper not modulating, excess OA.

1 Damper position vs command

On Trane YHC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Read the module in THIS hood (JADE W7220 / W7212 / Reliatel / Prodigy / factory FDD). Type the live LCD string — examples: MA SENS ERR, OA SENS ERR, CO2 SENS ERR, ACT ERROR.

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

Walk the rest of Econo2 more checks after sign-in

MA ERR

MA SENS ERR (JADE LCD example)

warn

JADE two-line LCD: MA / SENS ERR. Mixed-air sensor failed. This one alarms immediately on power-up — others wait the 60-minute setup window.

1 Damper position vs command

On Trane YHC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Probe mixed air after the damper vs MAT on the module.

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

Walk the rest of MA ERR2 more checks after sign-in

OA ERR

OA SENS ERR (JADE LCD example)

warn

JADE LCD: OA / SENS ERR (or OA SYLK ERR). Outside-air thermistor failed or lost SYLK. Board thinks the roof is 20 °F or 120 °F.

1 Which sensor is this code?

On Trane YHC OA ERR is a specific thermistor — indoor return/pipe, outdoor coil, discharge, or ambient. Unplug that sensor and ohm it vs the OEM temperature/resistance chart. Probe OA at the hood vs the module. Several degrees off is a sensor, not a damper.

Expect: Ohms move with temperature. Not open, not shorted.

Walk the rest of OA ERR2 more checks after sign-in

RA ERR

RA SENS ERR (JADE LCD example)

warn

JADE LCD: RA / SENS ERR. Return-air thermistor failed. Differential / enthalpy changeover compares OA to RA.

1 Damper position vs command

On Trane YHC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Probe RA in the return vs the module.

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

Walk the rest of RA ERR2 more checks after sign-in

CO2 ERR

CO2 SENS ERR (JADE LCD example)

warn

JADE LCD: CO2 / SENS ERR. DCV sensor failed or the 0–10 V input is floating. Damper holds open; compressor never runs.

1 Damper position vs command

On Trane YHC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Read CO2 in an empty space. 400–800 ppm typical empty retail. 2000 ppm empty is a failed sensor.

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

Walk the rest of CO2 ERR2 more checks after sign-in

ACT ERR

ACT ERROR (JADE LCD example)

warn

JADE LCD: ACT ERROR / ACT RANGE. Actuator did not follow command. Feedback pot off the shaft is the weekly.

1 Damper position vs command

On Trane YHC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Command min → 100%. 2–10 V (or 24 V floating) at the actuator vs blade travel.

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

Walk the rest of ACT ERR2 more checks after sign-in

FREEZE

FREEZING (JADE LCD example)

warn

JADE LCD: FREEZING. Mixed air below the low-limit. Damper drives shut; mechanical cool may lock.

1 Damper position vs command

On Trane YHC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. MAT vs a real probe. A failed MAT lying low is this, not a frozen DX coil.

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

Walk the rest of FREEZE2 more checks after sign-in

Not econ

Not economizing when it should

warn

OA is in the free-cooling window and the damper stayed shut. Title 24 FDD class.

1 Damper position vs command

On Trane YHC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Confirm OA really is below the high-limit / enthalpy changeover on THIS module (not a 55 °F guess).

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

Walk the rest of Not econ2 more checks after sign-in

False econ

Economizing when it should not

warn

Damper open with OA above changeover. Space hot, high OA bills, or wet coil.

1 Damper position vs command

On Trane YHC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. OA vs changeover setpoint. Sensor lying low (see OA T) is the usual.

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

Walk the rest of False econ2 more checks after sign-in

Excess OA

Excess outdoor air

warn

Damper open past the commanded minimum with no economizer or DCV request.

1 Damper position vs command

On Trane YHC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Commanded position vs blade. Feedback saying 80% when the board asked 15% is actuator/linkage.

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

Walk the rest of Excess OA2 more checks after sign-in

No mod

Damper not modulating

warn

Damper is two-position (0 or 100) instead of tracking 2–10 V. Title 24 FDD class.

1 Damper position vs command

On Trane YHC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. 2–10 V at the actuator while OA is in the window. 0 V or 24 V only = module output or a two-position actuator installed by mistake.

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

Walk the rest of No mod2 more checks after sign-in

VFD

VFD / indoor-fan drive

lockout

The indoor fan is a drive, not a contactor + cap. Type the keypad string: oC, Uv, ov, GF, oH, PF.

1 Read the drive before you cycle power

On Trane YHC photograph the VFD keypad or the unit-board fan alarm (OC, LU, OU, GF, OH, limp). Power-cycle wipes what you needed. Photograph the drive keypad before you cycle power. Yaskawa/ABB show oC / Uv / ov; EcoBlue / Reliatel may say fan fail instead.

Expect: Live drive code written down. Line voltage at L1/L2/L3 of the drive.

Walk the rest of VFD2 more checks after sign-in

Enable

VFD enable missing

warn

Drive has line voltage but will not run — the unit board never enabled it.

1 Read the drive before you cycle power

On Trane YHC photograph the VFD keypad or the unit-board fan alarm (OC, LU, OU, GF, OH, limp). Power-cycle wipes what you needed. 24 VAC (or the digital enable this drive uses) at the enable terminals while G / occupied / heat / cool is on.

Expect: Live drive code written down. Line voltage at L1/L2/L3 of the drive.

Walk the rest of Enable2 more checks after sign-in

0-10V

VFD speed reference

warn

Drive is enabled but stays at min Hz or 0 because analog / serial speed is missing.

1 Read the drive before you cycle power

On Trane YHC photograph the VFD keypad or the unit-board fan alarm (OC, LU, OU, GF, OH, limp). Power-cycle wipes what you needed. 0–10 VDC at the speed-reference pair under a high-fan call. Typical occupied cool is not 10 V — check the unit-board fan table.

Expect: Live drive code written down. Line voltage at L1/L2/L3 of the drive.

Walk the rest of 0-10V2 more checks after sign-in

oC

oC / OC — overcurrent

lockout

Keypad example: oC (Yaskawa) or OC. Output current trip. Locked rotor, dirty filters, or FLA set too low.

1 Read the drive before you cycle power

On Trane YHC photograph the VFD keypad or the unit-board fan alarm (OC, LU, OU, GF, OH, limp). Power-cycle wipes what you needed. Spin the wheel by hand (power off). Debris, seized bearing, belt wrapped.

Expect: Live drive code written down. Line voltage at L1/L2/L3 of the drive.

Walk the rest of oC2 more checks after sign-in

Uv

Uv / LU — undervoltage

lockout

Keypad example: Uv (Yaskawa) or LU. DC bus dropped. Incoming power or a missing phase.

1 Read the drive before you cycle power

On Trane YHC photograph the VFD keypad or the unit-board fan alarm (OC, LU, OU, GF, OH, limp). Power-cycle wipes what you needed. Three legs at the drive line terminals, under load. A single-phased 3-phase drive nuisances Uv / oC.

Expect: Live drive code written down. Line voltage at L1/L2/L3 of the drive.

Walk the rest of Uv2 more checks after sign-in

ov

ov / OU — overvoltage

lockout

Keypad example: ov (Yaskawa) or OU. DC bus high. Usually regen on decel, not a new drive.

1 Read the drive before you cycle power

On Trane YHC photograph the VFD keypad or the unit-board fan alarm (OC, LU, OU, GF, OH, limp). Power-cycle wipes what you needed. ov on shutdown = decel too fast; lengthen decel.

Expect: Live drive code written down. Line voltage at L1/L2/L3 of the drive.

Walk the rest of ov2 more checks after sign-in

GF

GF — ground fault

hazard

Keypad example: GF. Drive sees current to ground on the motor leads.

1 Read the drive before you cycle power

On Trane YHC photograph the VFD keypad or the unit-board fan alarm (OC, LU, OU, GF, OH, limp). Power-cycle wipes what you needed. Megger the motor with the drive disconnected. A wet rooftop motor after a rain is this code.

Expect: Live drive code written down. Line voltage at L1/L2/L3 of the drive.

Walk the rest of GF2 more checks after sign-in

oH

oH — heatsink overtemp

warn

Keypad example: oH. Drive thermal trip.

1 Read the drive before you cycle power

On Trane YHC photograph the VFD keypad or the unit-board fan alarm (OC, LU, OU, GF, OH, limp). Power-cycle wipes what you needed. Drive fan spinning. Heat sink packed with roof lint.

Expect: Live drive code written down. Line voltage at L1/L2/L3 of the drive.

Walk the rest of oH2 more checks after sign-in

PF

PF — input phase loss

lockout

Keypad example: PF. Missing or imbalanced incoming phase.

1 Three legs at the disconnect and the contactor

On Trane YHC measure L1 L2 L3 at the disconnect and at the compressor contactor. A phase monitor trips on loss, imbalance, or reverse rotation. L1 L2 L3 at the drive and at the disconnect. Tight lugs.

Expect: All three legs, nameplate voltage ±10%, phase monitor closed.

Walk the rest of PF2 more checks after sign-in

Limp

VFD limp / min Hz — fan prove

warn

Drive is running too slow to close the prove switch, so the unit board reports fan fail. Reliatel example: Fan Fail with the drive still at min Hz.

1 Read the drive before you cycle power

On Trane YHC photograph the VFD keypad or the unit-board fan alarm (OC, LU, OU, GF, OH, limp). Power-cycle wipes what you needed. Min-frequency / limp parameter vs the prove-switch setpoint (often ~0.07" on some Reliatel cabinets).

Expect: Live drive code written down. Line voltage at L1/L2/L3 of the drive.

Walk the rest of Limp2 more checks after sign-in

Drain

Condensate / float

warn

Float switch or tripped condensate opened 24V.

1 Float and the pan

On Trane YHC a drain / float code is water until proven otherwise. Pan full? Float stuck? Secondary drain piped? Roof drain pan, trap, and the overflow to the roof — not a furnace collector.

Expect: Pan dry after you clear it. Float moves freely.

Walk the rest of Drain2 more checks after sign-in

Workflows

First step is on the chart. The sequence after that is Diagnose.

No cool, YHC

Space hot. Indoor fan may or may not be running.

1 Prove the call and the live code

This is a packaged rooftop. There is no split outdoor to walk to. Cool, heat, and the economizer share this curb.

Expect: Write whatever Reliatel — Precedent YHC is showing. Reliatel last fail. Confirm YHC on the rating plate.

If fail: No call at the IFC → stat / harness. Do not change gas parts.

Continue this workflow2 more steps in Diagnose

No heat, YHC

Cool works or the space is cold on a W call.

1 Prove the call and the live code

Heat is the IGC / ignition module in the heat section — not the economizer board and not the compressor contactor.

Expect: Write whatever Reliatel — Precedent YHC is showing. Reliatel last fail. Confirm YHC on the rating plate.

If fail: No call at the IFC → stat / harness. Do not change gas parts.

Continue this workflow2 more steps in Diagnose

Economizer, YHC

Building hot with the compressor off, or high OA bills, or mixed air wrong.

1 Prove the call and the live code

Read the module in THIS hood (JADE W7220 / W7212 / Reliatel / Prodigy / factory FDD). Write the live alarm — OA T, MAT, CO2, ACT, not-economizing, excess OA.

Expect: Write whatever Reliatel — Precedent YHC is showing. Reliatel last fail. Confirm YHC on the rating plate.

If fail: No call at the IFC → stat / harness. Do not change gas parts.

Continue this workflow2 more steps in Diagnose

High static / limit / belt, YHC

Limit trips, noisy cabinet, or poor airflow on a rooftop.

1 Prove the call and the live code

Total external static vs the blower table for THIS tonnage and heat size. Rooftop ductboard and dirty 2" filters are the usual miss.

Expect: Write whatever Reliatel — Precedent YHC is showing. Reliatel last fail. Confirm YHC on the rating plate.

If fail: No call at the IFC → stat / harness. Do not change gas parts.

Continue this workflow2 more steps in Diagnose

VFD / indoor fan, YHC

Fan prove, no airflow, drive display in alarm, or EcoBlue / Reliatel limp.

1 Prove the call and the live code

Read the drive keypad (OC, LU, OU, GF, OH) or the unit-board fan alarm before you cycle 24V.

Expect: Write whatever Reliatel — Precedent YHC is showing. Reliatel last fail. Confirm YHC on the rating plate.

If fail: No call at the IFC → stat / harness. Do not change gas parts.

Continue this workflow2 more steps in Diagnose

Test points

Y1 at controller

~24 VAC on a mechanical-cool call. 0 V if the economizer is satisfying.

Contactor coil

~24 VAC when the board commands the compressor. 0 V with Y1 present = board or lockout.

HPS / LPS

Closed in the run circuit when pressures are legal. Open is a switch or a real pressure problem.

3-phase

All three legs, correct rotation. Nameplate voltage ±10%.

TES / static

External static vs the blower table for this tonnage — rooftops run dirty.

OA / MAT

Module reading vs a real thermometer at the hood and in the mixed-air stream.

Actuator

2–10 V (or 24 V floating) tracks commanded damper. Blade moves with voltage.

VFD enable

~24 VAC (or this drive’s digital enable) while G / occupied / a call is on.

VFD 0–10 V

Analog speed present under a high-fan call. 0 V with enable is a board/wire, not a motor.

IGC W

~24 VAC on a heat call.

Flame rod

µA DC per the IGC sticker in this heat section. Rising while running.

Manifold

Rating plate wins. Roof gas piping often starves high-fire.

Gotchas

  • Packaged rooftop — one nameplate. Do not pick a split furnace + condenser pair for this call.
  • Economizer can run the building without the compressor. Look at the damper before you condemn a scroll.
  • 3-phase rotation and a roof full of lint are the first two measurements, not a charge chart.
  • Type the live string in Diagnose. Examples: IGC 2-flash / 8-flash, JADE MA SENS ERR / ACT ERROR, Reliatel Fan Fail, VFD oC / Uv / GF. The sticker or LCD in THIS cabinet is the book.

Related plates

Install this plate

Install Trane YHC as Precedent high-efficiency G/E · Reliatel · under 15 t.

Precedent high-efficiency G/E · Reliatel · under 15 t

This plate — not the sister SKU

  • Not YSC standard-efficiency blower charts. Not Voyager. Not Symbio unless that board is in the box.
  • Packaged rooftop — one nameplate. Do not pick a split furnace + condenser pair for this call.
  • Economizer can run the building without the compressor. Look at the damper before you condemn a scroll.
  • 3-phase rotation and a roof full of lint are the first two measurements, not a charge chart.
  • Type the live string in Diagnose. Examples: IGC 2-flash / 8-flash, JADE MA SENS ERR / ACT ERROR, Reliatel Fan Fail, VFD oC / Uv / GF. The sticker or LCD in THIS cabinet is the book.

Controller on this rooftop

  • Same Reliatel heat-fail / cool-fail / fan-fail as YSC.
  • Charging and blower tables are YHC, not YSC.

Hardware

  • Size: Precedent high-efficiency, under 15 t on this chart.
  • Controls: Reliatel unless the control box is Symbio 700.

First fire

  1. 1This is a packaged rooftop. There is no split outdoor to walk to. Cool, heat, and the economizer share this curb.
  2. 2Prove 24 VAC Y1 at the unit controller under a cool call. Occupied/G first — a unoccupied shutdown looks like a dead compressor.
  3. 3Look at the economizer. Damper commanded open on cold OA? Mixed-air sensor lying? Compressor off by design is not a failed contactor.
  4. 4If the board is actually asking for mechanical cool: 24 VAC at the contactor coil, then cap, then rotation on 3-phase, then HPS/LPS, then pressures.
  5. 5Roof condenser: cottonwood, cardboard, hail guards packed with lint. High head here is dirt until proven otherwise.

Do not on Trane YHC

  • Not YSC standard-efficiency blower charts. Not Voyager. Not Symbio unless that board is in the box.
  • Packaged rooftop — one nameplate. Do not pick a split furnace + condenser pair for this call.
  • Economizer can run the building without the compressor. Look at the damper before you condemn a scroll.

Maker literature

Spec sheets open the manufacturer’s PDF. FieldBench does not host those files. Install I/O is often dealer-gated — the literature search is for that, not a homepage.

  • Open manufacturer wiring diagramWiring / I/OMaker I/O / wiring for this rooftop. Opens the manufacturer site — FieldBench does not host or redraw the schematic.Open manufacturer wiring diagram
  • Honeywell JADE W7220 economizer moduleWiring / I/OPublic module page for the FDD economizer in many 3–15 t hoods. Wiring silk is on the module — FieldBench does not host the I/O PDF.Open manufacturer wiring diagram
  • Trane e-Library (public search)Literature searchSearch the plate (S9V2, S9X2, XV20i). Full I/O often needs a dealer login.Open literature search

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • Residential limited warranty

    warranty sheet

    Trane furnace warranty hub

    Registered residential furnace warranty · Limited warranty certificate

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal